Plan Review Details - Permit 06082221
Plan Review Stops For Permit 06082221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-11 Cont ID  
Sent By jwitmer Date 2007-01-11 Time 08:04 Rev Time 1.22
Received By jwitmer Date 2007-01-11 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By jwitmer Date 2006-11-22 Time 13:50 Rev Time 2.22
Received By jwitmer Date 2006-11-22 Time 13:50 Sent To  
Notes
2006-11-22 13:51:00PERMIT: 06082221
 ADD: 500 PALM ST SUITE "C"
 CONT: MIKE MOORE CONST
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3 2ND REQUEST #8 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1609.1.4 : COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 B) ROOFING ASSEMBLIES
 THE ROOF REPORT SUBMITTED DOESN'T HAVE THE FLORIDA
 COVERSHEET
 NOR ARE THE SUBSYSTEM REPORTSHIGHLIGHTED AS TO WHICH
  
 SUBSYSTEM IS BEING USED. NOTE OVER 1/2 OF THE SUBSYSTEM
 REPORTS ARE FOR
 INSULATED ROOFS. OTHER SUBSYSTEM REPORTS ARE TO BE USED
 ONLY AS AN TILE
 UNDERLAYMENT. PLEASE NOTE MOST OF THE SUBSYSTEM REPORTS
 ONLY HAVE A
 MAXIMUM DESIGN PRESSURE OF -45 TO -60 WITH A LIMITATION
 # 7, NO
 ENHANCED FASTENING!!!!PLEASE HAVE THE DESIGN
 PROFESSIONALS REVIEW
 FOR CODE COMPLIANCE BEFORE SUBMITTAL TO THE CITY
 !!!!!!!!!!!!!!!!!!!!
  
 9) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 11:46 Rev Time 1.33
Received By jwitmer Date 2006-09-15 Time 11:23 Sent To PC
Notes
2006-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06082221
 ADD: 500 PALM ST SUITE "C"
 CONT: MIKE MOORE CONST
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET A2.1 THE RESTROOM DOOR IS
 MISSING THE 18" CLEAR SPACE LATCH SIDE
 OF DOOR.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 4) EXISTING BUILDING CODE LEVEL 2
 ALTERATION: 611.1 MINIMUM REQUIREMENTS: ALTERATIONS
 SUBJECT TO THIS CHAPTER
 SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE
 BUILDING.
 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL,
 WHEN APPLICABLE (SEE SECTION 202 ),
 COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400 C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED.
  
 5)ENGINEER GLENN GOLDBERG SEAL USING THE
 PHRASE "CERTIFICATE"
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 6) ENGINEER GLENN GOLDBERG:
 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 7) VINTAGE DESIGN AND CONSTRUCTION
 STRUCTURAL ENGINEER CONSULTANT:
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 8) FL BLD CODE 1609.1.4 : COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS, ANCHOR TIES
 B) ROOFING ASSEMBLIES
  
 9) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S-1 INDICATES THE USE OF AN
 EXISTING ROOF DRAIN, IT APPEARS TO
 PENETRATE THE EXTERIOR WALL AND DRAIN
 INTO AN SCUPPER AND DOWN SPOUT SYSTEM.
 NO MENTION OF AN EMERGENCY OVERFLOW?
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 10:05 Sent To PC
Notes
2008-08-28 10:06:04LTR FROM ARCHITECT DELTETING ALL LOW VOLTAGE SCOPE OF
 WORK FROM PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-07-24 Cont ID  
Sent By btrobaug Date 2008-07-24 Time 10:31 Rev Time 0.00
Received By btrobaug Date 2008-07-24 Time 10:31 Sent To PC
Notes
2008-07-24 10:32:20 
  
 SUBMBITTAL---CHANGED MOTION SENSOR, ARCHITECT./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2007-01-10 Time 12:13 Sent To  
Notes
2007-01-10 12:48:59** NOTES REDLINED **
  
 1) LOCATION OF FIRE PUMP TO BE IN A RATED ROOM AND
 LOCATION WAS APPROVED BY THE FIRE MARSHAL'S OFFICE.
 LOCATION OFKNOX-BOX FOR ACCESS TO BE DETERMINED BY
 THE FIRE MARSHAL'S OFFICE AND MUST BE IN PLACE BEFORE
 ANY FINAL ELECTRICAL INSPECTION. LOCATION/INSTALLATION
 OF THIS EXISTING FIRE PUMP/CONTROLLER LOCATION IS NOT
 PER ELECTRICAL PLAN REVIEW.
  
 2) LOCATION OF EXISTING SERVICE MAINS AND METERS SHALL
 CONTAIN SIGNAGE DENOTING THE LOCATION OF THE FIRE
 PUMP/FIRE PUMP CONTROLLER FOR THE DISCONNECTING MEANS
 AND HOW TO OBTAIN ACCESS ETC.
 SIGNAGE SHALL CONTAIN LETTERING OF A MINIMUM OF 1INCH
 IN HEIGHT WITH A CONTRASTING BACKGROUND. SIGNAGE SHALL
 BE PERMANENTLY ATTACHED TO THE BUILDING/STRUCTURE AND
 SHALL BE COMPLETELY RESISTANT TO FADING AS THIS IS
 LOCATED OUTSIDE.
 230.2E
  
  
 IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By dpalmer Date 2006-11-17 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2006-11-17 Time 09:47 Sent To  
Notes
2006-11-17 10:59:54** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE MOSTLY NEW COMMENTS BASED ON
 THE REVISED RISER DIAGRAM SUBMITTED.
  
  
 1NOTE: PLEASE SEE RISER NOW INDICATES THE NEW "TENANT
 SPACE" SERVICE BEING FROM THE BUILDINGS MAIN ELECTRICAL
 SERVICE, HOWEVER PLEASE PROVIDE THE SIZE OF THE
 EXISTING MAIN ELECTRICAL SERVICE AND THE LOAD ON SUCH
 SERVICE WITH THE NEW TENANTS SERVICE LOAD BEING ADDED
 TO IT.
 NEC 220
 FBC106.3.5.1.2 ADMIN SECT.
  
 2) NOTE: PLEASE SUBMIT AND PROVIDE AIC RATINGS FOR NEW
 SERVICE EQUIPMENT. PLEASE SEE 110.9 AND 240.12 FOR
 SELECTIVE COORDINATION.
  
 3) NOTE: PLEASE SEE FIRE PUMP ROOM FOR EXISTING FIRE
 PUMP IS BEING SHOWN IN A NEW PROPOSED TENANT SPACE.
 PLEASE KNOW, AS THIS BUILDING DOES NOT SEEM TO MEET THE
 EXCEPTIONS IN THE CODE UNDER NFPA-20 (FIRE
 PUMPS)(CHAPTERS 6-3, AND ALSO CHAPER 7) AND NEC 695,
 230.70, 230.2, , PLEASE KNOW THE ACCESS TO THE FIRE
 PUMP AND ANY FIRE PUMP CONTROLLER MUST BE FROM A COMMON
 AREA/CORRIDOR OR OUTSIDE. ACCESS THROUGH ONES TENANTS
 SPACE IS NOT PERMITTED.
  
  
 4) NOTE: PLEASE SEE METHOD "A" IS BEING SUBMITTED FOR
 THIS NEW SPACE HOWEVER THE METHOD "A" DOES NOT SEEM TO
 CORRELATE WITH SCOPE OF. PLEASE SEE OTHER METHODS. "B".
 13-415.2
 PLEASE ALSO SEE THAT THE CALCULATIONS AS SUBMITTED
 INDICATE MANUAL CONTROLS, HOWEVER AUTOMATED CONTROLS
 ARE SHOWN ON PLANS?
 PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD.
 13-415.1.AB.1, 13-415.2.ABC.1
  
 5) NOTE: PLEASE SE RISER AS SHOWN DOES NOT SEEM TO
 INDICATE ANY "MAIN" ON THE LINE SIDE OF THE GUTTER,
 THEREFORE AND EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT
 BE INSTALLED TO THE METER FROM THE GUTTER. IF A MAIN
 DOES EXISTS ON THE LINE SIDE OF THE GUTTER THEN ONE
 WOULD BE INSTALLED HOWEVER THE NEW TENANT METER WOULD
 THEN CONTAIN NOTES FOR A FLOATING NEUTRAL KIT.
 PLEASE SEE 250.6, 250.24B.
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 16:52 Sent To  
Notes
2006-09-09 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE 700.12E AS THE
 EMERGENCY LTS AND EXT LTS ARE REQUIRED
 TO BE CIRCUITED TO THE LOCAL AREA
 LIGHTING.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE CLARIFY "FIRE PUMP "
 EQUIPMENT BEING NOTED AND SHOWN IN ROOM.
 THIS ROOM WOULD REQUIRE AT LEAST A 1 HR
 RATING IF FULLY SPRINKLED.
 PLEASE SEE NFPA-20 FOR INSTALLATION OF
 FIRE PUMPS AND REQUIRD SEPARATION.
 PLEASE ALSO SEE NEC 695
  
 3) NOTE: PLEASE SEE RISER IS SHOWING A
 NEW 150A DISCONNECT BEING PROPOSED ON
 THE LINE SIDE THE FPL'S METER SHOWN AS
 EXISTING ON RISER??
 PLEASE SEE THE DISCONNECT WOULD BE ON
 THE LOAD SIDE OF ANY METERING DEVICES BY
 FPL. PLEASE SEE RISER ALREADY SHOWS AN
 EXISTING MAIN DISCONNECT??
 PLEASE CLARIFY AND PLEASE SEE FPL
 PERMITTED METERING LOCATIONS AND SERVICE
 STANDARDS GUIDE.
 PLEASE KNOW, AS THIS IS BEING SHOWN AS
 EXISTING, PLEASE KNOW A NEW SERVICE FOR
 THIS SPACE IS NOT PERMITTED FROM FPL.
 THIS SPACE IS NOT A SEPARATE BUILDING
 AND ANY NEW "TENANT SPACE" MUST BE FED
 FROM THE EXISTING SERVICE FOR THE ENTIRE
 BUIDLING.
 PLEASE SEE 230.2, 230.70, 230.72.
  
 4) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS (3 OR MORE HRS) AT 125%.
 215.3,230.42 ETC..
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 12:20 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 12:20 Sent To  
Notes
2007-01-16 12:28:39*****APPROVED*****
  
  
 PLAN SHEET PE-1 AND THE KODIAK FIRE SPRINKLER WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-06 Cont ID  
Sent By mawillia Date 2006-12-06 Time 14:16 Rev Time 0.00
Received By mawillia Date 2006-12-06 Time 14:16 Sent To  
Notes
2006-12-06 14:20:18*****PROVISO*****
  
  
  
 APPROVED PENDING THE CONCERN/MATTER OF THE FIRE PUMP
 ROOM HAS BEEN ADDRESSED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 10:30 Sent To  
Notes
2006-09-13 00:00:00***DENIED***
  
 1) PLEASE PROVIDE FURTHER INFORMATION
 REGARDING EXISTING FIRE PUMP/EQUIPMENT.
 IF THIS ROOM SERVICES THE BUILDING
 SPRINKLER SYSTEM, WHAT ACCESS FOR FIRE
 PERSONNEL TO THAT ROOM IS PROVIDED
 EXCLUSIVE OF UNIT C? IF THAT IS THE ONLY
 ACCESS, HOW IS THAT ROOM ACCESSED AFTER
 NORMAL BUSINESS HOURS?
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 13:45 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 13:45 Sent To E
Notes
2008-08-12 13:46:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 11:48 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 11:48 Sent To E
Notes
2008-06-30 11:50:04TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 10:10 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 10:10 Sent To M
Notes
2008-05-13 10:10:44TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 14:26 Sent To  
Notes
2007-01-09 14:04:52TO "BOB"#9
2006-12-26 14:26:56WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 15:05 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 15:02 Sent To  
Notes
2006-11-16 11:47:20TO "BOB"#17
2006-11-08 15:02:36WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 11:23 Rev Time 0.00
Received By jwitmer Date 2006-09-05 Time 10:28 Sent To  
Notes
2006-09-07 00:00:00TO "BOB"#2
2006-09-05 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-14 Cont ID  
Sent By tgordon Date 2008-05-14 Time 08:36 Rev Time 0.20
Received By tgordon Date 2008-05-14 Time 08:36 Sent To  
Notes
2008-05-14 08:37:57RECEIVED SUBMITTAL REGARDING A/C SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By tgordon Date 2007-01-10 Time 09:06 Rev Time 0.30
Received By tgordon Date 2007-01-10 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By tgordon Date 2006-11-22 Time 11:49 Rev Time 0.30
Received By tgordon Date 2006-11-22 Time 11:49 Sent To  
Notes
2006-11-22 11:52:42*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #4 REGARDING ENERGY
 CAL'S. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 11:34 Rev Time 0.30
Received By tgordon Date 2006-09-11 Time 11:34 Sent To  
Notes
2006-09-11 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06082229 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By jleech Date 2007-01-10 Time 13:18 Rev Time 0.00
Received By jleech Date 2007-01-10 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-08 Cont ID  
Sent By jleech Date 2006-12-08 Time 07:45 Rev Time 0.00
Received By jleech Date 2006-12-08 Time 07:44 Sent To  
Notes
2006-12-08 08:40:37DENIED;
 1.A DRINKING FOUNTAIN IS REQUIRED NOT A WATER COOLER. A
 DRAIN IS REQUIRED, PLEASE SHOW ON SANITARY RISER
 DIAGRAM. SEE SECTION 410.1
 2. DRINKING FOUNTAIN TO MEET ACCESSIBILITY CODES
 SECTION 11-4.1.3(10)A HI-LOW FOUNTAIN OR ONE D/F SET
 AT HANDICAP HIGHT WITH A CUP DISPENSOR. SHOW A DETAIL
 OF DRINKING FOUNTAIN WITH ALL MEASURMENTS REQUIRED BY
 SECTIONS 11-4.15.1 THRU 11-4.15.5.
 PLUMBING PLAN REVIEW;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 17:27 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 17:27 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. PER TABLE 403.1 AND SECTION 410.1 A
 DRINKING FOUNTAIN IS REQUIRED. SHOW
 CONNECTION TO SANT. AND WATER RISER
 DIAGRAMS.
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES ETC. SECTIONS
 106.3.5.1.3 AND 606.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy