Plan Review Details - Permit 06082023
Plan Review Stops For Permit 06082023
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-31 Cont ID  
Sent By lursu Date 2006-08-31 Time 10:53 Rev Time 0.00
Received By lursu Date 2006-08-31 Time 10:53 Sent To  
Notes
2006-08-31 00:00:00ATTACH PERMIT TO EXT #0007 UNDER PCN =
 74 43 43 21 13 003 0010

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By jwitmer Date 2007-01-19 Time 14:29 Rev Time 2.22
Received By jwitmer Date 2007-01-19 Time 14:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-09 Cont ID  
Sent By jwitmer Date 2006-11-09 Time 10:46 Rev Time 3.77
Received By jwitmer Date 2006-11-09 Time 09:34 Sent To  
Notes
2006-11-09 11:29:46BUILDING PLAN REVIEW
 PERMIT: 06082023
 ADD: 550 S ROSEMARY# 164
 CONT:PLAN REVIEW
 NEYITA
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE IN THE MBH TRANSMITTALTHE COMMENT STATES
 THAT " IF IN CASE YOU NEED TO SWITCH OUT SHEETS WITH
 THE ORIGINAL DRAWINGS".
 AS STATED ABOVE WE ASK FOR OLD VOID SHEETS TO BE PULLED
 FROM THE PLANS, ONELY 1 SET OF OLD SHEETS ARE REQUIRED
 FOR COMPARISION THE REVISED PLANS, 2 SETS THEN BOUND.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 THIS STATEMENT WILL APPEARUNTIL THE PLAN
 REVIEW IS TURNED INTO A PERMIT AND CONTRACTOR
 IS ON BOARD WITH A RECORDED NOC.
  
 3) 2ND REQUEST, SHEET AT.1 PROJECT DATA
 MALL CONSTRUCTION TYPE: IS TYPE I (LIST AOR B)
 CONSTRUCTION, YOU CAN NOT
 BUILD TO A TYPE VI( NO LONGER IN EXISTANCE)
 CONSTRUCTION IN A TYPE I BUILDING.
  
 4) COMPLIED.
  
 5) D H ARCHITECTS IS MISSING THEIR FIRMS LICENSE
 NUMBER, THIS IS CALLED A CERTIFICATE OF AUTHORIZATION.
 ) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 6) COMPLIED.
  
 7) SAME COMMENT AS # 5.
  
 8)COMPLIED.
  
 9) COMPLIED.
  
 10)2ND REQUEST SHEET A1.1 DEALS WITH THE NEW WOMENS
 RESTROOM,
 THE ENTRY DOOR IS MISSING THE REQUIRED 18" CLEAR FLOOR
  
 SPACE AT THE LATCH PULLSIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 10A) SHEET A1.1 INDICATES A RESTROOM DETAIL
 2 SHEET A3.3 NO SUCH IS IN THE PLANS.
  
 11A) 2ND REQUEST,SHEET A1.1 INDICATES A HANDICAPPED
 DRESSING ROOM, IT APPEARS THE 60"
 TURNING CIRCLE ENCROACHES INTO THE NEXT
 ROOM.11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON
 USING A WHEELCHAIR TO MAKE A 180-DEGREE
 TURN SHALL BE PROVIDED IN EVERY
 ACCESSIBLE DRESSING ROOM ENTERED THROUGH
 A SWINGING OR SLIDING DOOR. NO DOOR
 SHALL SWING INTO ANY PART OF THE TURNING
 SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM
 ENTERED THROUGH A CURTAINED OPENING AT
 LEAST 32 INCHES (815 MM) WIDE IF CLEAR
 FLOOR SPACE COMPLYING WITH SECTION
 11-4.2 RENDERS THE DRESSING ROOM USABLE
 BY A PERSON USING A WHEELCHAIR.
  
 THE MBH RESPONCE THAT THE ACCORDIAN DOOR
 WILL BE LOCKED IN THE "OPEN" POSITION AND WHEN
 NOT IN USE THE ACCORDIAN DOOR WILL BE CLOSED
 CREATING (2) DRESSING ROOMS.
  
 THE WHOLE IDEA BEHIND CHAPTER 11 THE ACCESSIBILTY CODE
 IS FOR
 PEOPLE WITH PHYSICAL DISSABILITIES WILL HAVE "
 EQUIVALENT FACILITATION" 11-2.2
 THAT IS REST ROOMS DRESSING ROOMS ARE ALREADY BUILT
 FOR THIER USE,AS IS THE ELEMENT IS IN ACCORDANCE
 WITH THE MINIMUM ACCESSIBILY REQUIREMENTS OF THE ADA.
  
 11B) COMPLIED.
  
 11C) COMPLIED.
  
 11D) 2ND REQUEST, DESCEPANCY,THE FLOOR PLAN INDICATES
  
 THAT DOOR# 3 IS TO BE A POCKET DOOR.
 SHEET A3.2 THE ELEVATIONS INDICATES IT TO BE A
 POCKET DOOR, SHEET A5.1 DETAIL# 10 INDICATES THE USE OF
 HINGES?
  
 12 ) 2ND REQUEST,PRODUCT APPROVALS SUBMITTED
 WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR GLAGED DOORS
 SUBMITTED KAWNEER DOORS PROBLEMS WITH SUBMITTALS 2001
 FLORIDA COVER SHEET, NOT 2004,
 SUBMITTED ARE TWO TYPES OF MIAMI-DADE NOA. HIGHLIGHT
 TYPE OF GLASS, MULLIONS IF MORE THAN ONE TYPE SYSTEM IS
 AVAILABLE.
 B) WINDOWSSTOREFRONT,
 KAWNEER PROBLEM WITH THE SUBMITTALS, 2001 FLORIDA
 COVERSHEET, NOT 2004.
 SUBMITTED ARE 2 TYPES OF MIAMI-DADE NOA. HIGHLIGHT
 SYSTEM, TYPE OF GLASS AND MULLIONS.
  
 13)2ND REQUEST, )W P B ADMINISTRTIVE CODE
 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 12:30 Rev Time 2.22
Received By jwitmer Date 2006-09-15 Time 12:30 Sent To PC
Notes
2006-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06082023
 ADD: 550 S ROSEMARY# 164
 CONT:PLAN REVIEW
 NEYITA
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET AT.1 PROJECT DATA
 MALL CONSTRUCTION TYPE:I (LIST AOR B)
  
 4) SAME SHEET INDICATES PALM BEACH
 COUNTY AMENDMENTS, CORRECT TO CITY OF
 WEST PALM BEACH CHAPTER 1
 ADMINISTRATIVE CODE.
  
 5) SAME SHEET PROJECT DICTIONARY,
 ARCHITECT OF RECORD IN THIS COLUMN
 DOESN'T MATCH THE FIRM IN THE HEADER
 STRIP.
  
 6) SAAME SHEET PROJECT DICTIONARY,
 ENGINEER FOR THE MEP DOESN'T MATCH THE
 ENGINEERS HEADER STRIP.
  
 7) THE ARCHITECTURAL FIRM IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. 481.219 F.S.CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
  
 8) THE ENGINEERING FIRM MBH IS MISSING
 THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER.471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.
  
 9) NOTE ON ALL NEW SHEETS BEING
 SUBMITTED TOTHE CITY WILL HAVE TO HAVE
 THE CITY PLACE APPROVAL STAMP BEFORE
 SUBMISSION.
  
 10) SHEET A1.1 INDICATES A NEW WOMENS
 RESTROOM, THE OUT SWING DOOR IS MISSING
 18" CLEARENCE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 11A) SHEET A1.1 INDICATES A HANDICAPPED
 DRESSING ROOM, IT APPEARS THE 60"
 TURNING CIRCLE IENCROACHES INTO THE NEXT
 ROOM.11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON
 USING A WHEELCHAIR TO MAKE A 180-DEGREE
 TURN SHALL BE PROVIDED IN EVERY
 ACCESSIBLE DRESSING ROOM ENTERED THROUGH
 A SWINGING OR SLIDING DOOR. NO DOOR
 SHALL SWING INTO ANY PART OF THE TURNING
 SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM
 ENTERED THROUGH A CURTAINED OPENING AT
 LEAST 32 INCHES (815 MM) WIDE IF CLEAR
 FLOOR SPACE COMPLYING WITH SECTION
 11-4.2 RENDERS THE DRESSING ROOM USABLE
 BY A PERSON USING A WHEELCHAIR.
  
 11B) THIS SAME AREA ALSO IS MISSING A
 BENCH TYPE SEAT. EVERY ACCESSIBLE
 DRESSING ROOM SHALL HAVE A 24 INCH BY 48
 INCH (610 MM BY 1219 MM) BENCH FIXED TO
 THE WALL ALONG THE LONGER DIMENSION. THE
 BENCH SHALL BE MOUNTED 17 INCHES TO 19
 INCHES (430 MM TO 485 MM) ABOVE THE
 FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE
 PROVIDED ALONGSIDE THE BENCH TO ALLOW A
 PERSON USING A WHEELCHAIR TO MAKE A
 PARALLEL TRANSFER ONTO THE BENCH. THE
 STRUCTURAL STRENGTH OF THE BENCH AND
 ATTACHMENTS SHALL COMPLY WITH SECTION
 11-4.26.3 .
  
 11C) 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING
 ROOMS OF THE SAME USE, THEN IN AN
 ACCESSIBLE DRESSING ROOM , A FULL-LENGTH
 MIRROR, MEASURING AT LEAST 18 INCHES
 WIDE BY 54 INCHES HIGH (460 MM BY 1370
 MM), SHALL BE MOUNTED IN A POSITION
 AFFORDING A VIEW TO A PERSON ON THE
 BENCH AS WELL AS TO A PERSON IN A
 STANDING POSITION.
  
 11D) SHEET A0.1 DOOR SCHEDULE DOOR TYPE
 "D" IS A POCKET DOOR BUT UNDER THE
 HEIGTH COLUMN THE DOOR IS 5'-0" HIGH?
  
 12) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR GLAZED DOORS
 B) STOREFRONT WINDOWS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-31 Cont ID  
Sent By dpalmer Date 2007-01-31 Time 18:08 Rev Time 0.00
Received By dpalmer Date 2007-01-31 Time 17:37 Sent To  
Notes
2007-01-31 18:08:29ELECTRICAL SHEETS AND FP SHEETS FOR FIRE ALARM DEVICES
 AND ENERGY CALCULATIONS ONLY REVIEWED FOR CODE
 COMPLIANCE.
  
 E-SHEETS STAMPED AND SIGNED.
 FP SHEETS FOR FA DEVICES STAMPED
 ENERGY CALCULATIONS STAMPED AND INITIALED FOR
 ELECTRICAL REVIEW ONLY.
  
 ***NO OTHER SHEETS FROM OTHER TRADES WERE REVIEWED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-19 Cont ID  
Sent By dpalmer Date 2007-01-19 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 16:14 Sent To  
Notes
2007-01-19 20:23:102007-01-19 20:23:10
  
 ** UNSAT 3RD REVIEW**
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
 THE TWO PREVIOUS REVIEWS WERE SUBMITTED UNDER *PLAN
 REVIEW*ONLY.
  
  
 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 THE ENERGY CALCULATIONS MEET THE 2004 FBC 13-415.2 AND
 13-415.1.AB.1.1 AND TO CORRELATE WITH THE SUBMITTED
 ELECTRICAL PLANS.
 PLEASE KNOW THAT A MEETING WAS HELD ON JANUARY 10TH,
 2007 WHICH THE ENERGY CALCULATIONS WERE GONE OVER ALONG
 WITH THE PLANS. THESE WERE TO BE SUBMITTED FOR PERMIT
 APPLICATION THE SAME DAY. UPON REVIEW OF CALCULATIONS,
 THIS REVIEWER COMMENTED ON THE FACT THAT THE ENERGY
 CALCULATIONS IN THE INPUT DATA SECTION WAS STILL
 INDICATING *MANUAL ON/OFF* AND NEEDED TO CORRELATE WITH
 PLANS FOR *AUTOMATED* CONTROLS.
 PLEASE SEE THIS WAS NOT DONE.
 THERE WERE ALSO COMMENTS ON THE MISSING OVER RIDE TIMES
 ON THE T-OVER-RIDE DEVICES AND MOTION/OCCUPANCY SENSORS
 WHICH DID NOT INDICATE THE MAXIMUM TIMES AS REQUIRED
 AND PERMITTED BY THE CODE WHICH WAS IN THE TWO PREVIOUS
 REVIEW COMMENTS.
 IT WAS THE SUGGESTION OF THIS REVIEWER THAT THESE ITEMS
 MAY BE CORRECTED AND NEW SHEETS AND CALCULATIONS MAY BE
 SUBMITTED PRIOR TO THE ELECTRICAL REVIEW COMMENCING AS
 A BENEFIT AND TO ALLEVIATE ANY FURTHER DENIALS AND
 DELAYS IN THE PERMITTING.PLEASE KNOW THAT NEW
 ELECTRICAL SHEETS, A NEW STRUCTURAL SHEET AND ENERGY
 CALCULATIONS WERE BROUGHT INTO OUR OFFICE BY THE PERMIT
 EXPEDITOR AND WERE ALLOWED TO BE INSERTED INTO THE
 SETS.THIS REVIEWER HAD NOTICED THE ENERGY
 CALCULATIONS WERE SIGNED, AND CONTAINED A *RUBBER
 STAMP* FOR SEAL; HOWEVER THE REQUIRED RAISED EMBOSSED
 TYPE SEAL AS REQUIRED UNDER THE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.001 WAS NOT VISIBLE WITH ANY INFORMATION
 ON SAID SEAL. IT WAS NOTED AND SUGGESED BY THIS
 REVIEWER ONCE AGAIN IN THE INTEREST OF NOT DELAYING THE
 PROJECT TO HAVE NEW SIGNED, DATED AND SEALED ENERGY
 CALCULATIONS BE SENT OVER NIGHT MAIL AND BROUGHT IN
 BEFORE REVIEW COMMENCED. THE NEW CALCULATIONS WERE
 SUBMITTED AND PLACED WITH PACKAGE FOR REVIEW. PLEASE
 SEE UPON REVIEW OF THE ENERGY CALCULATIONS, THE INPUT
 DATA STILL INDICATES * MANUAL ON/OFF* WHEN IN FACT
 THESE ARE OF AN *AUTOMATED* CONTROL. PLEASE SEE THAT
 THE FLA-COM DOES HAVE THE OPTION TO INSERT THE CORRECT
 INFORMATION FOR THIS AREA.
  
 ** PLEASE ALSO KNOW THAT UPON REVIEW OF SAID ENERGY
 CALCULATIONS, THESE ARE DATED NOVEMBER 27, 2006. IT IS
 UNCLEAR HOW THIS IS POSSIBLE WHEN THE MEETING TO GO
 OVER THESE CALCULATIONS AND PLANS DID NOT TAKE PLACE
 UNTIL JAN OF 07?
 A TECHNICAL REVIEW OF DOCUMENTS WAS NOT PERFORMED WHEN
 THESE TWO SUBMITTALS WERE BROUGHT IN BEFORE THIS
 REVIEW.
  
 2) NOTE: PLEASE SEE THE REVISED ELECTRICAL SHEETS WHICH
 WERE INSERTED INTO THE SETS. PLEASE SEE THE REQUIRED
 RAISED, EMBOSSED SEAL IS ILLEGIBLE AND NO INFORMATION
 ON SAID SEAL CAN BE MADE OUT EVEN BY USING A
 SHADOWING/DUSTING METHOD. THE RUBBER STAMPED SEAL IS
 NOT ACCEPTED IN THE STATE OF FLORIDA. FAC
 61G15-23.001.
  
 ** PLEASE ALSO SEE THESE SHEETS ARE ALSO DATED NOVEMBER
 27TH, 2006 WHICH IS NOT POSSIBLE ONCE AGAIN. PLEASE SEE
 THE REVISION DATES IN THE TITLE BLOCKS ALSO INDICATE
 11/27/06 WHICH IS NOT POSSIBLE WHEN THESE ARE RESPONSE
 TO COMMENTS FROM MEETING DATED 1/10/07 PLEASE SEE A
 RESPONSE LETTER FROM THE DESIGNER'S OFFICE DATED
 JANUARY 15TH, 2007 MENTIONS SOME RESPONSE(S) WHICH WERE
 NOT PART OF MY COMMENTS IN THE MEETING DATED JANUARY
 10TH, 2007. ( RESPONSE #4)
 PLEASE BE SURE ALL SHEETS ARE SIGNED, DATED AND SEALED
 CORRECTLY AND THE TITLE BLOCKS REFLECT THE CORRECT
 DATES WHEN PLANS WERE REVISED.
 FAC 61G15-23.002, FS 471.025
 FBC ADMIN SECTION 106.1
  
 3) NOTE: PLEASE ALSO SEE THAT AS OF THE MEETING DATED
 JANUARY 10TH, 2007 THE PREVIOUSLY REQUESTED DETAIL FOR
 TRANSFORMER MOUNTING WAS ALSO NOT SUBMITTED. IT WAS
 ONCE AGAIN STATED THAT THIS INFORMATION MAY BE BROUGHT
 IN WHEN INSERTING THE NEW REVISED ELECTRICAL SHEETS
 BEFORE THE ELECTRICAL REVIEW WAS TO COMMENCE. PLEASE
 SEE THE STRUCTURAL 8 1/2 X 11'S AND THE NEW *S* SHEETS
 IN SETS ARE MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING FIRM ON THE
 TITLE BLOCKS. PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 THIS IS REQUIRED WHETHER OR NOT SHEETS WERE STAMPED FOR
 REVIEW OF CODE COMPLIANCE BY ANY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE UPON REVIEW OF THE NEW FP SHEETS IN
 THE MEETING DATED JANUARY 10TH, 2007 IT WAS NOTED BY
 THIS REVIEWER THAT THE STROBE/HORN LEVELS DID NOT
 INDICATE THE REQUIRED MINIMUM LEVELS AS REQUIRED BY THE
 FBC 11-4.28.1,.2, .3(4). THIS WAS NEVER A COMMENT BY
 THIS REVIEWER AS THE RESPONSIBILITY OF THIS REVIEW WAS
 ONLY RECENTLY BEING HANDLED BY THE ELECTRICAL REVIEW.
 THE COMMENT WAS MADE IN THE MEETING THAT THE LEVELS
 WOULD BE REDLINED; HOWEVER AS THE PLANS ARE BEING
 DENIED AND GOING OUT FOR CORRECTIONS, PLEASE CORRECT
 AND REVISE THESE SHEETS AT THIS TIME WITH THE CORRECT
 MINIMUM LEVELS.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE KNOW AS THIS PROJECT DID NOT APPLY FOR
 PERMIT UNTIL AFTER DECEMBER 7TH, 2006,ON DECEMBER
 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE 2005
 NFPA-70. PLEASE ADJUST PLANS. THIS WAS GOING TO BE
 REDLINED AS STATED IN THE MEETING ON JAN 10TH, HOWEVER
 SINCE PLANS ARE COMING BACK PLEASE REVISE AT THIS TIME.
 THIS INCLUDES THE SHEET AT.1 WHICH CAN BE REDLINED.
 PLEASE ALSO SEE THAT THE 2006 REVISIONS TO THE 2004 FBC
 ALSO WENT INTO EFFECT ON THE SAME DATE. PLEASE CONFIRM
 CODE COMPLIANCE WITH CHAPTER 13, AS THERE WERE CHANGES,
 AND VERIFY ANY CHANGES WITH THE BUILDING CODE AND OTHER
 TRADES FOR POSSIBLE CHANGES.
 THIS IS REQUIRED WHETHER OR NOT COMMENTS ARE MADE BY
 OTHER TRADES.
 IF NO TECHNICAL CHANGES TO PLANS ARE REQUIRED, THEN THE
 CODE FOR THE 2006 REVISIONS TO THE 2004 FBC CAN ALSO BE
 HAND REDLINED ON AT.1
  
 6) NOTE: PLEASE SEE THAT THE SUBMITTED PLANS FOR THE
 FIRE SPRINKLER PLANS SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AND
 WORK FOR THIS SCOPE.
 FBC 106.1.2, 106.3.5.1.2, 106.1.1.1
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT WAS MADE BY
 THE FIRE MARSHAL'S OFFICE.
  
 7) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SHALL
 CONTAIN THE PRINTED NAME OF THE ARCHITECT. THIS CAN BE
 HAND PRINTED ON THE TITLE BLOCKS. THIS IS REQUIRED PER
 FAC 61G1-16.004.
 THIS IS REQUIRED EVEN IF ARCHITECTURAL PLANS HAVE BEEN
 STAMPED AS CODE COMPLIANT.
 THIS WAS IN THE ELECTRICAL REVIEW COMMENTS ON PREVIOUS
 REVIEWS. THIS IS REQUIRED.
  
 8) NOTE: ** PLEASE KNOW AS THE PLANS WERE SUBMITTED FOR
 * PLAN REVIEW* AND NOT FOR PERMIT THE 4X TIMES THE FEE
 FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE
 REPEAT CODE COMPLIANT COMMENTS HAS NOT BEEN ASSESSED AS
 REQUIRED PER FLORIDA STATUTES 553.80(2)(B). THIS IS
 ASSESSED WHEN PLANS HAVE BEEN SUBMITTED LEGALLY FOR
 PERMITTING.
 PLEASE KNOW HOWEVER THAT ONE SET OF EACH SET OF
 ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
  
  
 **** PLEASE KNOW AS THIS REVIEWER WILL BE THE LICENSED
 REVIEWER TO ISSUE SAID PROJECT, IT IS THE
 RESPONSIBILITY OF THIS REVIEWER THAT COMPLIANCE FOR
 ISSUANCE OF PERMIT IS MET FOR ALL ASPECTS OF THE
 FLORIDA ADMINISTRATIVE CODE, FLORIDA STATUTES AND OTHER
 PERTINENT LAWS AND ORDINANCES.
 PLEASE ADDRESS THE ABOVE COMMENTS.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-19 17:58:042007-01-19 17:58:04
 NEW SHEETS AND ENERGY CALCULATIONS SUBMITTED 1/16. ALSO
 NEW ENERGY CALCULATIONS SUBMITTED AS A SUBMITTAL ON
 1/19.
 REVIEW IN PROGRESS.
2007-01-14 16:16:102007-01019 16:16:10
 ELECTRICAL REVIEW ON HOLD, WAITING FOR NEW SHEETS ALONG
 WITH NEW ENERGY CALCULATIONS BEFORE REVIEW STARTS. THIS
 IS AT THE REQUEST OF THE OWNER'S AND ARCHITECT. OTHER
 TRADES MAY REVIEW WHEN AVAILABLE.
 TO BE SUBMITTED ON 1/16

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By dpalmer Date 2006-10-30 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 09:57 Sent To I
Notes
2006-10-30 18:26:06*** UNSAT 2ND REVIEW ***
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE FIRM NAME HAS BEEN
 CORRECTED ON ALL SHEETS HOWEVER THE FIRM LICENSE NUMBER
 AS REQUIRED ON PREVIOUS NOTES IS STILL NOT ON TITLE
 BLOCKS AS REQUIRED.
  
  
 ** PREVIOUS REVIEWNOTE **
 PLEASE CLARIFY TITLE BLOCKS FOR
 THE ARHCITECTURAL FIRM. PLEASE SEE COVER
 SHEET SHOWS "MBH " ARCHITECTS AND "A"
 SHEETS INDICATE "DH" ARCHITECTS??
 PLEASE SEE MEP SHEETS DO INDICATE
 "MDH"???
 PLEASE KNOW IN EITHER CASE, PLEASE SEE
 MISSING REQUIRED LICENSE NUMBERS FOR
 FIRM(S). PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004ANF
 FLORIDA STATUS 481.219 FOR ARCHITECTURAL
 FIRMS REQUIRING A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE ALSO SEE THE TITLE BLOCKS MISSING
 THE REQUIRED PRINTED NAME AND LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
 ** THIS IS REQUIRED ON ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE:NO, PLEASE SEE NUMEROUS SHEETS WHICH WERE NOT
 DATED BY THE ARCHITECT.
 PLEASE KNOW THIS IS REQUIRED WHICH LENDS TO THE
 AUTHENTICITY OF THE PLANS WHICH ARE BEING SIGNED AND
 SEALED.
 PLEASE ALSO BE SURE ALL SEALS ARE "RAISED" SO THAT ALL
 INFORMATION ON SAID SEAL IS CLEAR AND VISABLE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCHITECT TO DATE SAID
 PLANS WHEN SIGNING AND SEALING
 DOCUMENTS.
  
 5) NOTE: OK.
  
 6) NOTE:NO, PLEASE SEE SEPERATE SPACES.
 PLEASE SEE LIGHTING ALLOWED AND DEISGNED, SHOWN,
 HOWEVER WHERE ARE THESE FIGURES FROM AND WHAT ARE THEY?
 " X" PER SQ FT, PER RETAIL , STOCK AREA ETC.
 PLEASE SEE MISSING CONTROLS AT LOCATION OF INGRESS INTO
 SPACE.
  
 ** PREVIUOUS REVIEW NOTE **
 PLEASE SEE LIGHTING CONTROL
 CONTACTORS ARE BEING SHOWN , HOWEVER
 COULD NOT LOCATE THE AUTOMATIC SHUT OFF
 FOR LIGHTING CONTROLS AS REQUIRED UNDER
 FBC 2004 CHAPTER 13.
 PLEASE SEE MISSING THE SCHEDULING,
 OVER-RIDE DEVICES.
 PLEASE SEE SEPARATE SPACES WITH FLR TO
 CEILING HEIGHT PARTITIONS WHICH REQUIRE
 OVER RIDES OF THE NORMAL LC SYSTEM.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS
 AS SETFORTH IN
 13-415.2.ABC.1 AND TABLE 415.2.B.1,
 415.2.C.1
 ** PLEASE KNOW OVER-RIDES SHALL BE
 LOCATED SO THE OCCUPANT CAN SEE LIGTHING
 BEING CONTROLLED FOR MAIN SYSTEM.
 PLEASE SPECIFY THE OVER-RIDE DEVICES, IF
 TIMER TYPE (4HRS MAX) , IF OCCUPANT
 SENSOR TYPE (30MINS MAX).
 ** PLEASE KNOW, ANY LIGHTING BEING LEFT
 IN THE "ON" POSITION INTENDED AS NIGHT
 LTS SHOULD BE KEPT TO A MINIMUM. PLEASE
 SEE THE STORE FRONT WOULD BE ACCEPTABLE
 , HOWEVER ALL OTHER TRACK LIGHTING
 SHOULD BE SHUT OFF WITH THE AUTOMATED
 LIGHTING
 CONTROLS. PLEASE SEE THAT THIS NUMBER OF
 FIXTURES CAN BE GONE OVER. THE AMOUNT OF
 FIXTURES SHOWN EXCEEDS THAT REQUIRED BY
 THE FEC FOR THIS AHJ'S INTERPRETATION.
  
 7) NOTE: NO? , SAME NOTE AS ONLY MENTIONED BY THE
 ELECTRICLA REVIEWER.
 IF THIS IS A CODE VIOLATION, PLANS WILL BE REQUIRED TO
 BE MODIFIED.
  
 ** PREVIOUS REVIEW NOTE** PLEASE SEE POSSIBLE NOTES
 FROM BUILDING/PLUMBING REVIEW AS THE ACCESS
 TO THE HC BATHS SEEMS TO BE LOCATED
 THROUGH THE "STOCKROOM". THIS IS NOT AN
 ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR
 AND UNOBSTRUCTED PATH MAY NOT EXIST FOR
 FIRE EGRESS ETC.??
 THIS IS ONLY NOTED.
  
 8) NOTE: OK.
  
 9) NOTE:OK/NO., PLEASE SEE UNIT IS NOW BEING SHOWN
 BELOW CEILING, HOWEVER NO DETAIL FOR STRUCTURAL REVIEW
 WAS SUBMITTED AND IS NOTED TO BE DONE AT A LATER DATE.
 PLEASE KNOW THIS IS REQUIRED AT THIS TIME AS IF THE
 LCOATION AS SHOWN IS NOT SUFFICIENT OR AFFECT THE
 STRUCTURAL INTEGRITY OF THE EXISTIGN STRUCTURE, THE
 LOCATION MAY NEED TO BE CHANGED THEREFORE, REVISON OF
 ELECTRICLA AND POSSIBLE ITEMS PER
 450.9,450.13,110.26,240.21 MAY NEED TO BE REVIEWED.
 ** PLEASE SUBMIT AT THSI TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE TRANSFORMER IS
 BEING SHOWN ON THE RISER LOCATED ABOVE
 THE CEILING WHICH IS NOT PERMITTED PER
 450.13B.
 PLEASE PROVIDE AN ALTERNATE LOCATION.
 PLEASE SEE 450.9, 450.21A
 ** PLEASE ALSO SUBMIT A STRUCTURAL
 ENGINEERING DETAIL FOR THE SUPPORT AND
 MOUNTING OF UNIT.
 FBC 106.1.2
  
 10) NOTE: OK.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-30 09:58:23REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 19:45 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 18:33 Sent To  
Notes
2006-09-10 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE CORRECT ADDRESS AND SUITE/UNIT
 NUMBER ON ALL SHEETS IN CADD/PROGRAM.
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES
 ARE REQUIRED AT A MINIMUM.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003
 NFPA-101.
 THESE SHOULDS ALSO BE LOCATED IN NOTE ON ELECTRICAL
 PLANS 16A.
  
 2) NOTE: PLEASE BE SURE WHEN SUBMITTING
 PLANS TO ATTACH ALL SHEETS TOGETHER INTO
 TWO COMPLETE SETS. PLEASE SEE THAT PLANS
 WERE SUBMITTED AS LOOSE SHEETS AND WERE
 ATTACHED INTO SETS BY THIS OFFICE THIS
 TIME AS A COURTESY.
 FBC 106.1 ADMIN SECT.
  
 3) NOTE: PLEASE CLARIFY TITLE BLOCKS FOR
 THE ARHCITECTURAL FIRM. PLEASE SEE COVER
 SHEET SHOWS "MBH " ARCHITECTS AND "A"
 SHEETS INDICATE "DH" ARCHITECTS??
 PLEASE SEE MEP SHEETS DO INDICATE
 "MDH"???
 PLEASE KNOW IN EITHER CASE, PLEASE SEE
 MISSING REQUIRED LICENSE NUMBERS FOR
 FIRM(S). PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004ANF
 FLORIDA STATUS 481.219 FOR ARCHITECTURAL
 FIRMS REQUIRING A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE ALSO SEE THE TITLE BLOCKS MISSING
 THE REQUIRED PRINTED NAME AND LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
 ** THIS IS REQUIRED ON ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCHITECT TO DATE SAID
 PLANS WHEN SIGNING AND SEALING
 DOCUMENTS.
  
 5) NOTE: PLEASE CLARIFY ENGINEERING
 TITLE BLOCKS AND RESPONSIBLE PARTIES.
 PLEASE SEE COVERSHEET LIST "HBK
 ENGINEERING", YET MEP'S DO NOT CONTAIN
 THE SAME TITLE BLOCK??
 PLEASE ALSO SEE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SAID
 ENGINEERING FIRM.
 FAC 61G15-23.002, FS 471.023
  
 6) NOTE: PLEASE SEE LIGHTING CONTROL
 CONTACTORS ARE BEING SHOWN , HOWEVER
 COULD NOT LOCATE THE AUTOMATIC SHUT OFF
 FOR LIGHTING CONTROLS AS REQUIRED UNDER
 FBC 2004 CHAPTER 13.
 PLEASE SEE MISSING THE SCHEDULING,
 OVER-RIDE DEVICES.
 PLEASE SEE SEPARATE SPACES WITH FLR TO
 CEILING HEIGHT PARTITIONS WHICH REQUIRE
 OVER RIDES OF THE NORMAL LC SYSTEM.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS
 AS SETFORTH IN
 13-415.2.ABC.1 AND TABLE 415.2.B.1,
 415.2.C.1
 ** PLEASE KNOW OVER-RIDES SHALL BE
 LOCATED SO THE OCCUPANT CAN SEE LIGTHING
 BEING CONTROLLED FOR MAIN SYSTEM.
 PLEASE SPECIFY THE OVER-RIDE DEVICES, IF
 TIMER TYPE (4HRS MAX) , IF OCCUPANT
 SENSOR TYPE (30MINS MAX).
 ** PLEASE KNOW, ANY LIGHTING BEING LEFT
 IN THE "ON" POSITION INTENDED AS NIGHT
 LTS SHOULD BE KEPT TO A MINIMUM. PLEASE
 SEE THE STORE FRONT WOULD BE ACCEPTABLE
 , HOWEVER ALL OTHER TRACK LIGHTING
 SHOULD BE SHUT OFF WITH THE AUTOMATED
 LIGHTING
 CONTROLS. PLEASE SEE THAT THIS NUMBER OF
 FIXTURES CAN BE GONE OVER. THE AMOUNT OF
 FIXTURES SHOWN EXCEEDS THAT REQUIRED BY
 THE FEC FOR THIS AHJ'S INTERPRETATION.
  
 7) NOTE: PLEASE SEE POSSIBLE NOTES FROM
 BUILDING/PLUMBING REVIEW AS THE ACCESS
 TO THE HC BATHS SEEMS TO BE LOCATED
 THROUGH THE "STOCKROOM". THIS IS NOT AN
 ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR
 AND UNOBSTRUCTED PATH MAY NOT EXIST FOR
 FIRE EGRESS ETC.??
 THIS IS ONLY NOTED.
  
 8) NOTE: PLEASE SEE A SYMBOL IS BEING
 SHOWN ON THE LIGHTING PLAN E2.00,
 HOWEVER THIS SYMBOL COULD NOT BE LOCATED
 ON THE PLANS/SCHEDULE/SYMBOL LIST.
 THIS HAS BEEN REDLINED ON PLANS ON ONE
 SET TO CLARIFY??
 106.1.2 FBC ADMIN SECT.
  
 9) NOTE: PLEASE SEE THE TRANSFORMER IS
 BEING SHOWN ON THE RISER LOCATED ABOVE
 THE CEILING WHICH IS NOT PERMITTED PER
 450.13B.
 PLEASE PROVIDE AN ALTERNATE LOCATION.
 PLEASE SEE 450.9, 450.21A
 ** PLEASE ALSO SUBMIT A STRUCTURAL
 ENGINEERING DETAIL FOR THE SUPPORT AND
 MOUNTING OF UNIT.
 FBC 106.1.2
  
 10) NOTE: PLEASE KNOW, ANY LOCK-OFF
 DEVICE BEING PROPOSED FOR CIRCUITS,
 SHALL BE AN INTEGRAL PART OF THE BREAKER
 WHERE REQUIRED BY CODE. PLEASE KNOW THE
 DEVICE TYPE CAN NOT JUST SIMPLY FALL OFF
 UPON THE REMOVAL OF THE PANEL COVERS, OR
 SNAP ON TO THE BRKR.
 ** WHERE REQUIRED BY CODE FOR CIRCUITS,
 OPTIONAL CIRCUITS DO NOT APPLY.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-17 Cont ID  
Sent By mawillia Date 2007-01-17 Time 18:10 Rev Time 0.00
Received By mawillia Date 2007-01-17 Time 18:10 Sent To  
Notes
2007-01-17 18:13:36*****APPROVED*****
  
  
  
 PLAN SHEETS A3.1, E2.00, FP-1 (FIRE SPRINKLER), AND
 FP-1 (FIRE ALARM) WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By mawillia Date 2006-11-02 Time 12:41 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 12:41 Sent To  
Notes
2006-11-02 12:50:55****DENIED****
  
  
  
 PREVIOUS FIRE PLAN REVIEW COMMENTS STILL HAVE NOT BEEN
 ADDRESSED.TO EXPEDITE PLAN REVIEW PROCESS, THE
 RESPONSE LETTER SHOULD INDICATE WHERE AND/OR HOW EACH
 ITEM WAS ADDRESSED WHEN RESUBMITTING.
  
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By mawillia Date 2006-09-12 Time 16:18 Rev Time 0.00
Received By mawillia Date 2006-09-12 Time 16:18 Sent To  
Notes
2006-09-12 00:00:00*****UNSAT*****
  
  
  
  
  
 1.) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2.) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS. CLASS A OR B IS
 REQUIRED IN MEANS OF EGRESS AREAS.
  
 3.) PROVIDE SHOP DRAWING(S)/PLAN(S)
 INDICATING LIFE SAFETY FEATURES OF THE
 EXISTING AS WELL THE PROPOSED STRUCTURE.
  
 4.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE SPRINKLER OR FIRE ALARM SYSTEM,
 PROVIDE SEPARATE PERMIT AND SHOP
 DRAWINGS/PLANS.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-21 Cont ID  
Sent By adarroug Date 2007-03-21 Time 15:50 Rev Time 0.00
Received By adarroug Date 2007-03-21 Time 15:50 Sent To B
Notes
2007-03-21 15:50:39TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 16:56 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 16:56 Sent To  
Notes
2007-01-31 16:58:38TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-08 Cont ID  
Sent By adarroug Date 2007-01-08 Time 16:56 Rev Time 0.00
Received By adarroug Date 2007-01-08 Time 16:56 Sent To  
Notes
2007-01-11 11:58:15TO "BOB"#17
2007-01-08 16:56:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 08:44 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 08:44 Sent To  
Notes
2006-11-01 10:27:31TO "BOB"#12
2006-10-27 08:45:04WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2006-08-28 Time 10:12 Sent To  
Notes
2006-09-08 00:00:00TO "BOB"#7
2006-08-28 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-06 Cont ID  
Sent By tgordon Date 2007-02-06 Time 08:52 Rev Time 0.30
Received By tgordon Date 2007-02-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 15:29 Rev Time 0.30
Received By tgordon Date 2007-01-12 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 14:31 Rev Time 0.30
Received By tgordon Date 2006-11-01 Time 14:31 Sent To  
Notes
2006-11-01 14:35:34* FOR PLAN REVIEW ONLY NOT FOR PERMIT*
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 3 AND 4, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 12:16 Rev Time 0.30
Received By tgordon Date 2006-09-11 Time 12:16 Sent To  
Notes
2006-09-11 00:00:00FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
 1) PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS, PER 2004 FBC/M 403.2 .
  
 2) SEE ELECTRICAL REVIEW NOTES REGARDING
 TITLE BLOCK INFORMATION, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 07:03 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 07:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 08:30 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-09 Cont ID  
Sent By jleech Date 2006-11-09 Time 07:44 Rev Time 0.00
Received By jleech Date 2006-11-09 Time 07:44 Sent To  
Notes
2006-11-09 07:47:42ARCHITECTS LICENSE NUMBER TO BE ON TITLE BLOCK.
 PLUMBING PLAN REVIEW OK.
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By jleech Date 2006-09-09 Time 10:03 Rev Time 0.00
Received By jleech Date 2006-09-09 Time 10:03 Sent To  
Notes
2006-09-09 00:00:00DENIED;
 1. ADD NOTE TO PAGE A0.2; ALL PLUMBING
 PIPES NOT BEING RE-USED MUST BE REMOVED,
 AND A DEMO PLUMBING INSPECTION IS
 REQUIRED.SEE FBC-2004 PLUMBING, SECTION
 704.5 NO DEAD ENDS.
 2.NO PLUMBING PAGES FOUND WITH THIS SET
 OF PLANS. PLEASE PROVIDE WATER AND
 SANITARY RISER DIAGRAMS SIZE ALL PIPE
 SHOW LOCATION OF SHUTOFF VALVES AND
 LOCATION OF WATER HAMMER ARRESTORS TO BE
 INSTALLED. ALSO LOCATION OF WATER HEATER
 LISTED ON ELECTRICAL DRAWINGS.
 3.MENS HANDICAP BATHROOM DOOR TO BE
 DIAGONAL OF THE TOILET, SEE FBC-2004
 BUILDING CHAPTER 11 FIG. 30E NOTES.
 4. SHOW A DETAIL OF THE DRINKING
 FOUNTAIN ON PAGE A3.3 WITH HANDICAP
 REQUIREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695