Plan Review Details - Permit 06090092
Plan Review Stops For Permit 06090092
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By rbrown Date 2006-10-16 Time 18:08 Rev Time 0.00
Received By rbrown Date 2006-09-05 Time 13:02 Sent To  
Notes
2006-10-16 18:10:31ADDRESS CHANGED TO 330 CLEMATIS ST # 1-G (WAS 330
 CLEMATIS ST) BY LILI ON 9/6/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-07 Cont ID  
Sent By shill Date 2006-11-07 Time 09:23 Rev Time 0.00
Received By shill Date 2006-11-07 Time 09:23 Sent To  
Notes
2006-11-07 09:24:18SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 2.)ADDRESSED.
  
 3.)DELCARE LEVEL OF ALTERATION FBC EB
 3 AND INCLUDE FBC EB IN GOVERNING CODE.
  
 I THINK THAT THERE MAY HAVE BEEN A MISUNDERSTANDING.
 THE REFERENCE IS FOR FBC EB CHAPTER 3, WHICH SPECIFIES
 HOW TO DETERMINE THE LEVEL OF ALTERATION.ARCHITECT
 HAS DECLARED A LEVEL 3, WHICH IS OVER 50% RENOVATION.
 IF THIS IS A LEVEL 3 ALTERATION, SHOW COMPLIANCE WITH
 ALL REQUIREMENTS FOR THE EXISTING BUILDING ON THE PLAN.
 IF NOT, REVISE THE NOTE.
  
 4.-5.)ADDRESSED.
  
 6.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6,
 FIGURE 11-25.
  
 THIS WAS ADDRESSED FOR DOOR 3 ONLY.PLEASE ADDRESS FOR
 THE OTHER TWO DOORS OR CALL ME TO DISCUSS.
  
 7-9.)ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By shill Date 2006-10-05 Time 13:49 Rev Time 0.00
Received By shill Date 2006-10-05 Time 13:49 Sent To  
Notes
2006-10-05 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 2.)SHEET A.0 DECLARES A2 OCCUPANCY,
 EXIT REQUIREMENTS ARE FOR MERCANTILE,
 PLEASE REVISE.
  
 3.)DELCARE LEVEL OF ALTERATION FBC EB
 3 AND INCLUDE FBC EB IN GOVERNING CODE.
  
 4.)WHAT IS THE CURRENT OCCUPANCY?IF
 THIS IS A CHANGE OF OCCUPANCY, INDICATE
 ON THE PLAN.
  
 5.)PROVIDE ADDITIONAL INFORMATION IN
 REGARDS TO THE EXISTING BUILDING; TOTAL
 SF AREA, HEIGHT.CEILING HEIGHT IS
 SHOWN BUT PLEASE PROVIDE BUILDING
 HEIGHT.
  
 6.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6,
 FIGURE 11-25.
  
 7.)SEE FBC11-7.2, SERVICE COUNTER
 REQUIREMENT OF 36IN HEIGHT FOR A MINIMUM
 LENGTH OF 36IN, 40IN HEIGHT SHOWN.
  
 8.)THE PLAN STATES THAT SF AREA IS
 2853, ENERGY CALCS STATE 2250.REVISE.
  
 9.)THE ENERGY CALCS DECLARE PALM BEACH
 COUNTY AS JURISDICTION; CORRECT
 JURISDICTION IS CITY OF WEST PALM BEACH,
 604700.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 15:37 Sent To  
Notes
2006-10-28 16:40:03*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOMEITEMS FROM PREVIOUS REVIEW AND
 QUESTIONS ON REPSONSE LTR AND NEW NOTE FOR CHANGE IN
 RISER.
  
 ** PLEASE KNOW, AS RESUBMITTED PACKAGE WAS PICKED UP
 FOR REVIEW, THE ORIGINAL PERMIT APPLICATION FROM THE
 CONTRACTOR WAS NOT LCOATED IN WITH ALL OTHER PAPERWORK?
 CALLED AND LEFT A MESSAGE ON BILL RIELLY'S VM TO DROP
 OFF PERMIT APPLCATION.
  
 1) NOTE: OK, REVISED RISER.
  
 2) NOTE: OK REVISED RISER.
  
 3) NOTE: OK.
  
 4) NOTE: OK, REVISED RISER.
  
 5) NOTE: OK.
  
 6) NOTE: OK, HOWEVER LOAD CALCULATIONS DO INDICATE HOW
 THE LOADS FOR SHOW WINDOW CIRCUITS WERE DERIVED. PLEASE
 SEE 220.12A
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE NEW OR EXISTING RECEPT'S ABOVE
 WINDOW'S. (EVERY 12' OR FRACTION THEREOF)
 210.62,220.12
  
 7) NOTE:OK, HOWEVER RESPONSE MENTIONS EXISTING PANEL
 BEING REPLACED WITH A NEW 150A MAIN DISCONNETC HOWEVER
 RISER DOES NOT SHOW THIS? SHOWS AND INDICATES EQUIPMENT
 BEING REMOVED ONLY??
  
 8) NOTE: OK.
  
 9) NOTE: NO, PLEASE SEE THE TC SYSTEM IS BEING SHOWN
 HOWEVER THE OVER RIDE DEVICE(S) LOCATED AT THE POINT OF
 ENTRANCE INTO SPACE AND OVER RIDE DEVICE(S) LOCATED AT
 LOCATIONS WHERE THE OCCUPANT CAN VISUALLY SEE ALL
 LIGHTING BEING CONTROLLED. PLEASE SEE SEPARATE SPACES
 WITH FLR TO CEILING HEIGHT PARTITIONS REQUIRED SEPARATE
 CONTROL.
 PLEASE SEE "ST" DEVICE AS SHOWN FOR SOME RMS MENTIONS
 UP TO 12HRS, HOWEVER PLEASE SEE CODE ONLY PERMITS A MAX
 OF 4HRS ON TIMER TYPE DEVICES. ON OCC SENSOR TYPE
 DEVICES IT IS 30 MINS.
 PLEASE SEE SCHEDULE "A" WAS SUBMITTED WHICH DOES SEEM
 TO FIT FOR SCOPE OF WORK. PLEASE SEE "B" OR "C". PLEASE
 ALSO SEE PREVIOUS NOTE WITH RESPECT TO PERFORMANCE
 CALCULATIONS PER 13-415.2.
 13-101.1.3
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13 FOR
 AUTOMATED LIGHTING CONTROLLED REQUIRED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE SCHEDULING, TIMERS,
 OVER-RIDES AND TYPES OF DEVICES. PLEASE
 SHOW ALL CONTROL/OVER RIDE LOCATIONS.
 PLEASE SEE ALL SEPARATE SPACES WITH FLR
 TO CEILING HEIGHT PARTITIONS, WITH
 CONTROLS.
 PLEASE PROVIDE ENERGY CALCULATIONS AS
 REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1,
 415.2.C.
  
  
  
 10) NOTE: OK.
  
 11) NOTE:NO, PLEASE SEE RESPONSE SPEAKS OF A/C
 EQUIPMENT. THIS NOT WAS FOR THE "AIC" RATINGS FOR NEW
 EQUIPMENT/MAINS/PANELS ECT. PLEASE SEE PANELS ARE NOTED
 AND SHOWN AT 22K. PLEASE INDICATE FUSE RATING(S).
 110.9,240.12
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE AIC
 RATINGS FOR ALL NEW SERVICE
 MAINS/EQUIPMENT.
 110.9
  
 ** NEW NOTE **
  
 12) NOTE: PLEASE INDICATE VOLTAGE DROP FOR FEEDERS FROM
 MAIN ELECTRICAL ROOM TO NEW PANEL LOCATIONS.
 PLEASE SEE 13-413.1.ABC.1.1
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 14:03 Sent To  
Notes
2006-09-19 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE SERVICE IS BEING
 SHOWN TO A 350A CAPABILITY , HOWEVER
 RISER SHOWS A 200A METER CAN BEING
 TAPPED.
 PLEASE SEE NOTES ON LOAD CALCS, AS LOADS
 EXCEED RATINGS OF EQUIPMENT AS SHOWN.
 240.4,310.16,230.70 ETC
  
 2) NOTE: PLEASE INCLUDE CONDUCTORS FROM
 METER TO GUTTER ANF FROM GUUTER TO NEW
 MAIN.
 240.310.16 ETC
  
 3) NOTE: PLEASE SHOW LOAD ON EXISTING
 GUTEER, SIZE AND NEW LOADS BEIGN ADDED.
 220, 215. ETC.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE LOAD CALCS MENTIONS
 TWO PANEL "B" 'S?
 PLEASE CLARIFY.
 106.1.2 FBC.
  
 5) NOTE: PLEASE INDICATE NEW OR EXISTING
 SIGN CIRCUIT(S) PER 600.5
  
 6) NOTE: PLEASE INDICATE NEW OR EXISTIGN
 RECEPTS ABOVE WINDOWS. (EVERY 12' OR
 FRACTION THEROF.
 210.62, 220.12
  
 7) NOTE: PLEASE SEE THIS SERVICE IS
 BEING SHOWN FOR ONE TENANT, YET IT IS
 ALSO BEING SHOWN FOR FEEDING
 "COURTYARD"??
 PLEASE VERIFY AS THE CODE DOES NOT
 PERMIT COMMON AREA LIGHTING ETC BEING
 CONTROLLED OR FED FROM A TENANT
 OCCUPANCY.
 210.25, 240.24
  
 8) NOTE: PLEASE CLARIFY SHUNT BRKR FOR
 ANY HOOD POWER/ LTS. NFPA-96
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 AUTOMATED LIGHTING CONTROLLED REQUIRED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE SCHEDULING, TIMERS,
 OVER-RIDES AND TYPES OF DEVICES. PLEASE
 SHOW ALL CONTROL/OVER RIDE LOCATIONS.
 PLEASE SEE ALL SEPARATE SPACES WITH FLR
 TO CEILING HEIGHT PARTITIONS, WITH
 CONTROLS.
 PLEASE PROVIDE ENERGY CALCULATIONS AS
 REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1,
 415.2.C.
  
 PLEASE SEE THERE ARE SWITCHES BEING
 SHOWN ON PLANS WHICH DO NOT INDICATE
 CONTROL OF ANY PARTICULAR ITEM.?
  
 10) NOTE: PLEASE SHOW NEW OR EXISTING
 GFI RECEPT FOR ROOF TOP EQUIPMENT PER 210.8,210.63
  
 11) NOTE: PLEASE INDICATE THE AIC
 RATINGS FOR ALL NEW SERVICE
 MAINS/EQUIPMENT.
 110.9
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-13 Cont ID  
Sent By mawillia Date 2006-11-13 Time 16:00 Rev Time 0.00
Received By mawillia Date 2006-11-13 Time 15:59 Sent To  
Notes
2006-11-13 16:18:41*****DENIED*****
  
  
  
 PLEASE ACKNOWLEDGE COMMENTS FROM PREVIOUS FIRE PLAN
 REVIEW (10/12/2006) BY SHOWING ON THE PLANS HOW EACH
 ITEM WAS ADDRESSED.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By mawillia Date 2006-10-12 Time 10:20 Rev Time 0.00
Received By mawillia Date 2006-10-12 Time 10:20 Sent To  
Notes
2006-10-12 11:45:03*****DENIED*****
  
  
  
  
 1.)CONSTRUCTION, ALTERATION, ANDDEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
 AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B.
  
 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.)THE SCOPE OF THE INTERIOR BUILDOUT REQUIRING
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND PLANS ARE REQUIRED.
  
 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS
 AND EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 6.)ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE ADDRESS FOR THIS STRUCTURE.AS PER WEST PALM BEACH
 CODE, THE CHARACTERS (NUMBERS AND/OR LETTERS) SHALL BE
 NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING
 WITH THE BACKGROUND.IF USED, HURRICANE SHUTTERS SHALL
 NOT COVER OR CONCEAL ADDRESS.
  
 7.)ADDITIONAL MECHANICAL PERMITS AND PLANS ARE
 REQUIRED FOR HOOD/SUPPRESSION SYSTEM(S).
  
 8.)ON SHEET M-3 HOOD SYSTEM NOTE #1, REFERENCES SHALL
 BE MADE TO NFPA 96, 2004 EDITION.
  
 9.)AS PER WPBFR, DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By kstevens Date 2006-11-27 Time 17:42 Rev Time 0.00
Received By kstevens Date 2006-11-16 Time 17:42 Sent To  
Notes
2006-11-27 17:44:01DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEW
  
 1. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B"
 TO "D" IS NOT INDICATED
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT.
 ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C",
 AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B"
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES
 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004
 FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5
 PSI, NOT 1 PSI OR LESS.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
 ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE
 REQUIRED FOR PLAN REVIEW.
  
 H. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-29 Cont ID  
Sent By kstevens Date 2006-09-29 Time 08:38 Rev Time 0.00
Received By kstevens Date 2006-09-29 Time 08:38 Sent To  
Notes
2006-09-29 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (INDICATED
 AS EXISTING RELOCATING).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 08:56 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 08:56 Sent To  
Notes
2006-10-26 11:41:09TO "COMM" BD#14
2006-10-25 08:57:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-16 Cont ID  
Sent By pkrauss Date 2006-10-16 Time 10:20 Rev Time 0.00
Received By pkrauss Date 2006-09-08 Time 13:24 Sent To  
Notes
2006-09-13 00:00:00TO "COMM" BD#55
2006-09-08 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 14:58 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 12:36 Sent To  
Notes
2006-10-31 15:27:24 
 COMMENTS FROM REVIEW DATED 10-13-06:
  
 COMMENT 1, 2 ,3
  
 COMMENT 4: EF-2 TERMINATION TO THE ROOF IS NOT
 INDICATED ON PLAN SHEET M-1.2.THIS WAS NOT ADDRESSED.
 REFERENCED PLAN SHEET WAS REMOVED FROM THE RESUBMITTED
 PLANS.PLEASE PROVIDE DETAIL OF EQUIPMENT LOCATED ON
 THE ROOF.PROVIDE DETAIL OF REQUIRED CLEARANCES FROM
 ROOF SURFACE, FRESH AIR INTAKE IN RELATION TO EXHAUST
 TERMINATIONS, AS WELL AS CLEARANCES FOR THE GREASE DUCT
 TERMINATION TO PROPERTY LINES, CONTINGUOUS BUILDINGS
 ETC.2004 FMC 506.3.12.3.
  
 COMMENT 5 WAS NOT ADDRESSED.PLAN SHEET M-1 INDICATES
 EF-2 (WHICH THE LOCATION OR TERMINATION IS NOT
 INDICATED ON THE PLAN). IS THIS A GRILLE AT THE
 CEILING?A HOOD IS NOT SHOWN OVER THE OVEN.PLEASE
 INDICATE WHAT TYPE OF "OVEN" THIS IS.PLEASE
 REFERENCE 2004 FMC 507.2.1, TYPE I HOOD SHALL BE
 INSTALLED WHERE COOKING APPLIANCES PRODUCE GREASE OR
 SMOKE, SUCH AS OCCURS WITH GRIDDLES, FRYERS, BOILERS,
 OVENS, RANGES, AND WOK RANGES.A TYPE II HOOD IS SHALL
 BE INSTALLED WHERE COOKING OR DISHWASHING APPLIANCES
 THAT PRODUCE HEAT OR STEAM AND DO NOT PRODUCE GREASE OR
 SMOKE, SUCH AS STEAMERS, KETTLES, PASTA COOKERS &
 DISHWASHING MACHINES.PLEASE CLARIFY.PLEASE PROVIDE
 MANUFACTURER'S SUBMITTAL FOR THE OVEN.
  
 COMMENT6 WAS NOT ADDRESSED.(PLAN SHEET M-1.2 WAS
 REMOVED FROM SUBMITTAL SET)PLAN SHEET M-1.2 APPEARS
 TO HAVE A WALL THAT TERMINATES ABOVE THE ROOF THAT
 SEPARATES RTU-1 & EF-1. PER 2004 FMC 306.5, ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES.PLEASE NOTE, SHOULD ROOF HAVE A SLOPE
 GREATER THAN 4/14 PITCH SHOW COMPLIANCE WITH 306.5
 ITEMS 1 THROUGH 7.
  
 COMMENT 7 WAS NOT ADDRESSED.PLEASE INDICATE ACCESS TO
 ROOF.
  
 COMMENT8 WAS NOT ADDRESSED.PLEASE CLARIFY WHAT
 EQUIPMENTTHE20"X48" RETURN AIR DUCT & 20"X32"
 SUPPLY DUCT TERMINATING ON THE ROOF GO TO (RTU-1?)
  
 COMMENT 9 WAS NOT ADDRESSED.ADDITIONAL PERMITS
 REQUIRED FOR HOOD, FIRE SUPPRESSION, & WALK-IN COOLER.
 PLEASE PROVIDE PLANS AND MANUFACTURER'S SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  
  
 PLEASE NOTE, FAN SCHEDULE ON PLAN SHEET M-1 SHOWS EF-1
 AS A COOKING LINE HOOD FAN BUT THE PLAN INDICATES EF-1
 IN THE RESTROOM
  
 PLEASE NOTE, GREASE DUCT ENCLOSURE OR SHAFT SHALL NOT
 ENCLOSE ANY OTHER DUCT SYSTEMS PER NFPA 96-01 SECTION
 7.7.5.2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By pkrauss Date 2006-10-13 Time 07:45 Rev Time 0.00
Received By pkrauss Date 2006-10-12 Time 15:32 Sent To  
Notes
2006-10-13 07:57:06DENIED:
 PLEASE CLARIFY THE FOLLOWING:
 1.PLAN SHEET A-1 INDICATES WEST WALL IS INDICATED AS
 A EXISTING TENANT DEMISING WALL.IS THIS AN EXTERIOR
 WALL OR IS THIS INTERIOR TO THE TENANT SPACE.PLEASE
 CLARIFY IF THIS WILL BE SEPARATED OR PROTECTED BY AN
 ENCLOSURE OR SHAFT?
  
 2.PLAN SHEET M-1 DUCT MISSING FIRE DAMPER FROM
 20"X48" R/A DUCT PENETRATING TENANT DEMISING WALL.
  
 3.PLEASE PROVIDE CLEARANCES FROM THE GREASE DUCT TO
 COMBUSTIBLES.SHOW COMPLIANCE WITH 2004 FMC 506.3.6.
  
 4.PLAN SHEET M-1 INDICATES EF-2 SERVES A COOK LINE
 HOOD TERMINATING ON THE ROOF.THIS IS NOT SHOWN ON
 PLAN SHEET M-1.2.
  
 5.PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 HOOD & GREASE DUCT:
 A) TYPE I OR TYPE II HOOD
 B) INDICATE HOOD & DUCT MATERIAL AND GAUGE 2004
 FMC 507.4, 507.5, 506.3.1.1 & 506.4.
 C) INDCIATE DUCT SIZE AND LAYOUT
 D) AIR VELOCITY THROUGH THE GREASE DUCT SHALL
 COMPLY WITH 2004 FMC 506.3.4
  
 6.PLAN SHEET M-1.2 APPEARS TO HAVE A WALL THAT
 TERMINATES ABOVE THE ROOF THAT SEPARATES RTU-1 & EF-1.
 PER 2004 FMC 306.5, ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES.PLEASE NOTE,
 SHOULD ROOF HAVE A SLOPE GREATER THAN 4/14 PITCH SHOW
 COMPLIANCE WITH 306.5 ITEMS 1 THROUGH 7.
  
 7.PLEASE INDICATE ACCESS TO ROOF.
  
 8.PLEASE CLARIFY WHAT EQUIPMENTTHE20"X48" RETURN
 AIR DUCT & 20"X32" SUPPLY DUCT TERMINATING ON THE ROOF
 GO TO (RTU-1?)
  
 9.ADDITIONAL PERMITS REQUIRED FOR HOOD, FIRE
 SUPPRESSION, & WALK-IN COOLER.PLEASE PROVIDE PLANS
 AND MANUFACTURER'S SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By kstevens Date 2006-11-16 Time 16:52 Rev Time 0.00
Received By kstevens Date 2006-11-16 Time 16:52 Sent To  
Notes
2006-11-17 06:45:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 *******FROM 1ST REVIEW*******
  
 1. ALL SHEETS. THE ARCHITECTS TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS FOUND
 ON THE DBPR WEBSITE. FAC 61G1-16.004(1)
 AND FS 481.2055. (SEE ATTACHED SHEET). ****RESPONSE
 NOTED. SUBMIT A LETTER FROM DBPR INDICATING APPROVAL OF
 THIS TEMPORY ARRANGEMENT. I DO NOT HAVE THE AUTHORITY
 TO WAIVE THIS REQUIREMENT OF THE FLORIDA ADMINISTRATIVE
 CODE/FLORIDA STATUTES.
  
 2. ROUTE PLANS TO DBPR HOTEL AND
 RESTURANT DIVISION FOR REVIEW. MINIMUM 2
 SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS"
 REQUIRED FOR REVIEW.
 SECTION 102.2.1.
 ****RESPONSE NOTED. THIS IS REQUIRED FOR THE PLAN
 REVIEW AND SHALL BE REVIEWED BY DBPR, PLANS STAMPED AND
 WORKSHEETS ATTACHED AS REQUESTED.
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED.
 PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
 ****RESPONSE NOTED BUT NOT ACCEPTABLE. PLEASE CONTACT
 ENVIRONMENTAL COMPLIANCE. GREASE TRAP INSIDE NOT
 APPROVED. PER MUNICIPAL CODE A MINIMUM 750 GAL.GREASE
 INTERCEPTOR IS REQUIRED.
  
 4. OK
 5. OK
 6. OK
  
 7. SHT P-1 WATER FILTERS SHALL BE
 COMPLIANT WITH NSF-42. SUBMIT MANUF.
 SPECIFICATION SHEETS.
 ****RESPONSE NOTED. MANUFACTURE CUT SHEET INDICATED WAS
 NOT FOUND IN RESUBMITTAL.
  
 8. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED. THE CORRESPONDING LENGTH FROM "B"
 TO "D" IS NOT INDICATED
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED. THE DISTANCE SHOWN IS NOT CORRECT.
 ADDING WHAT IS SHOWN IS MINIMUM 68' FROM "F" TO "C",
 AND 64' FROM "F" TO "A" BUT THE SECTION BETWEEN "B"
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED. FLORIDA PUBLIC UTILITIES PROVIDES
 2LB OR .5 LB WITH A .5 INCHWC PRESSURE DROP. FBC-2004
 FUEL GAS TABLE 402.4(2). INDICATE THE PRESSURE AS .5
 PSI, NOT 1 PSI OR LESS.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
 ****RESPONSE NOTED. MANUF. SHEETS NOT SUBMITTED AND ARE
 REQUIRED FOR PLAN REVIEW.
  
 H. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-01 Cont ID  
Sent By kstevens Date 2006-09-29 Time 07:34 Rev Time 0.00
Received By kstevens Date 2006-09-29 Time 07:34 Sent To  
Notes
2006-09-29 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. ALL SHEETS. THE ARCHITECTS TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS FOUND
 ON THE DBPR WEBSITE. FAC 61G1-16.004(1)
 AND FS 481.2055. (SEE ATTACHED SHEET).
  
 2. ROUTE PLANS TO DBPR HOTEL AND
 RESTURANT DIVISION FOR REVIEW. MINIMUM 2
 SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS"
 REQUIRED FOR REVIEW.
 SECTION 102.2.1.
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED.
 PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
  
 4. SHT A-5 PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
  
 5. SHT P-1 ALL EQUIPMENT & FIXTURES
 UTILIZED FOR STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH
 AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP. SECTION 802.1.1. - FLOOR SINKS
 ARE REQUIRED PER SECTION 802.3.
  
 6. SHT P-1 PLUMBING NOTES #13 AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED AT QUICK CLOSING
 VALVES SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", (NOT
 IN THE CEILING), PER PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. (ICE
 MAKERS, DISHWASHERS, ETC).
  
 7. SHT P-1 WATER FILTERS SHALL BE
 COMPLIANT WITH NSF-42. SUBMIT MANUF.
 SPECIFICATION SHEETS.
  
 8. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (INDICATED
 AS EXISTING RELOCATING).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2006-11-03 Cont ID  
Sent By mflis Date 2006-11-03 Time 11:50 Rev Time 0.00
Received By mflis Date 2006-11-03 Time 11:50 Sent To  
Notes
2006-11-03 11:51:05INTERIOR REMODEL ONLY - NO DMP REVIEW NECESSARY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved