 |
Plan Review Details - Permit 06090092
Plan Review Stops For Permit 06090092 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-10-16 |
Time |
18:08 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-09-05 |
Time |
13:02 |
Sent To |
|
|
Notes |
2006-10-16 18:10:31 | ADDRESS CHANGED TO 330 CLEMATIS ST # 1-G (WAS 330 | | CLEMATIS ST) BY LILI ON 9/6/06 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-11-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-11-07 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-11-07 |
Time |
09:23 |
Sent To |
|
|
Notes |
2006-11-07 09:24:18 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB | | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS, | | FS713.13. | | | | 2.)ADDRESSED. | | | | 3.)DELCARE LEVEL OF ALTERATION FBC EB | | 3 AND INCLUDE FBC EB IN GOVERNING CODE. | | | | I THINK THAT THERE MAY HAVE BEEN A MISUNDERSTANDING. | | THE REFERENCE IS FOR FBC EB CHAPTER 3, WHICH SPECIFIES | | HOW TO DETERMINE THE LEVEL OF ALTERATION.ARCHITECT | | HAS DECLARED A LEVEL 3, WHICH IS OVER 50% RENOVATION. | | IF THIS IS A LEVEL 3 ALTERATION, SHOW COMPLIANCE WITH | | ALL REQUIREMENTS FOR THE EXISTING BUILDING ON THE PLAN. | | IF NOT, REVISE THE NOTE. | | | | 4.-5.)ADDRESSED. | | | | 6.)SHOW MANEUVERING CLEARANCE, PULL | | SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6, | | FIGURE 11-25. | | | | THIS WAS ADDRESSED FOR DOOR 3 ONLY.PLEASE ADDRESS FOR | | THE OTHER TWO DOORS OR CALL ME TO DISCUSS. | | | | 7-9.)ADDRESSED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-10-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-10-05 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-10-05 |
Time |
13:49 |
Sent To |
|
|
Notes |
2006-10-05 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS, | | FS713.13. | | | | 2.)SHEET A.0 DECLARES A2 OCCUPANCY, | | EXIT REQUIREMENTS ARE FOR MERCANTILE, | | PLEASE REVISE. | | | | 3.)DELCARE LEVEL OF ALTERATION FBC EB | | 3 AND INCLUDE FBC EB IN GOVERNING CODE. | | | | 4.)WHAT IS THE CURRENT OCCUPANCY?IF | | THIS IS A CHANGE OF OCCUPANCY, INDICATE | | ON THE PLAN. | | | | 5.)PROVIDE ADDITIONAL INFORMATION IN | | REGARDS TO THE EXISTING BUILDING; TOTAL | | SF AREA, HEIGHT.CEILING HEIGHT IS | | SHOWN BUT PLEASE PROVIDE BUILDING | | HEIGHT. | | | | 6.)SHOW MANEUVERING CLEARANCE, PULL | | SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6, | | FIGURE 11-25. | | | | 7.)SEE FBC11-7.2, SERVICE COUNTER | | REQUIREMENT OF 36IN HEIGHT FOR A MINIMUM | | LENGTH OF 36IN, 40IN HEIGHT SHOWN. | | | | 8.)THE PLAN STATES THAT SF AREA IS | | 2853, ENERGY CALCS STATE 2250.REVISE. | | | | 9.)THE ENERGY CALCS DECLARE PALM BEACH | | COUNTY AS JURISDICTION; CORRECT | | JURISDICTION IS CITY OF WEST PALM BEACH, | | 604700. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-10-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-28 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-28 |
Time |
15:37 |
Sent To |
|
|
Notes |
2006-10-28 16:40:03 | *** UNSAT 2ND REVIEW *** | | | | ** PLEASE SEE SOMEITEMS FROM PREVIOUS REVIEW AND | | QUESTIONS ON REPSONSE LTR AND NEW NOTE FOR CHANGE IN | | RISER. | | | | ** PLEASE KNOW, AS RESUBMITTED PACKAGE WAS PICKED UP | | FOR REVIEW, THE ORIGINAL PERMIT APPLICATION FROM THE | | CONTRACTOR WAS NOT LCOATED IN WITH ALL OTHER PAPERWORK? | | CALLED AND LEFT A MESSAGE ON BILL RIELLY'S VM TO DROP | | OFF PERMIT APPLCATION. | | | | 1) NOTE: OK, REVISED RISER. | | | | 2) NOTE: OK REVISED RISER. | | | | 3) NOTE: OK. | | | | 4) NOTE: OK, REVISED RISER. | | | | 5) NOTE: OK. | | | | 6) NOTE: OK, HOWEVER LOAD CALCULATIONS DO INDICATE HOW | | THE LOADS FOR SHOW WINDOW CIRCUITS WERE DERIVED. PLEASE | | SEE 220.12A | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE INDICATE NEW OR EXISTING RECEPT'S ABOVE | | WINDOW'S. (EVERY 12' OR FRACTION THEREOF) | | 210.62,220.12 | | | | 7) NOTE:OK, HOWEVER RESPONSE MENTIONS EXISTING PANEL | | BEING REPLACED WITH A NEW 150A MAIN DISCONNETC HOWEVER | | RISER DOES NOT SHOW THIS? SHOWS AND INDICATES EQUIPMENT | | BEING REMOVED ONLY?? | | | | 8) NOTE: OK. | | | | 9) NOTE: NO, PLEASE SEE THE TC SYSTEM IS BEING SHOWN | | HOWEVER THE OVER RIDE DEVICE(S) LOCATED AT THE POINT OF | | ENTRANCE INTO SPACE AND OVER RIDE DEVICE(S) LOCATED AT | | LOCATIONS WHERE THE OCCUPANT CAN VISUALLY SEE ALL | | LIGHTING BEING CONTROLLED. PLEASE SEE SEPARATE SPACES | | WITH FLR TO CEILING HEIGHT PARTITIONS REQUIRED SEPARATE | | CONTROL. | | PLEASE SEE "ST" DEVICE AS SHOWN FOR SOME RMS MENTIONS | | UP TO 12HRS, HOWEVER PLEASE SEE CODE ONLY PERMITS A MAX | | OF 4HRS ON TIMER TYPE DEVICES. ON OCC SENSOR TYPE | | DEVICES IT IS 30 MINS. | | PLEASE SEE SCHEDULE "A" WAS SUBMITTED WHICH DOES SEEM | | TO FIT FOR SCOPE OF WORK. PLEASE SEE "B" OR "C". PLEASE | | ALSO SEE PREVIOUS NOTE WITH RESPECT TO PERFORMANCE | | CALCULATIONS PER 13-415.2. | | 13-101.1.3 | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC CHAPTER 13 FOR | | AUTOMATED LIGHTING CONTROLLED REQUIRED. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND | | .1.3. | | PLEASE PROVIDE SCHEDULING, TIMERS, | | OVER-RIDES AND TYPES OF DEVICES. PLEASE | | SHOW ALL CONTROL/OVER RIDE LOCATIONS. | | PLEASE SEE ALL SEPARATE SPACES WITH FLR | | TO CEILING HEIGHT PARTITIONS, WITH | | CONTROLS. | | PLEASE PROVIDE ENERGY CALCULATIONS AS | | REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1, | | 415.2.C. | | | | | | | | 10) NOTE: OK. | | | | 11) NOTE:NO, PLEASE SEE RESPONSE SPEAKS OF A/C | | EQUIPMENT. THIS NOT WAS FOR THE "AIC" RATINGS FOR NEW | | EQUIPMENT/MAINS/PANELS ECT. PLEASE SEE PANELS ARE NOTED | | AND SHOWN AT 22K. PLEASE INDICATE FUSE RATING(S). | | 110.9,240.12 | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE INDICATE THE AIC | | RATINGS FOR ALL NEW SERVICE | | MAINS/EQUIPMENT. | | 110.9 | | | | ** NEW NOTE ** | | | | 12) NOTE: PLEASE INDICATE VOLTAGE DROP FOR FEEDERS FROM | | MAIN ELECTRICAL ROOM TO NEW PANEL LOCATIONS. | | PLEASE SEE 13-413.1.ABC.1.1 | | | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-19 |
Time |
17:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-19 |
Time |
14:03 |
Sent To |
|
|
Notes |
2006-09-19 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE SERVICE IS BEING | | SHOWN TO A 350A CAPABILITY , HOWEVER | | RISER SHOWS A 200A METER CAN BEING | | TAPPED. | | PLEASE SEE NOTES ON LOAD CALCS, AS LOADS | | EXCEED RATINGS OF EQUIPMENT AS SHOWN. | | 240.4,310.16,230.70 ETC | | | | 2) NOTE: PLEASE INCLUDE CONDUCTORS FROM | | METER TO GUTTER ANF FROM GUUTER TO NEW | | MAIN. | | 240.310.16 ETC | | | | 3) NOTE: PLEASE SHOW LOAD ON EXISTING | | GUTEER, SIZE AND NEW LOADS BEIGN ADDED. | | 220, 215. ETC. | | FBC 106.1.2 ADMIN SECT. | | | | 4) NOTE: PLEASE SEE LOAD CALCS MENTIONS | | TWO PANEL "B" 'S? | | PLEASE CLARIFY. | | 106.1.2 FBC. | | | | 5) NOTE: PLEASE INDICATE NEW OR EXISTING | | SIGN CIRCUIT(S) PER 600.5 | | | | 6) NOTE: PLEASE INDICATE NEW OR EXISTIGN | | RECEPTS ABOVE WINDOWS. (EVERY 12' OR | | FRACTION THEROF. | | 210.62, 220.12 | | | | 7) NOTE: PLEASE SEE THIS SERVICE IS | | BEING SHOWN FOR ONE TENANT, YET IT IS | | ALSO BEING SHOWN FOR FEEDING | | "COURTYARD"?? | | PLEASE VERIFY AS THE CODE DOES NOT | | PERMIT COMMON AREA LIGHTING ETC BEING | | CONTROLLED OR FED FROM A TENANT | | OCCUPANCY. | | 210.25, 240.24 | | | | 8) NOTE: PLEASE CLARIFY SHUNT BRKR FOR | | ANY HOOD POWER/ LTS. NFPA-96 | | | | 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR | | AUTOMATED LIGHTING CONTROLLED REQUIRED. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND | | .1.3. | | PLEASE PROVIDE SCHEDULING, TIMERS, | | OVER-RIDES AND TYPES OF DEVICES. PLEASE | | SHOW ALL CONTROL/OVER RIDE LOCATIONS. | | PLEASE SEE ALL SEPARATE SPACES WITH FLR | | TO CEILING HEIGHT PARTITIONS, WITH | | CONTROLS. | | PLEASE PROVIDE ENERGY CALCULATIONS AS | | REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1, | | 415.2.C. | | | | PLEASE SEE THERE ARE SWITCHES BEING | | SHOWN ON PLANS WHICH DO NOT INDICATE | | CONTROL OF ANY PARTICULAR ITEM.? | | | | 10) NOTE: PLEASE SHOW NEW OR EXISTING | | GFI RECEPT FOR ROOF TOP EQUIPMENT PER 210.8,210.63 | | | | 11) NOTE: PLEASE INDICATE THE AIC | | RATINGS FOR ALL NEW SERVICE | | MAINS/EQUIPMENT. | | 110.9 | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-11-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-13 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-13 |
Time |
15:59 |
Sent To |
|
|
Notes |
2006-11-13 16:18:41 | *****DENIED***** | | | | | | | | PLEASE ACKNOWLEDGE COMMENTS FROM PREVIOUS FIRE PLAN | | REVIEW (10/12/2006) BY SHOWING ON THE PLANS HOW EACH | | ITEM WAS ADDRESSED. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-12 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-12 |
Time |
10:20 |
Sent To |
|
|
Notes |
2006-10-12 11:45:03 | *****DENIED***** | | | | | | | | | | 1.)CONSTRUCTION, ALTERATION, ANDDEMOLITION | | OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING | | AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. | | | | 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). | | | | 4.)THE SCOPE OF THE INTERIOR BUILDOUT REQUIRING | | MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER | | SYSTEM, SEPARATE PERMIT AND PLANS ARE REQUIRED. | | | | 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS | | AND EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B". | | | | 6.)ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY | | THE ADDRESS FOR THIS STRUCTURE.AS PER WEST PALM BEACH | | CODE, THE CHARACTERS (NUMBERS AND/OR LETTERS) SHALL BE | | NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING | | WITH THE BACKGROUND.IF USED, HURRICANE SHUTTERS SHALL | | NOT COVER OR CONCEAL ADDRESS. | | | | 7.)ADDITIONAL MECHANICAL PERMITS AND PLANS ARE | | REQUIRED FOR HOOD/SUPPRESSION SYSTEM(S). | | | | 8.)ON SHEET M-3 HOOD SYSTEM NOTE #1, REFERENCES SHALL | | BE MADE TO NFPA 96, 2004 EDITION. | | | | 9.)AS PER WPBFR, DUCT SMOKE DETECTORS SHALL INITIATE | | A GENERAL FIRE ALARM. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-11-27 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-11-16 |
Time |
17:42 |
Sent To |
|
|
Notes |
2006-11-27 17:44:01 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | FROM PREVIOUS REVIEW | | | | 1. SHTS A-6 & P-1. SHT A-6 INDICATES A | | NEW OVEN, AND SHT P-1 INDICATES A FRYER | | AND THE OVEN AS RECONNECTING (GAS SIZE | | AND CAPACITY SAME EXISTING). A GAS | | PERMIT WILL BE REQUIRED AND THE | | FOLLOWING INFORMATION WILL BE REQUIRED | | TO VERIFY COMPLIANCE WITH THE GAS CODE: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B" | | TO "D" IS NOT INDICATED | | | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT. | | ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C", | | AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B" | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES | | 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004 | | FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5 | | PSI, NOT 1 PSI OR LESS. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR | | ALL NEW EQUIPMENT). | | ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE | | REQUIRED FOR PLAN REVIEW. | | | | H. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-09-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-09-29 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-09-29 |
Time |
08:38 |
Sent To |
|
|
Notes |
2006-09-29 00:00:00 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. SHTS A-6 & P-1. SHT A-6 INDICATES A | | NEW OVEN, AND SHT P-1 INDICATES A FRYER | | AND THE OVEN AS RECONNECTING (GAS SIZE | | AND CAPACITY SAME EXISTING). A GAS | | PERMIT WILL BE REQUIRED AND THE | | FOLLOWING INFORMATION WILL BE REQUIRED | | TO VERIFY COMPLIANCE WITH THE GAS CODE: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR | | ALL NEW EQUIPMENT). | | | | H. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. (INDICATED | | AS EXISTING RELOCATING). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-10-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-25 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-25 |
Time |
08:56 |
Sent To |
|
|
Notes |
2006-10-26 11:41:09 | TO "COMM" BD#14 | 2006-10-25 08:57:03 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-16 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-09-08 |
Time |
13:24 |
Sent To |
|
|
Notes |
2006-09-13 00:00:00 | TO "COMM" BD#55 | 2006-09-08 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-31 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-31 |
Time |
12:36 |
Sent To |
|
|
Notes |
2006-10-31 15:27:24 | | | COMMENTS FROM REVIEW DATED 10-13-06: | | | | COMMENT 1, 2 ,3 | | | | COMMENT 4: EF-2 TERMINATION TO THE ROOF IS NOT | | INDICATED ON PLAN SHEET M-1.2.THIS WAS NOT ADDRESSED. | | REFERENCED PLAN SHEET WAS REMOVED FROM THE RESUBMITTED | | PLANS.PLEASE PROVIDE DETAIL OF EQUIPMENT LOCATED ON | | THE ROOF.PROVIDE DETAIL OF REQUIRED CLEARANCES FROM | | ROOF SURFACE, FRESH AIR INTAKE IN RELATION TO EXHAUST | | TERMINATIONS, AS WELL AS CLEARANCES FOR THE GREASE DUCT | | TERMINATION TO PROPERTY LINES, CONTINGUOUS BUILDINGS | | ETC.2004 FMC 506.3.12.3. | | | | COMMENT 5 WAS NOT ADDRESSED.PLAN SHEET M-1 INDICATES | | EF-2 (WHICH THE LOCATION OR TERMINATION IS NOT | | INDICATED ON THE PLAN). IS THIS A GRILLE AT THE | | CEILING?A HOOD IS NOT SHOWN OVER THE OVEN.PLEASE | | INDICATE WHAT TYPE OF "OVEN" THIS IS.PLEASE | | REFERENCE 2004 FMC 507.2.1, TYPE I HOOD SHALL BE | | INSTALLED WHERE COOKING APPLIANCES PRODUCE GREASE OR | | SMOKE, SUCH AS OCCURS WITH GRIDDLES, FRYERS, BOILERS, | | OVENS, RANGES, AND WOK RANGES.A TYPE II HOOD IS SHALL | | BE INSTALLED WHERE COOKING OR DISHWASHING APPLIANCES | | THAT PRODUCE HEAT OR STEAM AND DO NOT PRODUCE GREASE OR | | SMOKE, SUCH AS STEAMERS, KETTLES, PASTA COOKERS & | | DISHWASHING MACHINES.PLEASE CLARIFY.PLEASE PROVIDE | | MANUFACTURER'S SUBMITTAL FOR THE OVEN. | | | | COMMENT6 WAS NOT ADDRESSED.(PLAN SHEET M-1.2 WAS | | REMOVED FROM SUBMITTAL SET)PLAN SHEET M-1.2 APPEARS | | TO HAVE A WALL THAT TERMINATES ABOVE THE ROOF THAT | | SEPARATES RTU-1 & EF-1. PER 2004 FMC 306.5, ACCESS | | SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER | | THAN 30 INCHES.PLEASE NOTE, SHOULD ROOF HAVE A SLOPE | | GREATER THAN 4/14 PITCH SHOW COMPLIANCE WITH 306.5 | | ITEMS 1 THROUGH 7. | | | | COMMENT 7 WAS NOT ADDRESSED.PLEASE INDICATE ACCESS TO | | ROOF. | | | | COMMENT8 WAS NOT ADDRESSED.PLEASE CLARIFY WHAT | | EQUIPMENTTHE20"X48" RETURN AIR DUCT & 20"X32" | | SUPPLY DUCT TERMINATING ON THE ROOF GO TO (RTU-1?) | | | | COMMENT 9 WAS NOT ADDRESSED.ADDITIONAL PERMITS | | REQUIRED FOR HOOD, FIRE SUPPRESSION, & WALK-IN COOLER. | | PLEASE PROVIDE PLANS AND MANUFACTURER'S SUBMITTAL DATA | | WITH PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. | | | | | | | | | | PLEASE NOTE, FAN SCHEDULE ON PLAN SHEET M-1 SHOWS EF-1 | | AS A COOKING LINE HOOD FAN BUT THE PLAN INDICATES EF-1 | | IN THE RESTROOM | | | | PLEASE NOTE, GREASE DUCT ENCLOSURE OR SHAFT SHALL NOT | | ENCLOSE ANY OTHER DUCT SYSTEMS PER NFPA 96-01 SECTION | | 7.7.5.2. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-10-13 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-10-13 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-10-12 |
Time |
15:32 |
Sent To |
|
|
Notes |
2006-10-13 07:57:06 | DENIED: | | PLEASE CLARIFY THE FOLLOWING: | | 1.PLAN SHEET A-1 INDICATES WEST WALL IS INDICATED AS | | A EXISTING TENANT DEMISING WALL.IS THIS AN EXTERIOR | | WALL OR IS THIS INTERIOR TO THE TENANT SPACE.PLEASE | | CLARIFY IF THIS WILL BE SEPARATED OR PROTECTED BY AN | | ENCLOSURE OR SHAFT? | | | | 2.PLAN SHEET M-1 DUCT MISSING FIRE DAMPER FROM | | 20"X48" R/A DUCT PENETRATING TENANT DEMISING WALL. | | | | 3.PLEASE PROVIDE CLEARANCES FROM THE GREASE DUCT TO | | COMBUSTIBLES.SHOW COMPLIANCE WITH 2004 FMC 506.3.6. | | | | 4.PLAN SHEET M-1 INDICATES EF-2 SERVES A COOK LINE | | HOOD TERMINATING ON THE ROOF.THIS IS NOT SHOWN ON | | PLAN SHEET M-1.2. | | | | 5.PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE | | HOOD & GREASE DUCT: | | A) TYPE I OR TYPE II HOOD | | B) INDICATE HOOD & DUCT MATERIAL AND GAUGE 2004 | | FMC 507.4, 507.5, 506.3.1.1 & 506.4. | | C) INDCIATE DUCT SIZE AND LAYOUT | | D) AIR VELOCITY THROUGH THE GREASE DUCT SHALL | | COMPLY WITH 2004 FMC 506.3.4 | | | | 6.PLAN SHEET M-1.2 APPEARS TO HAVE A WALL THAT | | TERMINATES ABOVE THE ROOF THAT SEPARATES RTU-1 & EF-1. | | PER 2004 FMC 306.5, ACCESS SHALL NOT REQUIRE CLIMBING | | OVER OBSTRUCTIONS GREATER THAN 30 INCHES.PLEASE NOTE, | | SHOULD ROOF HAVE A SLOPE GREATER THAN 4/14 PITCH SHOW | | COMPLIANCE WITH 306.5 ITEMS 1 THROUGH 7. | | | | 7.PLEASE INDICATE ACCESS TO ROOF. | | | | 8.PLEASE CLARIFY WHAT EQUIPMENTTHE20"X48" RETURN | | AIR DUCT & 20"X32" SUPPLY DUCT TERMINATING ON THE ROOF | | GO TO (RTU-1?) | | | | 9.ADDITIONAL PERMITS REQUIRED FOR HOOD, FIRE | | SUPPRESSION, & WALK-IN COOLER.PLEASE PROVIDE PLANS | | AND MANUFACTURER'S SUBMITTAL DATA WITH PERMIT | | APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-11-16 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-11-16 |
Time |
16:52 |
Sent To |
|
|
Notes |
2006-11-17 06:45:28 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUES | | | | *******FROM 1ST REVIEW******* | | | | 1. ALL SHEETS. THE ARCHITECTS TITLE | | BLOCK DOES NOT REFLECT THE ADDRESS FOUND | | ON THE DBPR WEBSITE. FAC 61G1-16.004(1) | | AND FS 481.2055. (SEE ATTACHED SHEET). ****RESPONSE | | NOTED. SUBMIT A LETTER FROM DBPR INDICATING APPROVAL OF | | THIS TEMPORY ARRANGEMENT. I DO NOT HAVE THE AUTHORITY | | TO WAIVE THIS REQUIREMENT OF THE FLORIDA ADMINISTRATIVE | | CODE/FLORIDA STATUTES. | | | | 2. ROUTE PLANS TO DBPR HOTEL AND | | RESTURANT DIVISION FOR REVIEW. MINIMUM 2 | | SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" | | REQUIRED FOR REVIEW. | | SECTION 102.2.1. | | ****RESPONSE NOTED. THIS IS REQUIRED FOR THE PLAN | | REVIEW AND SHALL BE REVIEWED BY DBPR, PLANS STAMPED AND | | WORKSHEETS ATTACHED AS REQUESTED. | | | | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. | | PLEASE CONTACT LYNN MASSON, | | ENVIRONMENTAL COMPLIANCE (561) 822-2271, | | FAX (561) 822-2279, OR E-MAIL | | [email protected]. WASTE ORD. 3434. | | ****RESPONSE NOTED BUT NOT ACCEPTABLE. PLEASE CONTACT | | ENVIRONMENTAL COMPLIANCE. GREASE TRAP INSIDE NOT | | APPROVED. PER MUNICIPAL CODE A MINIMUM 750 GAL.GREASE | | INTERCEPTOR IS REQUIRED. | | | | 4. OK | | 5. OK | | 6. OK | | | | 7. SHT P-1 WATER FILTERS SHALL BE | | COMPLIANT WITH NSF-42. SUBMIT MANUF. | | SPECIFICATION SHEETS. | | ****RESPONSE NOTED. MANUFACTURE CUT SHEET INDICATED WAS | | NOT FOUND IN RESUBMITTAL. | | | | 8. SHTS A-6 & P-1. SHT A-6 INDICATES A | | NEW OVEN, AND SHT P-1 INDICATES A FRYER | | AND THE OVEN AS RECONNECTING (GAS SIZE | | AND CAPACITY SAME EXISTING). A GAS | | PERMIT WILL BE REQUIRED AND THE | | FOLLOWING INFORMATION WILL BE REQUIRED | | TO VERIFY COMPLIANCE WITH THE GAS CODE: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B" | | TO "D" IS NOT INDICATED | | | | B. OK | | C. OK | | D. OK | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT. | | ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C", | | AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B" | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES | | 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004 | | FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5 | | PSI, NOT 1 PSI OR LESS. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR | | ALL NEW EQUIPMENT). | | ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE | | REQUIRED FOR PLAN REVIEW. | | | | H. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-09-29 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-09-29 |
Time |
07:34 |
Sent To |
|
|
Notes |
2006-09-29 00:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUES | | | | 1. ALL SHEETS. THE ARCHITECTS TITLE | | BLOCK DOES NOT REFLECT THE ADDRESS FOUND | | ON THE DBPR WEBSITE. FAC 61G1-16.004(1) | | AND FS 481.2055. (SEE ATTACHED SHEET). | | | | 2. ROUTE PLANS TO DBPR HOTEL AND | | RESTURANT DIVISION FOR REVIEW. MINIMUM 2 | | SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" | | REQUIRED FOR REVIEW. | | SECTION 102.2.1. | | | | 3. A GREASE INTERCEPTOR MAY BE REQUIRED. | | PLEASE CONTACT LYNN MASSON, | | ENVIRONMENTAL COMPLIANCE (561) 822-2271, | | FAX (561) 822-2279, OR E-MAIL | | [email protected]. WASTE ORD. 3434. | | | | 4. SHT A-5 PLEASE SHOW COMPLIANCE WITH | | THE FOLLOWING: | | A. 11-4.16.5 FLUSH CONTROLS | | B. 11-4.19.5 FAUCETS | | | | 5. SHT P-1 ALL EQUIPMENT & FIXTURES | | UTILIZED FOR STORAGE, PREPARATION AND | | HANDLING OF FOOD SHALL DISCHARGE THROUGH | | AN INDIRECT WASTE PIPE BY MEANS OF AN | | AIR GAP. SECTION 802.1.1. - FLOOR SINKS | | ARE REQUIRED PER SECTION 802.3. | | | | 6. SHT P-1 PLUMBING NOTES #13 AIR | | CHAMBERS ARE NOT APPROVED. WATER HAMMER | | ARRESTORS REQUIRED AT QUICK CLOSING | | VALVES SHALL BE LOCATED NEAR THE | | FIXTURES IN AN "EFFECTIVE RANGE", (NOT | | IN THE CEILING), PER PDI-WH 201 AND | | MANUF. INSTALLATION INSTRUCTIONS. (ICE | | MAKERS, DISHWASHERS, ETC). | | | | 7. SHT P-1 WATER FILTERS SHALL BE | | COMPLIANT WITH NSF-42. SUBMIT MANUF. | | SPECIFICATION SHEETS. | | | | 8. SHTS A-6 & P-1. SHT A-6 INDICATES A | | NEW OVEN, AND SHT P-1 INDICATES A FRYER | | AND THE OVEN AS RECONNECTING (GAS SIZE | | AND CAPACITY SAME EXISTING). A GAS | | PERMIT WILL BE REQUIRED AND THE | | FOLLOWING INFORMATION WILL BE REQUIRED | | TO VERIFY COMPLIANCE WITH THE GAS CODE: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. (FOR | | ALL NEW EQUIPMENT). | | | | H. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. (INDICATED | | AS EXISTING RELOCATING). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2006-11-03 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2006-11-03 |
Time |
11:50 |
Sent To |
|
|
Notes |
2006-11-03 11:51:05 | INTERIOR REMODEL ONLY - NO DMP REVIEW NECESSARY |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |