Plan Review Details - Permit 06090171
Plan Review Stops For Permit 06090171
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-12-19 Cont ID  
Sent By lursu Date 2006-09-21 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2006-09-21 Time 15:14 Sent To  
Notes
2006-09-21 00:00:00EXT # 0001 CREATED FOR THIS UNIT:420
 COLUMBIA DR # 110
2006-09-18 00:00:00NEEDS EXT, NO SUITE IN SYSTEM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-28 Cont ID  
Sent By rmcdouga Date 2007-02-28 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2007-02-28 Time 17:17 Sent To  
Notes
2007-02-28 17:18:31STAMP PLANS AND PRINT PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-05 Cont ID  
Sent By rmcdouga Date 2007-02-05 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2007-02-05 Time 10:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-19 Cont ID  
Sent By rmcdouga Date 2006-12-19 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2006-12-19 Time 09:53 Sent To  
Notes
2006-12-19 10:40:19DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ON SHEET A1.0 EXIT CORRIDOR 105THAT LEADS TO THE
 EXISTING EXIT DOOR IS SPECIFIED AS FILE ROOM. FBC
 1013.2 PROHIBITS EGRESS THROUGH STORAGE ROOMS OR SPACES
 USED FOR SIMILAR PURPOSES. PLEASE CORRECT AND INDICATE
 THAT 105 IS A CORRIDOR AND THE FILES ARE LOCATED IN THE
 CLOSET.
  
 3) THE EXIT LIGHT LAYOUT ON A2.0 DOES NOT INDICATE THAT
 THE EXIT AT CORRIDOR 105 IS A REQUIRED EXIT ( DUE TO
 REQUIRED EXIT SEPARATION) . PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By rmcdouga Date 2006-10-05 Time 14:42 Rev Time 0.00
Received By rmcdouga Date 2006-10-05 Time 14:42 Sent To  
Notes
2006-10-05 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LEVEL OF ALTERATION AS
 SPECIFIED IN CHAPTER 3 OF THE 2004 FBC
 EXISTING BUILDING CODE.
  
 3) SPECIFY THE TYPE OF CONSTRUCTION FOR
 THE BUILDING. SEE 2004 FBC 602 AND
 TABLES 601 AND 602.
  
 4) THERE ARE TWO DETAIL ELEVENS ON SHEET
 A5.0. PLEASE CORRECT.
  
 5) SPECIFY THE INSULATION AND REQUIRED
 FIRE RESISTANCE RATING FOR THE NEW
 EXTERIOR MASONRY WALL SHOWN IN DETAIL
 11/A5.0
  
 6) 2004 FBC 1014.2.1 TWO EXITS OR EXIT
 ACCESS DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS
 ARE REQUIRED FROM ANY PORTION OF THE
 EXIT ACCESS, THE EXIT DOORS OR EXIT
 ACCESS DOORWAYS SHALL BE PLACED A
 DISTANCE APART EQUAL TO NOT LESS THAN
 ONE-HALF OF THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED MEASURED
 IN A STRAIGHT LINE BETWEEN EXIT DOORS OR
 EXIT ACCESS DOORWAYS. INTERLOCKING OR
 SCISSOR STAIRS SHALL BE COUNTED AS ONE
 EXIT STAIRWAY.
 EXCEPTIONS:
 1.WHERE EXIT ENCLOSURES ARE
 PROVIDED AS A PORTION OF THE REQUIRED
 EXIT AND ARE INTERCONNECTED BY A 1-HOUR
 FIRE-RESISTANCE-RATED CORRIDOR
 CONFORMING TO THE REQUIREMENTS OF
 SECTION 1016 , THE REQUIRED EXIT
 SEPARATION SHALL BE MEASURED ALONG THE
 SHORTEST DIRECT LINE OF TRAVEL WITHIN
 THE CORRIDOR.
 2.WHERE A BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2 , THE SEPARATION
 DISTANCE OF THE EXIT DOORS OR EXIT
 ACCESS DOORWAYS SHALL NOT BE LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE AREA
 SERVED.
 THE EXITS TO THIS SPACE DO NOT COMPLY.
 PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2007-05-18 Time 17:03 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 14:51 Sent To  
Notes
2007-05-07 14:58:41** UNSAT **
  
