2006-09-15 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06082221 |
| ADD: 500 PALM ST SUITE "C" |
| CONT: MIKE MOORE CONST |
| TEL: (561)748-7000 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) SHEET A2.1 THE RESTROOM DOOR IS |
| MISSING THE 18" CLEAR SPACE LATCH SIDE |
| OF DOOR.11-4.13.6 MANEUVERING |
| CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| DOORS THAT ARE NOT |
| AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| AREA WITH IN THE REQUIRED CLEARANCES |
| SHALL BE CLEAR & LEVEL. |
| |
| 4) EXISTING BUILDING CODE LEVEL 2 |
| ALTERATION: 611.1 MINIMUM REQUIREMENTS: ALTERATIONS |
| SUBJECT TO THIS CHAPTER |
| SHALL COMPLY WITH THE REQUIREMENTS OF |
| CHAPTER 13 OF THE FLORIDA BUILDING CODE |
| BUILDING. |
| 13-101.1.3 RENOVATIONS. |
| RENOVATED COMMERCIAL BUILDINGS SHALL, |
| WHEN APPLICABLE (SEE SECTION 202 ), |
| COMPLY WITH THE PRESCRIPTIVE |
| REQUIREMENTS CONTAINED IN FORM 400 C OR |
| WITH METHOD B OF SUBCHAPTER 13-4 FOR |
| INSULATION, HVAC SYSTEMS, LIGHTING, |
| WATER HEATING SYSTEMS AND EXTERIOR |
| ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED. |
| |
| 5)ENGINEER GLENN GOLDBERG SEAL USING THE |
| PHRASE "CERTIFICATE" |
| RULE 61G155-23.001(1) F.A.C. |
| THE FLORIDA BOARD OF PROFESSIONAL |
| ENGINEERS HAS CLEANED UP THE APPEARANCE |
| OF THE SEAL BY ELIMINATING OBSOLETE |
| CONTENT AND CHANGING THE WORD |
| "CERTIFICATE" TO "LICENSE". A GRACE |
| PERIOD RAN THROUGH DEC. 31,2005. |
| |
| 6) ENGINEER GLENN GOLDBERG: |
| 61G15-23.002(2)FL. ADMIN. CODE. PLANS |
| SIGNED & SEALED BY A PROFESSIONAL |
| ENGINEER SHALL INCLUDE EITHER THE NAME, |
| ADDRESS AND LICENSE NUMBER OF THE |
| ENGINEER OR, THE NAME AND LICENSE NUMBER |
| OF THE ENGINEER AND THE NAME, ADDRESS |
| AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH |
| WHICH THE ENGINEER IS PRACTICING |
| (471.025 F.S. AND 471.023 F.S.). |
| |
| 7) VINTAGE DESIGN AND CONSTRUCTION |
| STRUCTURAL ENGINEER CONSULTANT: |
| 471.023 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ENGINEER |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| ADD THE NUMBER TO EACH SHEET.THIS MAY |
| BE ADDED BY HAND. |
| |
| 8) FL BLD CODE 1609.1.4 : COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) TRUSS ANCHORS, ANCHOR TIES |
| B) ROOFING ASSEMBLIES |
| |
| 9) W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 10) SHEET S-1 INDICATES THE USE OF AN |
| EXISTING ROOF DRAIN, IT APPEARS TO |
| PENETRATE THE EXTERIOR WALL AND DRAIN |
| INTO AN SCUPPER AND DOWN SPOUT SYSTEM. |
| NO MENTION OF AN EMERGENCY OVERFLOW? |
| 1503.4.3 |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW |
| WATER IS NOT PROVIDED, OVERFLOW SCUPPERS |
| SHALL BE PLACED IN WALLS OR PARAPETS NOT |
| LESS THAN 2 INCHES (51 MM) NOR MORE THAN |
| 4 INCHES (102 MM) ABOVE THE FINISHED |
| ROOF COVERING AND SHALL BE LOCATED AS |
| CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| LEADERS OR DOWNSPOUTS OR WALL AND |
| PARAPET SCUPPERS. AN OVERFLOW SCUPPER |
| SHALL BE SIZED IN ACCORDANCE WITH THE |
| FLORIDA BUILDING CODE, PLUMBING. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |