Plan Review Details - Permit 06082241
Plan Review Stops For Permit 06082241
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-19 Cont ID  
Sent By amorse Date 2008-04-19 Time 10:24 Rev Time 0.00
Received By amorse Date 2008-04-19 Time 10:24 Sent To PC
Notes
2008-04-19 10:25:45 
  
 PASSED
  
 REVISION ADDITION OF 4 DOORS TO SCOPE OF WORK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By amorse Date 2008-03-19 Time 18:24 Rev Time 0.00
Received By amorse Date 2008-03-19 Time 18:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-11 Cont ID  
Sent By amorse Date 2008-03-11 Time 15:37 Rev Time 0.00
Received By amorse Date 2008-03-11 Time 15:37 Sent To PC
Notes
2008-03-11 16:21:44 
  
 DENIED
  
 1)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC PLEASE NOTE THAT WIND EXPOSURE CATEGORY WAS NOT ON
 ORIGINAL SHEET A-1 AND SCOPE WAS FOR INTERIOR WORK
 ONLY
  
 2)PROVIDE STRUCTURAL DETAILS FOR ANY REPAIRS TO
 WINDOW OPENINGS AND INFILL OF OPENINGS WHERE WINDOWS
 ARE REMOVED
  
 3)PROVIDE CORRECT COMPLIANCE REPORT FOR THE STATEWIDE
 PRODUCT APPROVAL (SEE 2ND PAGE OF PRODUCT APPROVAL)
 MIAMI-DADE #05-0930.03 AND DRAWING 05-TRA-0003 THAT CAN
 BE DOWNLOADED FROM THE LINK ON PAGE 2
  
 4)EXTERIOR ELEVATION SHEETS ARE REQUIRED TO BE
 STAMPED BY THE HISTORIC PRESERVATION DIVISION
  
 5)INCREASE VALUE ON ORIGINAL PERMIT FOR NEW SCOPE OF
 WORK TO INCLUDE ALL NEW MATERIAL, REPAIRS AND WINDOW
 INSTALLATION
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-13 Cont ID  
Sent By amorse Date 2007-05-13 Time 14:32 Rev Time 0.00
Received By amorse Date 2007-05-13 Time 14:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By amorse Date 2007-03-26 Time 17:56 Rev Time 0.00
Received By amorse Date 2007-03-26 Time 17:56 Sent To PC
Notes
2007-03-26 18:02:01 
 DENIED
  
 1) IN AN EXISTING BUILDING A DESIGN PROFFESIONAL MUST
 ELECT THE LEVEL OF ALTERATION PER 301.5 OF EXISTING
 BUILDING CODE AND ALONG WITH THE TYPE OF CONSTRUCTION
 STATE ON THE DRAWINGS
  
 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. THE VALUE WAS NOT UPDATED FROM PREVIOUS
 REVIEW AND HAS NOW BEEN CHANGED TO REFLECT CORRECT
 VALUE AND ADDITIONAL FEES ARE DUE
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By alange Date 2006-10-11 Time 09:06 Rev Time 0.00
Received By alange Date 2006-10-11 Time 09:06 Sent To  
Notes
2006-10-11 09:19:21DENIED
  
 1.PERMIT VALUATION:VALUE ON PERMIT SHOULD REFLECT
 ALL MATERIALS AND LABOR FOR THE PROJECT. IFTHE
 PERMIT VALUATION IS NOT CORRECTED THE VALUE WILL BE
 ADJUSTED ACCORDING TO MARSHALL AND SWIFTS ESTIMATING
 GUIDE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-04 Cont ID  
Sent By btrobaug Date 2007-01-04 Time 10:29 Rev Time 1.00
Received By btrobaug Date 2007-01-04 Time 10:21 Sent To P
Notes
2007-01-04 10:28:53 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By btrobaug Date 2006-09-19 Time 08:07 Rev Time 1.00
Received By btrobaug Date 2006-09-18 Time 17:38 Sent To P
Notes
2006-09-18 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 3/0 SERVICE CONDUCTORS ARE NOT
 LARGE ENOUGH FOR THE CALCULATED LOAD.
 SEE 310.15(B)(6).
  
 2} THERE IS NO WATER HEATER LISTED IN
 THE HOUSE PANEL, YET THE REQUIRED
 LAUNDRY CIRCUIT (WASHER) IS LISTED IN
 THAT PANEL. PLEASE VERIFY THERE IS NO
 HOT WATER TO BE SUPPLIED TO THE WASHER.
 THE GARAGE PLUMBING DOES NOT SEEM TO BE
 ON THE PLUMBING RISR.
  
 3} THE BREAKFAST ROOM LISTED ON THE
 PANEL SCHEDULES,PANELS 1, 2, AND 3 MUST
 BE ON A 20AMP CIRCUIT PER 210.52(B)(1).
  
 4} THE BATH CIRCUITS SHALL BE 20 AMP.
 210.11(C)(3).
  
 5} PLEASE SEE ALL KITCHEN RECEPTACLES
 MUST COMPLY WITH 210.52(B). TWO
 RECEPTACLES IN UNIT #1, ONE LISTED ON
 C13 AND THE OTHER NOT LISTED BUT ON WITH
 A LIVING ROOM OUTLET, DO NOT COMPLY.
  
 6} THE BREAKFAST ROOM CIRCUIT IN UNIT #2
 MAY NOT FEED THE LIVING ROOM OUTLETS.
 210.52(B)(2).
  
 7} UNIT #3 KITCHEN NEEDS A RECEPTACLE
 ADDED BY THE RANGE TO COMPLY WITH
 210.52(C)(1).
  
 8} THE SMOKE DETECTOR LOCATION OUTSIDE
 THE BEDROOMS DO NOT COMPLY WITH THE
 "IMMEDIATE VICINITY" INTENT OF R313.1.1
 2.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-14 Cont ID  
Sent By adarroug Date 2008-04-14 Time 16:52 Rev Time 0.00
Received By adarroug Date 2008-04-14 Time 16:52 Sent To B
Notes
2008-04-14 16:52:59TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 10:20 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 10:20 Sent To B
Notes
2008-03-14 10:21:02TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 16:14 Sent To B
Notes
2008-02-29 16:15:18TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 11:27 Sent To P
Notes
2007-04-24 11:27:41TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-29 Cont ID  
Sent By adarroug Date 2006-12-29 Time 08:36 Rev Time 0.00
Received By adarroug Date 2006-12-29 Time 08:36 Sent To E
Notes
2006-12-29 08:37:21TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-11 Cont ID  
Sent By alange Date 2006-10-11 Time 09:20 Rev Time 0.00
Received By alange Date 2006-09-06 Time 16:50 Sent To  
Notes
2006-09-06 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 13:43 Rev Time 0.20
Received By tgordon Date 2007-01-09 Time 13:43 Sent To B
Notes
2007-01-09 13:44:38NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By mperson Date 2007-05-02 Time 16:38 Rev Time 0.45
Received By mperson Date 2007-05-02 Time 16:37 Sent To B
Notes
2007-05-02 16:40:39****************PROVISO****************
 PER FBC-2001 PLUMBING, SECTION 1002.3 "S" TRAPS ARE
 PROHIBITED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By mperson Date 2007-01-09 Time 10:05 Rev Time 0.33
Received By mperson Date 2007-01-09 Time 10:05 Sent To M
Notes
2007-01-09 11:22:34DENIED 2ND TIME
 REFERENCE: FBC-2001 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTED SHEET P2 SANITARY RISER
 DIAGRAM TO MEET CODE COMPLIANCE:
  
 1.SHEET P2 FIRST FLOOR UNIT #1: A} VENT REQUIRED FOR
 DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING,
 SEC. 901.2.1 B} PLEASE INDICATE DOUBLE BOWL SINK
 W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001
 SEC. 409.3.1.
  
 2.SHEET P2 FIRST FLOOR UNIT #2: A} VENT REQUIRED FOR
 DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING,
 SEC. 901.2.1. B} PLEASE INDICATE DOUBLE BOWL SINK
 W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001
 PLUMBING SEC. 409.3.1.
  
 3. SHEET P2 SECOND FLOOR UNIT #3: A} VENT REQUIRED FOR
 BATHROOM GROUP PER FBC-2001 PLUMBING SEC. 909.1. B}
 PLEASE INDICATE DOUBLE BOWL SINK W/ DISHWASHER AND ADD
 DRAIN FOR DISHWASHER PER FBC-2001 PLUMBING SEC.
 409.3.1.
  
 4. SHEET P2 GARAGE WASHING MACHINE: A} PLEASE INDICATE
 STANDPIPE FOR WASHING MACHINE DRAIN PER FBC-2001
 PLUMBING, SEC. 802.4. B} PLEASE INDICATE CLEANOUT FOR
 WASHING MACHINE AT FOUR FEET ABOVE FINNISH FLOOR (4'
 A.F.F.) PER FBC-2001 PLUMBING SEC. 708.10.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By btrobaug Date 2007-01-04 Time 10:37 Rev Time 0.55
Received By mperson Date 2006-10-02 Time 15:01 Sent To B
Notes
2006-10-02 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW. PLEASE
 REFERENCE THE CORRECTED DRAWINGS IN RED
 INK FOR RESUBMITTAL:
  
 1. PLEASE CHANGE THE WORDING ON SHEET
 P-1, COPPER PIPE SCH. 40 TO READ, COPPER
 PIPE TYPE "L" FOR THE RESUBMITTAL.
 2. PER FBC-2004 SEC. 608.15.4.2 HOSE
 CONNECTIONS: PLEASE CHANGE THE WORDING
 ON SHEET P-1, PLUMBING NOTE #4 TO READ
 VACUUM BREAKERS INSTEAD OF BACKFLOW
 PREVENTERS.
 3. THE S.V.= STUDOR VENTS (AUTOMATIC AIR
 VENTS) INDICATED ON SHEET P-2 ARE NOT
 REQUIRED BECAUSE THE SANITARY ISOMETRIC
 PLUMBING RISER DIAGRAM INDICATES V.T.R.
 (VENTS THROUGH ROOF). PLEASE DELETE THE
 S.V. FOR THE RESUBMITTAL.
 4. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE KITCHEN SINK INDICATED ON
 SHEET P-2 SANITARY RISER DIAGRAM FOR
 UNIT #2 IS PIPED WRONG, PLEASE REFERENCE
 THE CORRECTED DRAWING IN RED INK FOR
 RESUBMITTAL.
 5. PER FBC-2004 PLUMBING, SECTION 1002.1
 A FIXTURE SHALL NOT BE DOUBLE TRAPPED.
 NOTE: THE W.C. INDICATED ON SHEET P-2
 SANITARY RISER DIAGRAM HAS AN INTREGRAL
 TRAP THEREFORE A TRAP NEED NOT BE
 INDICATED FOR THE W.C. ON THE SANITARY
 RISER DIAGRAM. PLEASE CORRECT FOR THE
 RESUBMITTAL.
 6. PER FBC-2004 PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED FIXTURES:
 ONE (1) AUTOMATIC CLOTHES WASHER
 REQUIRED PER TWENTY (20) DWELLING UNITS.
 PLEASE INDICATE ON THE RESUBMITTAL THE
 AUTOMATIC CLOTHES WASHER LOCATION.
 7. PER FBC-2004 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: THE TUBS
 INDICATED ON SHEET P-2, UNITS #1 AND #2
 REQUIRE VENTS.
 8. PLEASE INDICATE ON THE RESUBMITTAL IF
 THERE IS ANY PLUMBING IN THE EXISTING
 GARAGE. IF THERE IS PLUMBING IN THE
 GARAGE PLEASE INDICATE PLUMBING ON THE
 SANITARY ISOMETRIC RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***