Plan Review Details - Permit 06090190
Plan Review Stops For Permit 06090190
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 14:00 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 13:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-26 Cont ID  
Sent By mjacobs Date 2006-09-26 Time 07:18 Rev Time 0.00
Received By mjacobs Date 2006-09-26 Time 06:11 Sent To PC
Notes
2006-09-26 00:00:00 
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) THE CLAIMED VALUAATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 2) ADDITIONAL PERMITS WILL BE REQUIRED
 FOR THE PAVERS DECK/BABY FENCE ALARMS
 ETC.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-03 Cont ID  
Sent By btrobaug Date 2006-10-03 Time 13:45 Rev Time 0.33
Received By btrobaug Date 2006-10-03 Time 12:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By btrobaug Date 2006-09-18 Time 13:03 Rev Time 0.33
Received By btrobaug Date 2006-09-18 Time 12:53 Sent To P
Notes
2006-09-18 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE POOL SPECIFICATIONS CALL FOR A GAS
 HEATER. THE ELECTRICAL SCHEMATIC
 INDICATES AN ELECTRICAL HEAT PUMP.
 PLEASE CORRELATE THE PLAN WITH ACTUAL
 PROPOSED WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-10-04 Cont ID  
Sent By mperson Date 2006-10-04 Time 10:46 Rev Time 0.00
Received By mperson Date 2006-10-04 Time 10:46 Sent To B
Notes
2006-10-04 00:00:00NOTE: PRIVIOUS COMMENTS ADRESSED,
 400,000 BTU GAS HEATER

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mperson Date 2006-09-21 Time 10:02 Rev Time 0.00
Received By mperson Date 2006-09-21 Time 10:02 Sent To B
Notes
2006-09-21 00:00:00REFERENCE PLUMBING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 15:20 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 15:20 Sent To E
Notes
2006-09-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 13:53 Sent To E
Notes
2006-09-14 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-09-26 Time   Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 14:17 Sent To  
Notes
2006-09-09 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-04 Cont ID  
Sent By mperson Date 2006-10-04 Time 10:45 Rev Time 0.33
Received By mperson Date 2006-10-04 Time 10:44 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mperson Date 2006-09-21 Time 09:52 Rev Time 0.33
Received By mperson Date 2006-09-21 Time 09:52 Sent To G
Notes
2006-09-21 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 SWIMMING
 POOLS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. PLEASE CORRELATE THE PRINTS FOR
 RESUBMITTAL. THE POOL SPECIFICATIONS
 INDICATE A GAS POOL HEATER AND THE
 ELECTRICAL SCHEMATIC INDICATES AN
 ELECTRIC POOL HEATER.
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED PROVIDE ONE COPY OF
 ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-12 Cont ID  
Sent By mmclean Date 2006-09-12 Time 17:20 Rev Time 0.00
Received By mmclean Date 2006-09-12 Time 17:20 Sent To I
Notes
***NONE***