Plan Review Details - Permit 06090025
Plan Review Stops For Permit 06090025
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 15:15 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 15:15 Sent To M
Notes
2006-09-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 12:28 Rev Time 0.00
Received By tgordon Date 2006-09-06 Time 15:18 Sent To  
Notes
2006-09-06 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By tgordon Date 2006-09-29 Time 13:51 Rev Time 0.30
Received By tgordon Date 2006-09-29 Time 13:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 12:21 Rev Time 0.25
Received By tgordon Date 2006-09-12 Time 12:20 Sent To  
Notes
2006-09-12 00:00:00*** DENIED ***
 1) NEED TO SUBMIT TWO COPYS OF THE
 ENERGY CAL'S.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 3) SHOW ON MECHANICAL PLANS HOW AIR WILL
 RETURN TO AHU (AND GRILL SIZE).
  
 4) PLANS NEED TO BE SIGNED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. PER FBC
 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.