Plan Review Details - Permit 06090238
Plan Review Stops For Permit 06090238
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-10 Cont ID  
Sent By rmcdouga Date 2007-01-10 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2007-01-10 Time 14:12 Sent To  
Notes
2007-01-10 14:18:59BUILDING PROVISO
  
 1) IF EXISTING DOORS D01 AND D02 ON THE FIRST FLOOR ARE
 REMOVED, RELOCATED OR REPLACED, THEY SHALL BE REQUIRED
 TO COMPLY WITH FBC 3202.2 AND NOT OPEN INTO THE PUBLIC
 WAY.
  
 2) THE FIRST FLOOR ELEVATOR LOBBY MUST REMAIN
 UNCONDITIONED SPACE, UNLESS THE ROLL UP OVERHEAD DOOR
 IS REPLACED WITH A DOOR COMPLYING WITH 2004 FBC
 13-403.1ABC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-11 Cont ID  
Sent By rmcdouga Date 2006-12-11 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2006-12-11 Time 12:37 Sent To  
Notes
2006-12-11 13:53:48DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY
 THE DESIGNER OF RECORD. SEE FS 471 AND FAC
 61G15-23.002.
  
 3) 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3 . DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY. THE DOORS AT THE
 STAIRWAY AND ELEVATOR LOBBY CAN NOT SWING OUT ACROSS
 THE PROPERTY LINE INTO THE PUBLIC WAY.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE NEWEXTERIOR
 DOORS. SEE FS 553.842 AND DCA RULE 9B-72.
  
 5) THE PRODUCT APPROVAL IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. SEE 2004
 FBC ( CITY AMENDMENTS) 106.3.3.
  
 6) INDICATE THE SWING OF THE NEW EXTERIOR DOUBLE DOOR
 (D03) ON THE FIRST FLOOR PLAN ON SHEET A-1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By rmcdouga Date 2006-09-26 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2006-09-26 Time 15:51 Sent To  
Notes
2006-09-26 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT AN EXISTING FIRST FLOOR PLAN,
 INDICATING THE WALL LOCATIONS AND
 PROPERTY LINES PRIOR TO ANY DEMOLITION
 OR REMODELING.
  
 3) PLEASE CLARIFY IF THE 100 SQFT FIRST
 FLOOR ELEVATOR LOBBY IS EXISTING.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By rmcdouga Date 2006-09-14 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2006-09-14 Time 06:59 Sent To  
Notes
2006-09-14 00:00:00DENIED BY BUILDING
  
 1) PROVIDE BUILDING INFORMATION. SPECIFY
 THE TYPE OF CONSTRUCTION, BUILDING
 HEIGHT, NUMBER OF STORIES, WHETHER
 SPRINKLERED OR NOT.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) ENGINEER IS REQUIRED TO LEGIBLY
 INDICATE THEIR LICENSE NUMBER IN
 ADDITION TO NAME AND ADDRESS ON EACH
 SHEET OF THE PLANS. THIS INFORMATION IS
 ALSO REQUIRED ON SIGNED AND SEALED
 LETTERS. SEE FAC 61G15-23.002.
  
 4) OVERHEAD DOOR WILL NOT COMPLY WITH
 ENERGY CODE REQUIREMENTS IF THE LOBBY IS CONDITIONED
 SPACE OR IS NOT SEPARATED
 FROM CONDITIONED SPACE. SEE FBC 13-403
 AND 13-406.
  
 5) THE PLANS MUST BE REVISED TO SHOW THE
 TYPE OF DOORS. A LETTER IS NOT
 SUFFICIENT.
  
 6) SUBMIT PLANS THAT INDICATE THE
 EXISTING BUILDING WALL LOCATIONS PRIOR
 TO ANY DEMOLITION OR REMODELING.
  
 7) SPECIFY HOW TERMITE PROTECTION WILL
 BE PROVIDED ON THE PLANS. FBC 1816.1
  
 8) EACH ENCLOSED ELEVATOR LOBBY AND EACH
 ELEVATOR MACHINE ROOM SHALL BE PROVIDED
 WITH AN APPROVED SMOKE DETECTOR LOCATED
 IN THE LOBBY CEILING IN ACCORDANCE WITH
 NFPA 72. SMOKE DETECTORS MAY BE
 INSTALLED IN ANY HOISTWAY, AND SHALL BE
 INSTALLED IN HOISTWAYS WHICH ARE
 SPRINKLERED. WHEN THE SMOKE DETECTOR IS
 ACTIVATED, ALL AFFECTED ELEVATORS SHALL
 OPERATE IN CONFORMANCE WITH NFPA 72,
 SECTION 3?9.3. FBC 3002.8
  
 9) THE ELEVATOR MUST COMPLY WITH
 ACCESSIBILITY REQUIREMENTS OF FBC 2007.
  
 10) ELEVATOR MACHINE ROOMS AND MACHINERY
 SPACES SHALL BE ENCLOSED WITH
 CONSTRUCTION HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THE REQUIRED RATING
 OF THE HOISTWAY ENCLOSURE SERVED BY THE
 MACHINERY. OPENINGS SHALL BE PROTECTED
 WITH ASSEMBLIES HAVING A FIRE-RESISTANCE
 RATING NOT LESS THAN THAT REQUIRED FOR
 THE HOISTWAY ENCLOSURE DOORS. FBC 3006.4
  
 11) PROVIDE DETAILS AND THE TESTED FIRE
 ASSEMBLY TYPES AND FILE NUMBERS FOR ALL
 FIRE RATED ASSEMBLIES.
  
 12)INDICATE ON THE PLANS THAT THE
 WALLS ADJACENT TO THE EGRESS STAIRS ARE
 FIRE RATED WALLS. THE DASHED LINE
 INDICATING RATED WALLS SHOULD CONTINUE
 AROUND THE STAIR SHAFT.
  
 13) FBC 3202.2 ENCROACHMENTS INTO THE
 PUBLIC RIGHT-OF-WAY ABOVE GRADE AND
 BELOW 8 FEET (2438 MM) IN HEIGHT SHALL
 BE PROHIBITED EXCEPT AS PROVIDED FOR IN
 SECTIONS 3202.2.1 THROUGH 3202.2.3 .
 DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
 SUBMIT A SITE PLAN SHOWING THE LOCATION
 OF THE PROPERTY LINES.
  
 14) SUBMIT PRODUCT APPROVALS FOR
 EXISTING STOREFRONT DOORS THAT ARE TO BE RELOCATED.
 THEY MUST COMPLY WITH IMPACT
 AND WINDLOAD REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-10 Cont ID  
Sent By rmcdouga Date 2007-01-10 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2007-01-09 Time 15:06 Sent To  
Notes
2007-01-10 14:21:42OK PER D. PALMER 1/9/07

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2006-12-08 Time 19:22 Sent To  
Notes
2006-12-08 19:58:53***UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEWS WHICH
 STILL NEED TO BE ADDRESSED.
  
  
 1) NOTE:PLEASE SEE STILL MISSING REQUIRED DEDICATED
 CIRCUITS AND EQUIPMENT AS REQUIRED PER 620.22A, 620.23,
 AND 620.24 ETC.
 PLEASE COMPLETE PLANS THIS IS THE THIRD TIME FOR
 REQUEST OF THE ABOVE.
 PLEASE SEE THE FOLLOWING SECTIONS WHICH ARE BEING
 EXTRACTED FROM THE CODE IN ORDER TO HELP IN WHAT THE
 CODE REQUIRES.
  
 620.22 THE REQUIREMENTS IN 620.22(A) AND 620.22(B)
 SPECIFY THAT THE OVER-CURRENT DEVICES PROTECTING THE
 BRANCH CIRCUITS FOR ELEVATOR CAR LIGHTING AND
 HEATING/AIR CONDITIONING ARE TO BE LOCATED IN THE
 ELEVATOR MACHINE ROOM OR CONTROL ROOM OR IN THE
 ELEVATOR MACHINERY OR CONTROL SPACE. THIS REQUIREMENT
 FACILITATES EASE OF MAINTENANCE AND TROUBLESHOOTING AND
 CORRELATES WITH OTHER NORTH AMERICAN CODE REQUIREMENTS.
 SEE EXHIBIT 620.1.
  
 620.23 BRANCH CIRCUITS FOR MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING AND
 RECEPTACLE(S).
 (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT
 SHALL SUPPLY THE MACHINE ROOM OR CONTROL ROOM/MACHINERY
 SPACE OR CONTROL SPACE LIGHTING AND RECEPTACLE(S).
 REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD
 SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER.
 LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED TO THE
 LOAD SIDE OF A GFCI DEVICE OF ANY KIND, BECAUSE THE
 MACHINE ROOM LIGHTING COULD BE DE-ENERGIZED DURING
 CERTAIN FAULT CONDITIONS.
 (B) LIGHTING SWITCH. THE MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE LIGHTING SWITCH
 SHALL BE LOCATED AT THE POINT OF ENTRY.
 (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN
 EACH MACHINE ROOM OR CONTROL ROOM AND MACHINERY SPACE
 OR CONTROL SPACE.
 FPN:SEE ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS
 AND ESCALATORS, FOR ILLUMINATION LEVELS.
 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
 (A) SEPARATE BRANCH CIRCUIT. A SEPARATE BRANCH CIRCUIT
 SHALL SUPPLY THE HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
 REQUIRED LIGHTING SHALL NOT BE CONNECTED TO THE LOAD
 SIDE OF A GROUND-FAULT CIRCUIT INTERRUPTER.
 (B) LIGHTING SWITCH. THE LIGHTING SWITCH SHALL BE
 LOCATED SO AS TO BE READILY ACCESSIBLE FROM THE PIT
 ACCESS DOOR.
 (C) DUPLEX RECEPTACLE. AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, DUPLEX RECEPTACLE SHALL BE PROVIDED IN
 THE HOISTWAY PIT.
  
 THE RECEPTACLES REQUIRED BY 620.23 AND 620.24 ARE ALSO
 REQUIRED TO BE PROVIDED WITH GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL (SEE
 620.85). LUMINAIRES ARE NOT PERMITTED TO BE CONNECTED
 TO THE LOAD SIDE OF GFCI DEVICES. SEE ALSO THE
 COMMENTARY FOLLOWING 620.23(A).
 ANSI/ASME A17.1-1996, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
 LUMINAIRES IN PITS SHOULD BE MOUNTED SO THAT THE CAR OR
 COUNTERWEIGHT DOES NOT STRIKE THEM WHEN ON FULLY
 COMPRESSED BUFFERS. IT IS RECOMMENDED THAT LUMINAIRES
 BE MOUNTED IN THE CORNERS OF THE PIT.
  
 2) NOTE: PLEASE SEE NEW EMERGENCY AND EXIT LIGHTS NOW
 BEING SHOWN IN THIS SCOPE OF WORK SHALL INDICATE
 CIRCUITING AND MEET 700.12E. THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES
  
 3) NOTE: PLEASE SEE THAT THE ELEVATOR EQUIPMENT ROOM
 WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK
 UP LIGHT OF SOME SORT. PLEASE SEE THIS ILLUMINATION OF
 THE ELEVATOR EQUIPMENT AND CONTROLS IN IMPERATIVE IN
 THE EVENT OF A POWER FAILURE. PLEASE SEE 700.16 AS THE
 FIXTURE SHOWN IS NOT CLEAR.
 LS 101 7.8,7.9
  
 4) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WHICH
 REQUESTED THE APPROPRIATE VALUE BE APPLIED ON THE
 PERMIT APPLICATION. PLEASE KNOW A VALUE WILL BE
 ASSESSED FOR SCOPE OF WORK AS SHOWN OF ONE IS NOT
 SHOWN. THE VALUE AS SHOWN IS LOW FOR SCOPE OF WORK AS
 SHOWN ON PLANS.
 FBC 108.3.
  
 5) NOTE: PLEASE KNOW AS A NEW DESIGNER HAS NOW TAKEN
 OVER PROJECT, PLEASE SEE FS 553.80(2)(B).
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 15:02 Sent To  
Notes
2006-09-24 00:00:00*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SAME COMMENTS FROM
 PREVIOUS REVIEW AND NEW COMMENTS.
  
 1) NOTE:NO, SAME NOTE.
 PLEASE KNOW THIS ELECTRICAL SCOPE IS
 REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT AND SHOW ALL
 ELECTRICAL REQUIRED FOR THE NEW PROPOSED
 ELEVATOR AND ELEVATOR MACHINE ROOM.
 NFPA-70 620., 620.23,620.24 ETC
 STATE ELEVATOR CODE. NFPA-101 ETC.
  
 ** PLEASE SEE NOTE ON PLANS MENTIONS
 SEPARATE ELECTRICAL PERMIT ALREADY
 APPLIED FOR, HOWEVER THE ELECTRICAL
 PERMIT DONE WAS FOR "DEMO ONLY " OF SOME
 EXISTING ELECTRICAL.
  
 ALL ELECTRICAL PLANS FOR THIS SCOPE
 SHALL BE SUBMITTED UNDER THIS PERMIT.
  
 2) NOTE: NO, SAME NOTE, NO CHANGE MADE
 TO VALUE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE VALUE SHALL BE BASED
 ON ALL LABOUR AND MATERIALS EVEN OF ANY
 EQUIPMENT IS BEING OWNER SUPPLIED PER
 FBC108.3.
 PLEASEKNOW A VALUE MAY ALSO BE ASSESSEDD
 PER MARSHALL'S & SWIFT GUIDE AS ADOPTED
 BY THE FBC AND THIS OFFICE.
  
 3) NOTE:NO, PLEASE SEE FS 481.223(1)(A)
 WHICH DEFINES WHO CAN PROVIDE
 ARCHITECTURAL DOCUMENTATION.
 COULD NOT LOCATE AN LICENSEURE
 INFORMATION FOR SAID COMPANY AS SHOWN ON
 PLANS.
 PLEASE SEE 481.203, 481.229 (1)(C), AS
 THIS SCOPE MUST BE DONE BY AN ARCHITECT
 OR ENGINEER AND A "DESIGN" OR "DRAFTING"
 FIRM MAY NOT DO PLANS AS SHOWN AND
 SUBMITTED. PLEASE KNOW, THIS WAS
 CONFIRMED WITH THE STATE'S LEGAL COUNSEL
 TO THE FLORIDA BOARD OF ARCHITECTS ON
 9/22/06.
 PLEASE MAKE ADJUSTMENTS AND PLEASE KNOW,
 ONE SET OF PLANS ARE BEING RETAINED BY
 THIS OFFICE AT THE REQUEST OF THE
 BOARD'S LEGAL COUNSEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ANY DOCUMENTATION
 SIGNED,DATED AND SEALED BY THE ENGINEER
 SHALL CONTAIN MIN TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002. PLEASE
 SEE THE ARCHITECTURAL TITLE BLOCK IS NOT
 RELEVANT FOR THE ENGINEER.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE WITH REPSECT TO DESIGN
 PROFESSIONALS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 17:39 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 17:37 Sent To  
Notes
2006-09-17 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SUBMIT AND SHOW ALL
 ELECTRICAL REQUIRED FOR THE NEW PROPOSED
 ELEVATOR AND ELEVATOR MACHINE ROOM.
 NFPA-70 620., 620.23,620.24 ETC
 STATE ELEVATOR CODE. NFPA-101 ETC.
  
 ** PLEASE SEE NOTE ON PLANS MENTIONS
 SEPARATE ELECTRICAL PERMIT ALREADY
 APPLIED FOR, HOWEVER THE ELECTRICAL
 PERMIT DONE WAS FOR "DEMO ONLY " OF SOME
 EXISTING ELECTRICAL.
  
 ALL ELECTRICAL PLANS FOR THIS SCOPE
 SHALL BE SUBMITTED UNDER THIS PERMIT.
  
 2) NOTE: PLEASE SEE VALUE SAHLL BE BASED
 ON ALL LABOUR AND MATERIALS EVEN OF ANY
 EQUIPMENT IS BEING OWNER SUPPLIED PER
 FBC108.3.
 PLEASEKNOW A VALUE MAY ALOS BE ASSESSD
 PER MARSHALL'S & SWIFT GUIDE AS ADOPTED
 BY THE FBC AND THIS OFFICE.
  
 3) NOTE: PLEASE SEE ANY DOCUMENTATION
 SIGNED,DATED AND SEALED BY THE ENGINEER
 SHALL CONTAIN MIN TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002. PLEASE
 SEE THE ARCHITECTURAL TITLE BLOCK IS NOT
 RELEVANT FOR THE ENGINEER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-10 Cont ID  
Sent By mawillia Date 2007-01-10 Time 13:32 Rev Time 0.00
Received By mawillia Date 2007-01-10 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-12 Cont ID  
Sent By mwennerg Date 2006-12-12 Time 12:52 Rev Time 0.00
Received By mwennerg Date 2006-12-12 Time 12:52 Sent To  
Notes
2006-12-12 12:55:28***PROVISO***
  
 PLEASE NOTE THAT PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
  
  
 1) PLEASE REFER TO BUILDING COMMENT #2 REGARDING
 SIGNING AND SEALING REQUIREMENTS FOR ALL SHEETS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-28 Cont ID  
Sent By mawillia Date 2006-09-28 Time 15:36 Rev Time 0.00
Received By mawillia Date 2006-09-28 Time 15:36 Sent To  
Notes
2006-09-28 00:00:00*****DENIED*****
  
  
  
  
  
 PLAN REVIEW COMMENTS/CONCERNS OF
 09/19/2006 HAVE NOT BEEN ADDRESSED.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By mwennerg Date 2006-09-19 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2006-09-19 Time 15:08 Sent To  
Notes
2006-09-19 00:00:00***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, WORK SHALL COMPLY WITH NFPA 101,
 2003 EDITION SECTION 9.4.
  
 2) PLEASE PROVIDE INFORMATION REGARDING
 IF BUILDING IS PROTECTED BY AUTOMATIC
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
 IF SO, HOW WILL THIS WORK IMPACT
 REFERENCED SYSTEMS?
  
 3) PLEASE SEE OTHER COMMENT REGARDING
 REQUIRED SMOKE DETECTORS.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-02 Cont ID  
Sent By adarroug Date 2007-01-02 Time 16:58 Rev Time 0.00
Received By adarroug Date 2007-01-02 Time 16:58 Sent To  
Notes
2007-01-09 14:24:15TO "BOB"#14
2007-01-02 16:58:54WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 13:54 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 13:54 Sent To  
Notes
2006-12-08 16:50:25TO "BOB"#17
2006-11-21 13:55:31WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 16:21 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#16
2006-09-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-19 Cont ID  
Sent By mwennerg Date 2006-09-19 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2006-09-09 Time 19:13 Sent To  
Notes
2006-09-11 00:00:00TO "BOB"#14
2006-09-09 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-09-28 Time 11:11 Rev Time 0.20
Received By tgordon Date 2006-09-28 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-09-15 Time 11:03 Rev Time 0.30
Received By tgordon Date 2006-09-15 Time 11:03 Sent To  
Notes
2006-09-15 00:00:00*** DENIED ***
 1) PLEASE SHOW ON PLANS HOW THE ELEVATOR
 MACHINE ROOM WILL BE VENTED TO COMPLY
 WITH 2004 FBC 3006.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.