 ** PLEASE SEE THE PREVIOUS *PROVISO* NOTES WHICH WERE
 REDLINED ON PLAN 2/4/07 WHICH REQUESTED CORRECTIONS TO
 BE MADE BEFORE ROUGH ELECTRICAL INSPECTION.
 PLEASE SEE ITEMS BELOW WHICH WERE ON PLANS TO BE
 ADDRESSED.
  
 1) NOTE: PLEASE INDICATE ALL OVER RIDE TIMES AND ANY
 TIMES FOR OCCUPANCY TYPE DEVICES ON PLANS.
 PLEASE LIST ANY TIMED SCHEDULING.
 PLEASE SEE 13-415.1.ABC.1.1, 1.2 AND .1.3.
  
 2) NOTE: PLEASE NOTE AND INDICATE ALL BRANCH CIRCUITING
 FOR EMERGENCY AND EXIT LIGHTS AHEAD OF ANY LOCAL
 SWITCHING INCLUDING NEW LIGHTING CONTROLS SUCH AS
 OCCUPANCY DEVICES, TIMER OVER RIDES ETC.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 19:23 Sent To  
Notes
2007-02-04 09:49:48*** PROVSIO/ REDLINED NOTES ***
  
 ** IMPORATANT**
  
 THE FOLLOWING MUST BE REVISED, SUBMITTED, REVIEWED AND
 STAMPED FOR JOB-SITE INSPECTION BEFORE ANY ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 1) NOTE: PLEASE SEE NO TIMES ARE STATED ON PLANS FOR
 OVER RIDE CONTROLS AS PREVIOUSLY REQUESTED. PLEASE SEE
 THE RESPONSE LETTER MENTIONS THIS WILL BE SET PER THE
 OWNERS? REQUEST: HOWEVER THE MAXIMUM TIMES ARE
 DETERMINED BY THE FLORIDA BUILDING CODE
 13-415.1.ABC.1.1 AND .1.2. THIS IS NOT AN OPTION OF THE
 OWNER.
 PLEASE SEE MAXIMUM TIMES FOR ALL OCCUPANCY TYPE DEVICES
 ARE 30 MINUTES MAX.
  
  
 2) NOTE: ALL EM/EXT LTS WIRED PER 700.12E. AHEAD OF ANY
 SWITCH OR OC DEVICE.
  
 ** RISER WAS REVISED TO SHOW CORRECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW AND
 STAMPING BEFORE ANY ELECTRICLA INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE DO NOT HESIATE ON CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-02-03 19:23:42 
 IN ELEC FOR REIVEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-03 Cont ID  
Sent By dpalmer Date 2006-12-03 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2006-12-03 Time 20:17 Sent To  
Notes
2006-12-03 20:42:20*** UNSAT 2ND REVIEW****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW
 NOTES DUE TO THE PLANS SUBMITTED.
 THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW
 AND INDICATE A "NO OR OK". IF A "NO" IS SHOWN, FURTHER
 EXPLANATION/NOTES MAY BE PRESENT.
 ** PLEASE SEE ANY NEW NOTES ARE BEING ADDED TO THE
 BOTTOM OF FIRST REVIEW NOTES.
  
 1) NOTE: OK
  
 2) NOTE: OK.
  
 3) NOTE: NO, LIGHTING CONTROLS ONLY SEEM TO BE SHOWN
 FOR SOME LOCATIONS. PLEASE SEE 13-415.1.ABC.1.2, WHICH
 REQUIRES CONTROL IN ALL AREAS WITH FLOOR TO CEILING
 HEIGHT PARTITIONS.
 PLEASE SEE RESPONSE LETTER MENTIONS LIGHTING DENSITIES
 SHOWN ON E5.1, HOWEVER RISER AND LOAD SUMMARY WERE THE
 ONLY ITEMS LOCATED ON 5.1.
 PLEASE SUBMIT AND SHOW IN DETAIL THE PROPOSED LIGHTING
 CONTROL SYSTEM. PLEASE INDICATE THE NORMAL TIME
 SCHEDULE(S), THE TIMES ON THE TYPES OF OVER RIDE
 DEVICES ETC.
 PLEASE SEE PREVIOUS REVIEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE SOME NOTES ARE MENTIONED FOR SOME SORT OF
 LIGHTING CONTROL, HOWEVER ONLY IT SEEMS FOR COMMON
 AREAS?
 PLEASE SEE .1.3, FOR ALL SEPARATE AREAS, WITH FLR TO
 CEILING HEIGHT PARTITIONS.
 PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM BEING
 INSTALLED AND PROPOSED. PLEASE INCLUDE ALL LOCATIONS
 FOR OVER-RIDE DEVICES AS REQUIRED INCLUDING INGRESS/
 EGRESS INTO SPACE, SO THE OCCUPANT MAY VISUALLY SEE
 LIGHTING BEING CONTROLLED.
 PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION.
 PLEASE INDICATE THE MAXIMUM OF THE TIMES ALLOWED FOR
 EACH TYPE OF OVER-RIDE DEVICE WHICH MAY BE CHOSEN.
 (TIMER TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX)
 PLEASE BE SURE TO UPDATE THE SYMBOL LEGEND FOR DEVICES
 CHOSEN.
 PLEASE PROVIDE LIGHTING POWER DENSITIES, PER
 13-415.1.AB.1, 415.2.C.1, 415.2.B.1 ETC.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
  
 *** NEW NOTES 2ND REVIEW***
  
 1) NOTE: PLEASE SEE PANEL "LA" HAS NOW BEEN CHANGED TO
 A 225A MLO, WITH 300A OVER CURRENT PROTECTION FEEDING
 THIS PANEL??
 PLEASE SEE PREVIOUS PLANS INDICATED THIS PANEL AS A 400
 MLO.
 PLEASE SEE RISER SHOWS "LA" FEEDING "LC", WHICH IS OK,
 HOWEVER SEE "LB" INDICATES THIS PANEL AS THE PANEL
 CONTAINING THE "FEED-THRU" LUGS?
 PLEASE SEE RISER AND CORRELATE ALL OF THE ABOVE.
 ADJUST PANEL SIZES AND/OR OVER CURRENT PROTECTION AS
 NEEDED.
 THIS IS A NEW COMMENT AS PLANS WERE CHANGED.
 240.4, 310.16, 408 ETC.
  
 2) NOTE: PLEASE SEE ATTACHED SHEET WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 FLORIDA STATUTES 553.80(2)(B). THIS IS ONLY GIVEN AS A
 NOTICE AT THIS TIME.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By dpalmer Date 2006-09-18 Time 11:30 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 17:53 Sent To  
Notes
2006-09-18 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROIVDE THE YEARS FOR
 THE CODE BEING REFERENCED WHICH ARE
 CURRENTLY IN EFFECT AND RELEVANT TO
 DESIGN.
 NFPA-70 (NEC) 2002, NFPA-72 2002,
 NFPA-101 2003 AND THE 2004 FBC ON
 ELECTRICAL PLANS.
 FBC 106.1.2 ADMIN SECT.
  
 2) NOTE: PLEASE VERIFY THE LOCATIONS OF
 THE EM LTS AND NIGHT LTS.
 PLEASE SEE THE SYMBOL BEING USED FOR THE
 NL'S APPEAR TO BE ON SOME FIXTURES WHICH
 ARE NOT THE EM LTS/W/ BATTERY BACK UP.
 IF THE EM LTS ARE NOT ON THE NL CIRCUIT,
 WIRED AHEAD OF ANY SWITCHABLE MEANS,
 THIS WOULD CAUSE EACH OF THESE TO BE RUN
 DOWN EACH NIGHT. PLEASE SEE THAT IT
 APPEARS IT MAY BE A MISPRINT FOR THE
 LOCATION OF THESE ON PLANS.??
 700.12E.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
 PLEASE SEE SOME NOTES ARE MENTIONED FOR
 SOME SORT OF LIGHTING CONTROL, HOWEVER
 ONLY IT SEEMS FOR COMMON AREAS?
 PLEASE SEE .1.3, FOR ALL SEPARATE AREAS,
 WITH FLR TO CEILING HEIGHT PARTITIONS.
 PLEASE SUBMIT AND SHOW THE ENTIRE SYSTEM
 BEING INSTALLED AND PROPOSED. PLEASE
 INCLUDE ALL LOCATIONS FOR OVER-RIDE
 DEVICES AS REQUIRED INCLUDING INGRESS/
 EGRESS INTO SPACE, SO THE OCCUPANT MAY
 VISUALLY SEE LIGHTING BEING CONTROLLED.
 PLEASE SUBMIT THE SCHEDULING TO TIME OF OPERATION.
 PLEASE INDICATE TH MAXIMUM OF THE TIMES
 ALLOWED FOR EACH TYPE OF OVER-RIDE
 DEVICE WHICH MAY BE CHOOSEN. (TIMER
 TYPE, 4HRS MAX, SENSOR TYPE 30 MINS MAX)
 PLEASE BE SURE TO UPDATE THE SYMBOL
 LEGEND FOR DEVICES CHOSEN.
 PLEASE PROVIDE LIGHTING POWER DENSITIES,
 PER 13-415.1.AB.1, 415.2.C.1, 415.2.B.1
 ETC.
  
 4) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125%.
 215.3,230.42
  
 5) NOTE: PLEASE SEE PANEL SCHEDULE
 MENTIONS THE FACP IS GOING TO HAVEA
 RECEPT AT THIS LOCATION.PLEASE VERIFY
 THE RECEPT AND WHERE IT WILL BE LCOATED.
 PLEASE SEE ELECTRICAL PLANS INDICATE THE
 CIRCUIT LOCATION, HOWEVER THE FACP IS
 NOT SHOWN. PLEASE SEE THE FOLLOWING TEXT
 FROM NFPA-72
 4.4.1.4.2.1THE DEDICATED BRANCH
 CIRCUIT(S) AND CONNECTIONS SHALL BE
 MECHANICALLY PROTECTED.
 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS
 SHALL HAVE A RED MARKING, SHALL BE
 ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL,
 AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT."
 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL
 UNIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-09-17 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 13:05 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 17:13 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 17:13 Sent To  
Notes
2007-02-26 17:24:00*****APPROVED******
  
  
 ALL OTHER PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 SATISFIED.SHEET A3.0 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 17:34 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 17:34 Sent To  
Notes
2006-12-21 17:54:11*****UNSAT******
  
  
  
 1.CORRECT VERBAGE ON SHEET A3.0 AND SHEET A3.1 TO:
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS "A" OR CLASS "B" IN EXITS AND IN EXIT ACCESS
 CORRIDORS.ALL OTHER AREAS SHALL BE CLASS A, CLASS B,
 OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-25 Cont ID  
Sent By mawillia Date 2006-10-25 Time 09:19 Rev Time 0.00
Received By mawillia Date 2006-10-25 Time 09:19 Sent To  
Notes
2006-10-25 09:54:47*****DENIED*****
  
  
  
  
 1.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OF HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR THE VICINITY THEREOF ( INCLUDING FIRE LANES
 ).
  
 2.)WHERE THE BUILDING IS PROTECTED BY FIRE PROTECTION
 SYSTEM,SUCH SYSTEM SHALL BE MAINTAINED OPERATIONAL AT
 ALL TIMES DURING ALTERATION.
  
 3.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE
 PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED
 TO SERVICE.
  
 4.)ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED.
  
 5.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM SYSTEM
 , SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED FOR
 REVIEW.
  
 6.)IF THIS BUILDING IS INDEED"UNSPRINKLERED" AS
 LISTED ON SHEET A3.1,THE INTERIOR FINISH
 CLASSIFICATION SHALL BE CLASS"A" OR CLASS "B".
  
  
  
  
 CAPT MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 11:55 Sent To M
Notes
2007-06-07 11:55:39TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 15:27 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 15:27 Sent To E
Notes
2007-05-18 15:27:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 16:05 Sent To  
Notes
2007-05-04 08:58:20TO "COMM" BD#28
2007-04-24 16:06:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 15:44 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 15:44 Sent To  
Notes
2007-02-02 09:09:11TO "COMM" BD#5
2007-01-20 15:44:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 10:42 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 10:42 Sent To  
Notes
2006-11-29 14:56:57TO COMM BOARD SPACE #45
2006-11-20 10:43:15WAITING FOR "COMM"BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-25 Cont ID  
Sent By mawillia Date 2006-10-25 Time 09:19 Rev Time 0.00
Received By mawillia Date 2006-09-09 Time 16:02 Sent To  
Notes
2006-09-15 00:00:00TO "COMM" BD#4
2006-09-09 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-06-22 Cont ID  
Sent By rregueir Date 2007-06-22 Time 15:41 Rev Time 0.00
Received By rregueir Date 2007-06-22 Time 14:56 Sent To  
Notes
2007-06-22 15:42:45MECH REV P M2.1 AND T & B REPORT.
  
 ISSUE ON PROVISO FROM PREVIOUS REVIEW CORRECTED ON THS
 REVISION. NO LETTER FROM ENGINEER REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-08 Cont ID  
Sent By rregueir Date 2007-06-08 Time 13:00 Rev Time 0.00
Received By rregueir Date 2007-06-08 Time 09:15 Sent To  
Notes
2007-06-08 13:00:31***********PROVISO************
  
 PLEASE PROVIDE 2 SIGNED/SEALED LETTERS FROM THE
 ENGINEER OF RECORD STATING THAT THE EXTRA GRILL/CFM
 DESIGNATION ON PLAN IN ROOM 132 WAS LEFT ON PLAN IN
 ERROR AND THE CFMS SHOWN WERE NOT USED IN THE AIR
 BALANCE CALCULATIONS.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-05-15 Cont ID  
Sent By rregueir Date 2007-05-15 Time 09:13 Rev Time 0.00
Received By rregueir Date 2007-05-14 Time 12:59 Sent To  
Notes
2007-05-15 09:12:36--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/2005 REVISIONS
 FBC 2004 CH.1 AS AMENDED BY THE CITY OF WEST PALM
 BEACH
  
 1. WHAT IS THE SIZE OF THE FLEX DUCT FEEDING SUPPLY
 DISTRIBUTION BOX IN ROOM 104?
  
 2. WHAT IS THE CFM OF THE 6" SUPPLY FLEX IN CORR. 105?
  
 3. ROOM 113 SHOWS 8" FLEX SUPPLY AND RETURN WITH 320
 AND 290 CFM RESPECTIVELY. THESE ARE OUTSIDE THE RANGES
 OF THE FLEX SCHEDULES FOR 8" ON PG M6.1. PLEASE
 CLARIFY.
  
 4. ROOMS 107,109,115 ALSO SHOW FLEX DUCTS WITH CFM'S
 OUTSIDE OF THE RANGES ON THE M6.1 SCHEDULE.
  
 5. RTU-3: 14" FLEX ATTACHED TO R/A RISER IS CARRYING
 1230 CFM. SCHEDULE STATES A MAX. 700 CFM FOR 14" R/A
 FLEX. WHICH IS CORRECT? PLEASE CLARIFY.
  
 6. RTU-4: WHAT IS THE SIZE OF THE SUPPLY FLEX FEEDING
 DISTRIBUTION BOX FOR ROOMS 149,153,155?
  
 7. RTU-4: EQUIPMENT SCHEDULE CALLS FOR 2600 CFM. FLOOR
 PLAN SHOWS 2320 CFM. WHICH ONE IS CORRECT? ALSO, THERE
 ARE ONLY 755 CFM TOTAL RETURN AIR FOR THIS SYSTEM,
 LEAVING SOME AREAS WITHOUT BALANCED RETURN AS REQUIRED
 BY FBC,M 601.4.
  
 8. ROOM 118 SHOWS 8" SUPPLY FLEX AT 260 CFM, OUTSIDE
 THE RANGE AS SHOWN ON FLEX SCHEDULE. PLEASE CLARIFY.
  
 9. ROOM 152 SHOWS 6" R/A FLEX AT 120 CFM, OUTSIDE THE
 RANGE AS SHOWN ON FLEX SCHEDULE. PLEASE CLARIFY.
  
 10. CORR. 140 SHOWS "AA" GRILL FOR 290 CFM WITH NO DUCT
 OR GRILL SHOWN IN CEILING. IS THIS TO BE THROUGH THE
 DOOR INTO ROOM 141? IF SO, HOW WILL 290 CFM BE DRAWN
 THROUGH THE DOOR? THERE IS ONLY 115 CFM OF EXHAUST IN
 THIS SPACE. PLEASE CLARIFY.
  
 11. ROOM 132 SHOWS "AA" GRILL FOR 240 CFM. NO GRILL IS
 SHOWN IN CEILING AND NO DUCT IS SHOWN. PLEASE CLARIFY.
  
 12. RTU-5: SCHEDULE SHOWS 1780 CFM SUPPLY. FLOOR PLAN
 SHOWS 2400 CFM SUPPLY WITH 2380 CFM RETURN. WHICH IS
 CORRECT? ALSO, HOW WILL 200 CFM OUTDOOR AIR BE
 INTRODUCED IF THE UNIT RETURNS ALL BUT 20 CFM OF INDOOR
 AIR?
  
 13. THE AMOUNT OF SUPPLY AIR (INCLUDING OUTDOOR AIR)
 SHALL BE APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN
 AND EXHAUST AIR PER FBC,M 403.1.
 BASED ON TOTAL CFM AS SHOWN ON FLOOR PLAN:
  
 SUPPLY: 11,040 CFM
 RETURN: 8,755 CFM
 EXHAUST: 325 CFM
  
 RETURN PLUS EXHAUST IS 9,080 CFM WHICH IS 1960 CFM LESS
 THAN THE SUPPLY. RETURN PLUS EXHAUST SHOULD APPROX.
 EQUAL 11,040 CFM, WITH THE EXHAUST BEING APPROX. EQUAL
 TO THE 1170 CFM OF OUTDOOR AIR SHOWN ON SCHEDULE TO
 ACHIEVE THE VENTILATION RATES REQUIRED BY FBC,M 403.3.
 NOTE: THE ABOVE R/A TOTAL DOES NOT INCLUDE THE RETURNS
 QUESTIONED IN COMMENTS 10 AND 11, BUT THIS IS NOT
 ENOUGH TO PUT THE SYSTEM IN BALANCE.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE
 CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-04 Cont ID  
Sent By rregueir Date 2006-12-04 Time 17:12 Rev Time 0.00
Received By rregueir Date 2006-12-04 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By rregueir Date 2006-10-14 Time 10:42 Rev Time 0.00
Received By rregueir Date 2006-10-14 Time 10:42 Sent To  
Notes
2006-10-14 10:48:53---------------------DENIED-----------------------
  
 1. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL IN
 COMPLIANCE WITH FBC,M 307.2.1 AND FBC 1503.6. AUXILIARY
 DRAIN PROTECTION IS ALSO REQUIRED PER FBC,M 307.2.3.
  
 2. ALL R/A GRILL CONNECTIONS ARE SHOWN ON PLAN TO BE
 RIGID RECTANGULAR DUCT EXCEPT ROOM 129. NO SIZES ARE
 GIVEN AS THERE IS ONLY A DUCT SIZE SCHEDULE FOR
 FLEXIBLE DUCT. IF THE INTENT IS TO USE FLEX, PLEASE
 INDICATE SO ON PLAN. IF THE INTENT IS TO USE
 RECTANGULAR RIGID DUCT, PLEASE PROVIDE SIZES FOR EACH
 R/A DROP. NOTE: IN THIS CASE, A RECTANGULAR VOLUME
 DAMPER WILL BE REQUIRED AT EACH DROP.
  
 3. PAGE M7.1 ROOF CURB DETAIL NOTE #9 STATES THAT A
 STRUCTURAL ENGINEER WILL PROVIDE THE NUMBER AND SIZE OF
 ANCHORS TO BE USED FOR CURB ATTACHMENT. NO SUCH
 INFORMATION WAS PROVIDED.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 07:19 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 07:19 Sent To  
Notes
2007-06-09 07:24:36REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. NO CHANGES FOUND. THE SAME NUMBERED TRIANGLE AND
 SAME CLOUDED AREAS ARE INDICATED ON THE REVISIED SHEETS
 AS ARE INDICATED ON THE STAMPED ISSUED PLANS FOR
 PERMIT. PLEASE CLOUD ALL REVISIONS AND INDICATE
 REVISIONS WITH A NEW NUMBERED TRANGLE. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-17 Cont ID  
Sent By pschmitz Date 2007-02-17 Time 14:17 Rev Time 0.00
Received By pschmitz Date 2007-02-17 Time 14:17 Sent To  
Notes
2007-02-17 14:52:59RE-SUB

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-10 Cont ID  
Sent By kstevens Date 2007-01-10 Time 09:08 Rev Time 0.00
Received By kstevens Date 2007-01-10 Time 09:08 Sent To  
Notes
2007-01-10 09:10:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM FIRST REVIEW:
  
 1. OK
  
 2. SHTS PO.1 & P2.1. ENGINEERS SIGNATURE
 IS REQUIRED ON THE SEAL. INITIALS ARE
 NOT ACCEPTABLE. FAC 61G15-23.002(1) AND
 FS 471.025.
 ****RESPONSE NOTED, BUT INITIALS ARE STILL SHOWN ON SHT
 P2.1. PLEASE COMPLY WITH FAC REQUIREMENT.
  
 3. OK
 4. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 8O5-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By kstevens Date 2006-10-04 Time 18:04 Rev Time 0.00
Received By kstevens Date 2006-10-04 Time 18:04 Sent To  
Notes
2006-10-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A3.1 ROOMS 136, & 138. INTERIOR
 FINISH SCHEDULE INDICATES THE WALLS TO
 BE EPOXY PAINT. SECTION 1210.2 STATES
 WALLS WITHIN 2' OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. PLEASE INDICATE
 HOW "PAINT" MEETS THE REQUIREMENT FOR A
 HARD SURFACE.
  
 2. SHTS PO.1 & P2.1. ENGINEERS SIGNATURE
 IS REQUIRED ON THE SEAL. INITIALS ARE
 NOT ACCEPTABLE. FAC 61G15-23.002(1) AND
 FS 471.025.
  
 3. SHT P5.1 DOMESTIC WATER ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLLATION INSTRUCTIONS.
  
 4. SHT P5.1 DOMESTIC WATER ISOMETRIC.
 MOP SINK HOT WATER IS PIPED TO THE RIGHT
 SIDE OF THE FIXTURE, NOT TO THE LEFT
 SIDE AS REQUIRED IN SECTION 607.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 8O5-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy