Plan Review Details - Permit 06090035
Plan Review Stops For Permit 06090035
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-12 Cont ID  
Sent By pkrauss Date 2006-09-12 Time 09:12 Rev Time 0.00
Received By pkrauss Date 2006-09-06 Time 08:56 Sent To  
Notes
2006-09-06 00:00:00TO "TGORDON" DESK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-25 Cont ID  
Sent By pschmitz Date 2006-09-25 Time 10:50 Rev Time 0.00
Received By pschmitz Date 2006-09-25 Time 10:50 Sent To  
Notes
2006-09-25 00:00:00WINE COOLER APPROVED, PER PHK & HM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-12 Cont ID  
Sent By pkrauss Date 2006-09-12 Time 09:12 Rev Time 0.00
Received By pkrauss Date 2006-09-12 Time 09:12 Sent To  
Notes
2006-09-12 00:00:00HVAC DUCTS ONLY / WINE COOLER STILL
 UNDER REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By pkrauss Date 2006-09-07 Time 06:51 Rev Time 0.00
Received By pkrauss Date 2006-09-07 Time 06:51 Sent To  
Notes
2006-09-07 00:00:00DENIED:
 PLEASE CLARIFY THE FOLLOWING:
 1.PROVIDE COMPLETE SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE
 CONDENSING UNIT.IS AN INTERIOR
 LOCATION ACCEPTABLE?
  
 CONTRACTOR INDICATED WATER TAP INTO
 EXISTING CONDENSOR WATER LINES.CALLED
 ED O'NEAL ENGINEER (239-454-5511)
 AWAITING RESPONSE - HOW MANY EXTRA UNITS
 WILL THE EXISTING SYSTEM SUPPORT?