Plan Review Details - Permit 06082033
Plan Review Stops For Permit 06082033
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-31 Cont ID  
Sent By lursu Date 2006-08-31 Time 11:02 Rev Time 0.00
Received By lursu Date 2006-08-31 Time 11:02 Sent To  
Notes
2006-08-31 00:00:00OWNER INFO UPDATED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 11:35 Sent To M
Notes
2007-03-01 11:35:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-03 Cont ID  
Sent By adarroug Date 2006-10-03 Time 14:11 Rev Time 0.00
Received By adarroug Date 2006-10-03 Time 14:11 Sent To M
Notes
2006-10-03 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-01 Cont ID  
Sent By tgordon Date 2006-09-01 Time 13:57 Rev Time 0.00
Received By tgordon Date 2006-08-28 Time 11:37 Sent To  
Notes
2006-08-28 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-03-02 Cont ID  
Sent By tgordon Date 2007-03-02 Time 11:05 Rev Time 0.30
Received By tgordon Date 2007-03-02 Time 11:05 Sent To  
Notes
2007-03-02 11:33:41** MECHANICAL REVISION **
 *** DENIED ***
 1) PLANS STATE ON THEM FOR 1315 APT. 202 A/H LOCATED IN
 GARAGE, AND ALSO STATE A/H BELOW IN CARPORT, PLEASE
 CORRECT.
  
 2) PLANS SHOW NO GARAGE OR CARPORT ON THE FIRST FLOOR
 PLAN (APT. 101), PLEASE CORRECT.
  
 *** 2004 FBC 106.1.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR AHU
 #3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-10 Cont ID  
Sent By tgordon Date 2006-10-10 Time 11:25 Rev Time 0.30
Received By tgordon Date 2006-10-10 Time 11:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By tgordon Date 2006-09-01 Time 13:27 Rev Time 1.00
Received By tgordon Date 2006-09-01 Time 13:27 Sent To  
Notes
2006-09-01 00:00:00*** DENIED ***
 1) BUILDING 1315 APT.101 & 202 CAN BE ON
 THE SAME ENERGY CAL. BUT BUILDING 1309
 MUST HAVE ITS OWN ENERGY CAL; PER 2004
 FBC 13-101.2.5.1 .
  
 2) ENERGY CAL'S NEED TO BE SIGNED BY THE
 PREPARER NOT STAMPED AND ALSO SIGNED BY
 THE OWNER/AGENT, PER 2004 FBC
 13-600.ABC.1.1 .
  
 3) ALL INFORMATION, DRAWINGS, (PLANS),
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1 .
  
 5) PLANS REFER TO THE SAME APT. AS 201
 AND 202, PLEASE CORRECT.
  
 6) WHITE OUT MAY NOT BE USED ON PLANS.
  
 7) PLEASE SHOW AIR HANDLER UNIT CFM'S ON
 PLANS.
  
 8) A/C #3, PLEASE PROVIED RETURN AIR FOR
 BEDROOMS, PER 2004 FBC/R M1602.4 .
  
 9) A/C #3, IS 16" RETURN AIR DUCT GOING
 TO A SIDE WALL GRILL, PLEASE CLARIFY.
  
 10) PLEASE SHOW SIZES OF SUPPLY AIR
 TRUNK LINES FOR AHU #1 AND #3.
  
 11) DO BATHROOMS HAVE WINDOWS OR ARE
 EXHAUST FANS BEING INSTALLED, PLEASE
 CLARIFY.
  
 12) NEED TO FILE A NOTICE OF
 COMMENCEMENT FOR WALLEN SERVICE CORP. AS
 THE CONTRACTOR AS INSTALLING NEW A/C
 SYSTEMS WAS NOT PART OF THE GENERAL
 REPAIRS PERMIT, PER F. S. 713.13 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  