Plan Review Details - Permit 06082000
Plan Review Stops For Permit 06082000
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-09 Cont ID  
Sent By rmcdouga Date 2007-10-09 Time 17:22 Rev Time 0.00
Received By rmcdouga Date 2007-10-09 Time 17:22 Sent To  
Notes
2007-10-09 17:24:17THE EQUIPMENT IS LOCATED IN AN A9 FLOOD ZONE. AN
 ELEVATION CERTIFICATE IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-28 Cont ID  
Sent By rmcdouga Date 2007-03-28 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2007-03-28 Time 07:05 Sent To  
Notes
2007-03-28 08:34:21DENIED BY BUILDING (3RD REVIEW)
  
 1) THE GENERATOR TO PAD ATTACHMENT IS SPECIFIED AS (4)
 1/4" X 2-1/4" TAP-CONS. THIS IS NOT ADEQUATE. SEE THE
 SIGNED AND SEALED ENGINEERING FOR THE FEATHERLITE
 GENERATOR PAD WHICH SPECIFIES ALL ANCHORS TO BE 3/8 "
 DIAMETER GALVANIZED GRADE 2 BOLTS WITH GALVANIZED HEAVY
 FENDER WASHERS ON THE BOTTOM OF THE PAD. PLEASE REVISE.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By rmcdouga Date 2007-02-12 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2007-02-12 Time 17:52 Sent To  
Notes
2007-02-12 18:16:19DENIED BY BUILDING
  
 1) THE GENERATOR IS 115.2 INCHES LONG. THE ONLY PAD
 LISTED ON THE ENGINEERING LARGE ENOUGH IS FRCC GEN 5.
 THE CALCULATIONS FOR THIS PAD WERE NOT PROVIDED.
  
 2)FS 471 REQUIRES EACH SHEET TO BE SIGNED AND SEALED
 OR A SIGNED AND SEALED COVER OR INDEX SHEET SPECIFING
 THE PAGES IN THE REPORT OR SPECIFICATIONS. ENGINEERING
 SUBMITTED DOES NOT COMPLY. SEE FAC 61G15-23.
  
 3)THE SIGNATURE IS REQUIRED TO BE ORIGINAL. COLOR
 PHOTO COPIES ARE NOT ACCEPTABLE. ALSO THE DATE ON THE
 ENGINEERING IS THE DATE OF WHEN THE RAISE SEAL IS
 AFFIXED. SEE FS 471.
  
 4) SUBMIT SIGNED AND SEALED PAD AND BOLT LAYOUTS AND
 CONNECTION DETAIL DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By rmcdouga Date 2006-08-28 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2006-08-28 Time 11:24 Sent To  
Notes
2006-08-28 00:00:00DENIED BY BUILDING
  
 1) THE EQUIPMENT IS LOCATED IN AN "A9"
 FLOOD ZONE, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. BASE FLOOD ELEVATION
 IS 13 FEET PLUS THE ADDITIONAL .5 FEET
 REQUIRED BY CITY ORDINANCE.
  
 2) THE CLADLITE PADS LISTED ON THE
 WEBSITE ARE 4" THICK AND HAVE SMALLER
 DIMENSIONS THAN SPECIFIED ON THE SLAB
 CUT SHEET, WHICH SPECIFIES A 6" THICK
 PAD. UNDER EXCLUSIONS AND LIMITATIONS
 THE CLADLITE PADS THE MANUFACTURER
 STATES THAT THEY ARE DESIGNED FOR LIGHT
 GROUND SUPPORTED EQUIPMENT SUCH AS AIR
 CONDITIONING CONDENSERS. ANCHORAGE FOR
 UNITS OVER 36" TALL SHALL BE DESIGNED IN
 ACCORDANCE WITH FBC MECHANICAL SECTION
 301.13. SUBMIT INFORMATION FROM THE
 MANUFACTURER THAT SLAB WILL SUPPORT THIS
 GENERATOR AND CALCULATIONS FOR WIND
 LOADS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 11:10 Sent To  
Notes
2007-09-22 12:12:38 
 ** DENIED 4TH REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE KNOW THERE ARE SOME ITEMS WHICH COULD BE
 REDLINED.
  
 1) NOTE: PLEASE SEE CODE STATED IN THE 2005 WHEN
 PROJECT IS UNDER 2002 NEC> ALSO STATES 220.83 WHICH IS
 FOR RESIDENTIAL.
 THESE COULD BE REDLINED HOWEVER COMMENTS ARE MADE AT
 THIS TIME FOR OTHER ITEMS.
  
 2) NOTE: PLEASE SEE THE LOAD BASED ON ONE YEAR IS
 ACTUALLY HIGHER THAN THE RATING OF THE GENERATOR.
 HOW WILL THIS BE ADDRESSED? WILL LOADS BE SHED?
 702.5, 220.87
  
 3) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW.
 PLEASE PROVIDE DOCUMENTATION FOR THE NEW MTSAND
 WHETHER OR NOT THIS IS SERVICE ENTRANCE RATED. BASED ON
 THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED THERE IS
 NOT INFORMATION ON THIS.
 230, 110.3, 90.7, 230.76, 230.79 ETC,
  
 4) NOTE: PLEASE SEE THE RISER INDICATES *EQUIPMENT
 GROUNDING CONDUCTORS* FROM METER TO THE MTS. IF THE MTS
 IS SERVICE ENTRANCE RATED AND IS THE FIRST MEANS OF
 DISCONNECT, AN *EGC* IS NOT PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
 THIS COULD BE REDLINED HOWEVER PLANS HAVE OTHER NOTES.
  
 5) NOTE: PLEASE CLARIFY WHERE THE ELEVATION OF NEW SLAB
 IS LOCATED ON PLANS?
 PLEASE SEE BUILDING REVIEW COMMENTS ALSO, AS THIS IS
 REQUIRED TO BE 6INCHES ABOVE ANY BASE FLOOD ELEVATION
 IF THIS IS LOCATED IN A FLOOD ZONE A.
 ** IT WAS NOTED THE RESPONSE MENTIONS AN ELEVATION
 CERTIFICATE WILL BE SUBMITTED HOWEVER IT IS THE
 UNDERSTANDING THE ELEVATION WILL BE NEEDED ON SHEETS.
 ** SEE BUILDING REVIEW NOTES**
  
 6) NOTE: PLEASE SEE NO VALUE FOR GAS SCOPE OF WORK
 APPLICATION IS STATED.
 PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK
 MUST INCLUDE ALL LABOR AND MATERIALS, INCLUDING
 EQUIPMENT ETC
 FBC 108.3
 AS THE SCOPE OF WORK HAS INCREASED SINCE ORIGINAL
 PERMIT APPLICATION, PLEASE ADJUST.
  
 7) NOTE: THE NOTICE OF COMMENCEMENT WHICH WAS SUBMITTED
 RECORDED ON 3/14/07 HAS BECOME VOID PER FS 713.13(2).
 WHEN WORK HAS NOT COMMENCES WITHIN 90DAYS OF RECORDING
 THE NOC, THE NOC BECOMES VOID.
 **THIS WILL ONLY NEED TO BE RE-RECORDED AND SUBMITTED
 PRIOR TO PICKING UP THE PERMIT ONCE ISSUED.
  
 8) NOTE: PLANS NOW MENTIONS BUILDING OF NEW WALL,
 HOWEVER NO PLANS FOR WALL ETC WAS SUBMITTED. PLEASE SEE
 COMMENTS FROM OTHER TRADES AS THIS IS NOT AND
 ELECTRICAL REVIEW ITEM. PLEASE ONLY KNOW THE
 CONSTRUCTION OF WALL MAY NOT BE DONE UNDER THE
 ELECTRICAL U LICENSE.
  
 ** PLEASE KNOW SOME OF THE ABOVE ITEMS COULD HAVE BEEN
 REDLINED, HOWEVER PLANS NEEDED SOME OTHER ITEMS TO BE
 ADDRESSED AT THIS TIME.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-25 Cont ID  
Sent By dpalmer Date 2007-03-25 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2007-03-25 Time 07:58 Sent To  
Notes
2007-03-25 09:15:02 
  
 ****** UNSAT 3ND REVIEW******
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER
 THAN ELECTRICAL BY THIS REVIEW. THESE COMMENTS ARE
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 ** IMPORTANT**
 DUE TO MANY OF THE COMMENTS BELOW ONE COMPLETE SET OF
 EACH PLAN SUBMITTED ARE BEING RETAINED BY THIS OFFICE.
 PLEASE ALSO SEE THAT COMMENTS FROM PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS DUE
 TO PLANS CHANGING.
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS WITH
 ALL INFORMATION IN TWO NEAT AND ORDERLY SETS. PLEASE
 SEE THE SHEETS SUBMITTED ARE IN COMPLETE DISARRAY WITH
 MANY SHEETS LOOSE AND NOT IN ANY SETS OR BOUND
 TOGETHER??
 ** PLEASE SEE THERE IS MULTIPLE ELECTRICAL RISERS YET
 SOME CONTAIN THE SAME DATE OF THE PREVIOUS RISER
 DIAGRAM SUBMITTED. PLEASE CORRELATE ALL PLANS, SHEETS,
 DATE THE REVISED SHEETS. THE PLANS WHICH SEEMED TO BE
 REVISED SHEETS CONTAIN A DATE OF JANUARY 10, 2007
 HOWEVER THAT DATESBEFORE THE LAST ELECTRICAL REVIEW
 WHICH WAS DONE ON 2/2/07.THE PREVIOUS REVIEWED PLANS
 ALSO CONTAINED A DATE OF 1/10/07???
 FBC 106.3
  
 2) NOTE: PLEASE SEE THE PLANS SUBMITTED STILL DO NOT
 INDICATE THE CORRECT CODES RELEVANT TO THE PLANS AND
 DESIGNS AT A MINIMUM AS REQUESTED ON THE TWO PREVIOUS
 REVIEWS. PLEASE SEE THE CODES REQUESTED ARE FOR THIS
 REVIEWER ONLY AND OTHER CODES FROM OTHER TRADES MAY BE
 NEEDED.
  
 3) NOTE: PLEASE SEE THE REQUIRED GAS RISER PLANS WERE
 NOT SUBMITTED IN PACKAGE FOR PLUMBING REVIEW. SEE
 PLUMBING REVIEW COMMENTS.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE MODEL OF THE GENERATOR IS STILL
 NOT INDICATED ON THE MANUFACTURES SPECS/CUT SHEETS
 SUBMITTED AND NOW THE BREAKER ON THE RISER DIAGRAM ON
 THE GENERATOR HAS NOW INCREASED WHICH NOW CORRELATES TO
 THE SINGLE PHASE GENERATOR ON SPECS?
 PLEASE SPECIFY WHICH UNIT IS BEING INSTALLED, PLEASE
 HIGHLIGHT UNIT, PLEASE REVISE RISER IF INDEED THIS IS
 NOW THE SINGLE PHASE UNIT AS IT SEEMS.PLEASE SEE THE
 FOLLOWING COMMENT #5.
 110.3, 90.7
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE CONDUCTORS ARE NOT THE CORRECT
 SIZE FROM THE GENERATOR TO THE MTS PER 310.16 BASED ON
 THE NEW 350AMP OVER CURRENT PROTECTION AS SHOWN. PLEASE
 SEE THE 300MCM IS ONLY RATED AT 285AMPS.
 240.4, 310.16.
  
 6) NOTE: PLEASE SEE A COMPLETE READABLE LAYOUT FOR ALL
 EQUIPMENT, LOCATIONS, SET-BACKS ETC WAS NOT SUBMITTED.
 THE DETAILS ON THE SHEETS ARE TOO SMALL, ARE NOT CLEAR
 AND DO NOT PROVIDE THE LOCATIONS OF ALL EQUIPMENT.
 AS THE NOW MTS IS NOT CLEAR IF IT IS SERVICE ENTRANCE
 RATED DUE THE SPECS WHICH MENTIONS EQUIPMENT RATED TO
 GO TO THE SERVICE ENTRANCE EQUIPMENT, IS THE EXISTING
 PANEL LOCATED IN CLOSE PROXIMITY AND DOES IT CONTAIN
 OVER CURRENT PROTECTION?
 IS THIS MTS SERVICE ENTRANCE RATE AND CONTAIN OVER
 CURRENT PROTECTION. THE SPECS MENTIONS FUSES AS PART OF
 THE FEATURES HOWEVER THE NOTES ON SAME SHEET SEEM TO
 CONTRADICT THIS.
 PLEASE SEE 230.76, 230.79, 230.70, 71, 230.90 ETC.
 IS THERE ANY FURTHER SPECS/CUT SHEETS WHICH INDICATE
 THE INTERNAL WIRING AND INFORMATION ON UNIT?
 110.3, 90.7.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 AND BUILDING
 CODE REQUIREMENTS WHICH REQUIRE THIS UNIT TO BE MOUNTED
 A MINIMUM OF 6INCHES ABOVE THE BFE. THE PLANS/SHEETS
 SUBMITTED DO NOT INDICATE THE ELEVATIONS AND SO ON. SEE
 THE BUILDING REVIEW COMMENTS FOR THIS ALSO.
  
 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE
 THE SAME AS SUBMITTED FROM PREVIOUS REVIEWED PLANS
 WHICH ARE FOR A RESIDENTIAL APPLICATION.
 PLEASE SUBMIT THE LOADS INTENDED FOR THIS UNIT AS
 COMMERCIAL.PLEASE ALSO SEE THAT BASED ON NOW A SINGLE
 PHASE UNIT BEING INSTALLED, THIS WILL REVISE SHEETS.
 PLEASE COORDINATE ALL SHEETS, PLANS, ETC.
 220.3,220.10,220.11,220.13, 220.35 ETC
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE WHAT APPEARS TO BE THE LATEST RISER
 DOES NOT CONTAIN AN CONDUCTOR SIZES FROM THE METER TO
 THE MTS??
 PLEASE COMPLETE RISER.
 PLEASE SEE 310.16, 240.4.
  
 10) NOTE: PLEASE KNOW SINCE THERE WERE COMMENTS AND
 PLANS HAVE FAILED THREE TIME FOR SOME OF THE SAME
 NOTES, THE PREVIOUS REVIEW MENTIONED FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS. A FEE IS NOW ASSESSED
 IN THE AMOUNT OF $771.50 WHICH WILL BE REQUIRED TO BE
 PAID BEFORE THE NEXT RE-SUBMITTAL.
  
 11) NOTE: PLEASE SEE AS NOTED ON THE PREVIOUS REVIEW
 THE NOC WILL NEED TO BE RE-RECORDED AS IT HAS EXPIRED
 PER FS 713.13(2).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCEA ND THESE SHEETS SHOULD BE ATTACHED IN
 ONE SET AND LABLED OLD/VOIDED SHEETS.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By dpalmer Date 2007-02-02 Time 08:04 Rev Time 0.00
Received By dpalmer Date 2007-02-01 Time 19:17 Sent To  
Notes
2007-02-02 08:07:46***** UNSAT 2ND REVIEW*******
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **.
  
  
  
 1) NOTE: NO, PLEASE SEE PLANS DO NOT CONTAIN ANY CODE
 INFORMATION AS REQUIRED.
 FBC 106.1.2, 106.5.3.1.2 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT PLANS WHICH REFLECT THE 2002 NFPA-70
 (NEC), THE 2002
 NFPA-110, 2004 FBC.
  
 2) NOTE: OK/NO, PLEASE SEE THE SPECS FOR THE UNIT ARE
 OK, HOWEVER PLEASE SEE THE ENGINEERING SUBMITTED FOR
 THE SLAB CONTAINS A RAISED SEAL OVER A COLOR
 PHOTO-COPIED SIGNATURE WHICH IS NOT PERMITTED UNDER FS
 471.025.
 PLEASE SEE THE STRUCTURAL CONNECTION WITH THE USE OF 4-
 2 1/4 INCH TAPCONS DO NOT SEEM SUFFICIENT, PLEASE SEE
 BUILDING REVIEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE CORRELATE SLAB DETAIL AND SPECS FROM
 MANUFACTURE. PLEASE SEE SIZE INDICATED FOR THIS 80KW
 UNIT DOES NOT EXIST ON SHEETS FROM THIS MANUFACTURE AND
 HAS NOT BEEN LOCATED ON THEIR WEBSITE.
 PLEASE SEE NFPA-110 CHAPTER 7 FOR MOUNTING AND
 LOCATIONS OF GEN..
 FBC CHAPTER 27. 2004.
 ** PLEASE SEE BUILDING REVIEW COMMENTS AS UNIT IS BEING
 PROPOSED IN A FLOOD ZONE "A", WHICH WILL REQUIRE UNIT
 AT A MIN OF 6" ABOVE BFE. PLEASE KNOW, ENGINEERING ON
 SLAB, FOUNDATION AND MOUNTING IS NEEDED AS THE
 INFORMATION SUBMITTED IS NOT SUFFICIENT.
 FBC 106.1.2
  
 3) NOTE:NO, SAME COMMENT, PLEASE PROVIDE LOAD
 CALCULATIONS FOR THE EXISTING SERVICE.
 220.35, 215.5, ETC. PLEASE SEE THE SEC AND FEEDERS TO
 EXISTING PANEL.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE RISER SUBMITTED IS SHOWING SEC'S AND FEEDERS
 WHICH ARE NOT LARGE ENOUGH FOR THE GENERATOR FEEDERS OR
 THE 600A SERVICE BEING SHOWN.
 PLEASE SEE 240.4, 310.16 AND ADJUST.
  
 4) NOTE: NO, SAME COMMENT, NO EGC IS TO BE INSTALLED
 FROM METER TO FIRST MEANS OF DISCONNECT, THIS IS
 PARALLELING THE NEUTRAL.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE RISER IS SHOWING AN "EQUIPMENT GROUNDING
 CONDUCTOR" FROM METER TO MAIN/FIRST MEANS OF DISCONNECT
 WHICH WILL CREATE OBJECTIONABLE CURRENTS. 250.6,
 250.24B
  
 5) NOTE: NO, PLEASE SEE THE SITE PLAN SUBMITTED IN NOT
 SUFFICIENT WITH COMPLETE DETAILS LAYOUTS ETC. THIS MUST
 SHOW ALL IN DETAIL, NO WHITE OUT, OR HAND DRAWN CHANGES
 WHICH DEFER FROM EACH SHEET. PLEASE SEE FBC 106.1.3 FOR
 MINIMUM REQUIRED DETAILS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE BE SURE UNIT IS BEING SHOWN ON SITE/SURVEY PLANS
 SHOWING THE EXACT LOCATIONS AND SETBACKS FROM ALL
 SURROUNDING STRUCTURAL WALLS, FENCES ETC.
 PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE
 WHICH SPECIFIES THE MINIMUM CLEARANCES. PLEASE KNOW, AS
 THE SPEC FOR THE GEN WAS NOT SUBMITTED, IT IS BEING
 ASSUMED THIS UNIT IS A GENERAC UNIT, AND THE
 INFORMATION OBTAINED FROM THIS OFFICE IS THAT THEY
 REQUIRE A MIN OF 5FT FOR THE LARGER LIQUID COOLED
 UNITS.
 110.3, 90.7
  
 6) NOTE: NO, THIS WAS STILL NOT SUBMITTED IN PACKAGE
 AND WILL BE REQUIRED AT STATED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE KNOW AS TO DATE THE SUBMITTED GENERATOR
 PACKAGE MUST CONTAIN THE GAS INFORMATION RISER ETC,
 PLEASE SEE PLUMB REVIEW COMMENTS.
  
 7) NOTE: NO, THE PARTIAL LAYOUT ON ONE SHEET IN THE
 PACKAGE DOES NOT PROVIDE THE DETAIL REQUESTED. PLEASE
 SEE THE MANUFACTURE SPEC/CUT SHEETS DO NOT INDICATE ANY
 LISTING FROM A NRTL.
 PLEASE SEE MODEL, UNIT, VOLTAGE, TYPE OF UNIT IS NOT
 HIGHLIGHTED ON SPECS.
 110.3, 90.7.
 FBC 106.1.2
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE A LAYOUT/OVERVIEW ON PLANS WHICH SHOWS
 THE LOCATIONS OF ALL SERVICE EQUIPMENT AS SHOWN ON
 RISER DIAGRAM.
 PLEASE SEE SPECS FOR ATS DO NOT SEEM TO INDICATE THE
 NEMA RATING IF THE ATS IS OUTSIDE.
 PLEASE ALSO HIGH-LIGHT UNIT.
 FBC 106.1.2, 110.3
  
 8) NOTE: NO/OK, THIS SEEMS TO BE OK, HOWEVER PLEASE
 KNOW AT THIS TIME AS THE LISTING ON EQUIPMENT CAN NOT
 VERIFIED BASED ON THE DOCUMENTATION SUBMITTED THIS
 COMMENT REMAINS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE NO DISCONNECT GROUPED WITH THE EXISTING MAIN
 COULD BE LOCATED ON PLANS OR ON RISER. PLEASE SEE
 225.31-225.39, 230.72.
 PLEASE KNOW THE BREAKER LOCATED INSIDE THE GENERATOR IS
 NOT ACCEPTABLE FOR THIS.
 PLEASE KNOW THE ATS AS SUBMITTED DOES NOT CONTAIN A
 MAIN DISCONNECT RATED FOR THE LOAD SERVED AS REQUIRED
 FOR THE FEEDERS COMING FROM THE GENERATOR. THIS TYPE
 UNIT MAY ONLY CONTAIN "TOGGLE" TYPE DEVICE WHICH IS NOT
 RATED.
  
 9) NOTE: NO, SEE NOTE #3 ABOVE. PLEASE ALSO SEE NOT
 LOAD CALCULATIONS ARE SUBMITTED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT COMPLETE ELECTRICAL LOAD CALCULATIONS FOR
 THIS COMMERCIAL BUILDING. PLEASE SEE THE LOAD CALCS
 SUBMITTED ARE FOR A RESIDENTIAL HOUSE WHEN THIS IS A
 COMM BLDG.???? 220.3, 220.10, 220.11, 220.13, ETC
 CONTINUOUS LOADS AT 125% 215.3, 230.42 ETC.
  
 10) NOTE: OK, HOWEVER THIS COMMENT WILL REMAIN AS ANY
 NEW SHEETS SHOULD CONTAIN THE SAME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 WHEN SUBMITTING PLANS/DESIGNS WHICH ARE NOT DONE BY AN
 ENGINEER, PLEASE SEE THAT ALL PLANS/DESIGNS MUST
 CONTAIN THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS AND DESIGNS.
 FBC 106.1.2
  
  
 **** NEW NOTES****
  
 11) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT HAS
 EXPIRED SINCE ITS RECORDING IN AUGUST. PLEASE SEE THAT
 THE NOC WILL ONLY NEED TO BE RE-RECORDED BEFORE PICKING
 UP THE PERMIT. FS 713.13(2).
  
 12) NOTE: PLEASE SEE AS THE SCOPE OF WORK AND EQUIPMENT
 HAS INCREASED SO THE VALUE FOR COMPELTE SCOPE OF WORK
 NEEDS TO BE INCREASED.
 FBC 108.3
  
 13) NOTE: PLEASE SEE 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2006-09-05 Time 10:14 Sent To  
Notes
2006-09-05 00:00:00********** UNSAT *************
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH
 REFLECT THE 2002 NFPA-70 (NEC), THE 2002
 NFPA-110, 2004 FBC.
  
 2) NOTE: PLEASE CORRELATE SLAB DETAIL
 AND SPECS FROM MANUFACTURE. PLEASE SEE
 SIZE INDICATED FOR THIS 80KW UNIT DOES
 NOT EXIST ON SHEETS FROM THIS
 MANUFACTURE AND HAS NOT BEEN LOCATED ON
 THEIR WEBSITE.
 PLEASE SEE NFPA-110 CHPATER 7 FOR
 MOUNTING AND LOCATIONS OF GEN..
 FBC CHAPTER 27. 2004.
 ** PLEASE SEE BUILDING REVIEW COMMENTS
 AS UNIT IS BEING PROPOSED IN A FLOOD
 ZONE "A", WHICH WILL REQUIRE UNIT AT A
 MIN OF 6" ABOVE BFE. PLEASE KNOW,
 ENGINEERING ON SLAB, FOUNDATION AND
 MOUNTING IS NEEDED AS THE INFORMATION
 SUBMITTED IS NOT SUFFICIENT.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE RISER SUBMITTED IS
 SHOWING SEC'S AND FEEDERS WHICH ARE NOT
 LARGE ENOUGH FOR THE GENERATOR FEEDERS
 OR THE 600A SERVICE BEING SHOWN.
 PLEASE SEE 240.4,310.16 AND ADJUST.
  
 4) NOTE: PLEASE SEE RISER IS SHOWING AN
 " EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO MAIN/FIRST MEANS OF DISCONNECT
 WHICH WILL CREATE OBJECTIONAL CURRENTS. 250.6,250.24B
  
 5) NOTE: PLEASE BE SURE UNIT IS BEING
 SHOWN ON SITE/SURVEY PLANS SHOWING THE
 EXACT LOCATIONS AND SETBACKS FROM ALL
 SURROUNDING STRUCTURAL WALLS, FENCES
 ETC.
 PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE
 WHICH SPECIFIES THE MIN
 CLEARENCES. PLEASE KNOW, AS THE SPEC FOR
 THE GEN WAS NOT SUBMITTED, IT IS BEING
 ASSUMED THIS UNIT IS A GENERAC UNIT, AND
 THE INFORMATION OBTAINED FROM THIS
 OFFICE IS THAT THEY REQUIRE A MIN OF 5FT
 FOR THE LARGER LIQUID COOLED UNITS.
 110.3,90.7
  
 6) NOTE: PLEASE KNOW AS TO DATE THE
 SUBMITTED GENERATOR PACKAGE MUST CONTAIN
 THE GAS INFORMATION RISER ETC, PLEASE
 SEE PLUMB REVIEW COMMENTS.
  
 7) NOTE: PLEASE PROVIDE A
 LAYOUT/OVERVIEW ON PLANS WHICH SHOWS THE
 LOCATIONS OF ALL SERVICE EQUIPMENT AS
 SHWON ON RISER DIAGRAM.
 PLEASE SEE SPECS FOR ATS DO NOT SEEM TO
 INDICATE THE NEMA RATING IF THE ATS IS
 OUTSIDE.
 PLEASE ALSO HIGH-LIGHT UNIT.
 FBC 106.1.2, 110.3
  
 8) NOTE: PLEASE SEE NO DISCONNECT
 GROUPED WITH THE EXISTING MAIN COULD BE
 LOCATED ON PLANS OR ON RISER. PLEASE SEE 225.31-225.39,
 230.72.
 PLEASE KNOW THE BREAKER LOCATED INSIDE
 THE GENERATOR IS NOT ACCEPTABLE FOR
 THIS.
 PLEASE KNOW THE ATS AS SUBMITTED DEOS
 NOT CONTAIN A MAIN DISCONNECT RATED FOR
 THE LOAD SERVED AS REQUIRED FOR THE
 FEEDERS COMING FROM THE GENERATOR. THIS
 TYPE UNIT MAY ONLY CONTAINA "TOGGLE"
 TYPE DEVICE WHICH IS NOT RATED.
  
 9) NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICAL LOAD CALCULATIONS FOR THIS
 COMMERCIAL BUILDING. PLEASE SEE THE LOAD
 CALCS SUBMITTED ARE FOR A RESIDENTIAL
 HOUSE WHEN THIS IS A COMM BLDG.????
 220.3,220.10,220.11,220.13, ETC
 CONTINUOUS LOADS AT 125% 215.3,230.42
 ETC.
  
 10) NOTE: WHEN SUBMITTING PLANS/DESIGNS
 WHICH ARE NOT DONE BY AN ENGINEER,
 PLEASE SEE THAT ALL PLANS/DESIGNS MUST
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBEL FOR PLANS AND
 DESIGNS.
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By mwennerg Date 2007-10-23 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2007-10-23 Time 14:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 16:31 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 16:24 Sent To E
Notes
2007-04-12 16:27:35*****DENIED*****
  
  
 PLEASE ADDRESS COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 16:55 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 16:55 Sent To  
Notes
2007-02-23 16:58:55*****UNSAT*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER
 SYSTEMS, SHALL BE REFERENCED.
  
 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL
 IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE
 SAID PROPERTY AND/OR VICINITY THEREOF.
  
 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR
 (CAR AND/OR TRUCK) DAMAGE?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By mawillia Date 2006-10-11 Time 13:53 Rev Time 0.00
Received By mawillia Date 2006-10-11 Time 13:24 Sent To  
Notes
2006-10-11 13:49:11*****UNSAT*****
  
  
  
 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER
 SYSTEMS, SHALL BE REFERENCED.
  
 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL
 IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE
 SAID PROPERTY AND/OR VICINITY THEREOF.
  
 4.)PROVIDE MANUFACTURER SPECS SHEETS FOR THE
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR
 (CAR AND/OR TRUCK) DAMAGE?
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-10-11 Cont ID  
Sent By mawillia Date 2006-10-11 Time 13:57 Rev Time 0.00
Received By mawillia Date 2006-10-11 Time 13:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-11-02 Time 16:05 Rev Time 0.00
Received By kstevens Date 2007-11-02 Time 16:05 Sent To  
Notes
2007-11-02 16:25:14DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A SEPARATE GAS PERMIT IS REQUIRED
  
 FROM THE PREVIOUS REVIEWS:
 ****FROM PREVIOUS REVIEWS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. OK
 2. OK
  
 3. TYPE OF GAS (NATURAL SHOWN ON
 GENERATOR SPECIFICATION SHEETS. INDICATE
 ON ISOMETRIC).
 ****RESPONSE NOTED, BUT THERE IS A CONFLICT OF
 INFORMATION SUBMITTED, APPLICATION AND PLANS INDICATE
 AND LP SYSTEM WITH AN UNDERGROUND 1000 GAL LP TANK. THE
 INFORMATION SUBMITTED UNDER THE RISER DIAGRAM STATES
 NATURAL GAS. PLEASE CLARIFY.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU'S INDICATED ON THE
 INFORMATION UNDER THE RISER DIAGRAM STATES 273,120
 BTU"S/PER HR, BUT THE MANUF. SPECIFICATIONS SHEETS
 INDICATE 1,100 CUBIC FT/HR. . MANUF SPECIFICATION
 SHEETS ALSO INDICATE NATURAL GAS. NO LP GAS IS
 INDICATED. PLEASE CLARIFY.
  
 5. OK
 6.OK
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION REQUIREMENTS SHALL BE
 SUBMITTED TO VERIFY CLEARANCES FROM
 ADJACENT STRUCTURES.
 ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED
 WITH THE MANUF. SPECIFICATION SHEETS.
 ******INSTALLATION INSTRUCTIONS WITH REQUIRED
 CLEARANCES HAV NOT BEEN SUBMITTED.
  
 ************NEW COMMENT*************
  
 1B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-11-02 Cont ID  
Sent By kstevens Date 2007-04-07 Time 13:06 Rev Time 0.00
Received By kstevens Date 2007-04-07 Time 13:06 Sent To  
Notes
2007-04-07 13:07:38DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A SEPARATE GAS PERMIT IS REQUIRED
  
 FROM THE PREVIOUS REVIEWS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS (NATURAL SHOWN ON
 GENERATOR SPECIFICATION SHEETS. INDICATE
 ON ISOMETRIC).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION REQUIREMENTS SHALL BE
 SUBMITTED TO VERIFY CLEARANCES FROM
 ADJACENT STRUCTURES.
 ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED
 WITH THE MANUF. SPECIFICATION SHEETS
  
 ************NEW COMMENT*************
  
 1B. THE GAS PERMIT APPLICATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE COMMERICAL GENERATOR AND ALL
 INFORMATION REQUESTED SHALL BE SUBMITTED WITH THE GAS
 PERMIT APPLICATION.
 ******NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-02-15 Cont ID  
Sent By kstevens Date 2007-02-15 Time 07:15 Rev Time 0.00
Received By kstevens Date 2007-02-14 Time 18:51 Sent To  
Notes
2007-02-15 07:32:09DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A SEPARATE GAS PERMIT IS REQUIRED
  
 FROM THE PREVIOUS REVIEW:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS (NATURAL SHOWN ON
 GENERATOR SPECIFICATION SHEETS. INDICATE
 ON ISOMETRIC).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION REQUIREMENTS SHALL BE
 SUBMITTED TO VERIFY CLEARANCES FROM
 ADJACENT STRUCTURES.
 ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED
 WITH THE MANUF. SPECIFICATION SHEETS
  
 ************NEW COMMENT*************
  
 1B. THE GAS PERMIT APPLICATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE COMMERICAL GENERATOR AND ALL
 INFORMATION REQUESTED SHALL BE SUBMITTED WITH THE GAS
 PERMIT APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 18:25 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 18:25 Sent To  
Notes
2006-09-06 00:00:00THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS (NATURAL SHOWN ON
 GENERATOR SPECIFICATION SHEETS. INDICATE
 ON ISOMETRIC).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION REQUIREMENTS SHALL BE
 SUBMITTED TO VERIFY CLEARANCES FROM
 ADJACENT STRUCTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 16:49 Sent To  
Notes
2007-09-22 11:10:52TO COMM BOARD SPACE #61, DVP.
2007-08-30 16:50:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 10:21 Sent To  
Notes
2007-03-22 10:23:02TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 12:06 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 12:06 Sent To  
Notes
2007-01-30 09:53:56TO "COMM" BD#20
2007-01-18 12:07:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-11 Cont ID  
Sent By mawillia Date 2006-10-11 Time 13:57 Rev Time 0.00
Received By mawillia Date 2006-08-26 Time 16:33 Sent To  
Notes
2006-08-31 00:00:00TO "COMM" BD#50
2006-08-26 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 4 Status F Date 2007-10-02 Cont ID  
Sent By lfranco Date 2007-10-02 Time 19:58 Rev Time 0.00
Received By lfranco Date 2007-10-02 Time 19:58 Sent To  
Notes
2007-10-02 20:00:31PLANNING AND ZONING: **** FAILED ****
  
 1. PROVIDE RESPONSE IN WRITING AND SUBMIT ALL RESPONSES
 TOGETHER WITH THE RE-SUBMITTAL OF THE PERMIT.
  
 2. PURSUANT TO SECTION 94-444(B): SCREENING OF THE
 MECHANICAL EQUIPTMENT SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR
 COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A NOTATION IS MADE THAT A WALL AND
 LANDSCAPING WILL BE ADDED WITH NO DETAILS OF WALL OR
 LANDSCAPING.PLEASE PROVIDE AN ELEVATION OF THE WALL
 AND THE TYPE, HEIGHT, WIDTH, ALONG WITH THE
 LANDSCAPING.PROVIDE A SITE PLAN WITH ALL DIMENSIONS
 AT A LARGER SCALE WHICH INCLUDES THE WHOLE SITE PLAN IN
 RESPECT TO THE BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, CALL ME AT THE NUMBER
 BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2007-03-22 Cont ID  
Sent By jbabcock Date 2007-03-22 Time 17:50 Rev Time 0.00
Received By jbabcock Date 2007-03-22 Time 17:46 Sent To I
Notes
2007-03-22 17:50:47PLANNING AND ZONING **FAILED**
  
 1. PROVIDE RESPONSES TO COMMENTS IN WRITING AND SUBMIT
 ALL RESPONSES TOGETHER WITH RE-SUBMITTAL OF PERMIT.
  
 2. PURSUANT TO SECTION 94-444 (B) STATES THAT ALL
 MECHANICAL EQUIPMENT SHALL BE SCREENED.
  
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-02-08 Cont ID  
Sent By mmclean Date 2007-02-08 Time 12:05 Rev Time 0.00
Received By mmclean Date 2007-02-08 Time 12:05 Sent To  
Notes
2007-02-08 13:44:55DENIED,
 1. SEE ELECTRICAL COMMENT #5
 2. THE EXISTING HEDGES IS SHOWN ON THE SURVEYS AS 5.2FT
 AND THE DISTANCE OF THE PROPOSED GENERATOR IS 5FT FROM
 SIDE PROPERTY LINE.PLEASE CLARIFY.
 3. PLEASE PROVIDE A LARGER COPY OF SURVEYS, THE ONES
 SUBMITTED IS NOT VISIBLE TO READ.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By mmclean Date 2006-09-19 Time 10:20 Rev Time 0.00
Received By mmclean Date 2006-09-19 Time 10:20 Sent To I
Notes
2006-09-19 00:00:00DENIED,
 1. PLEASE INDICATE IF THE PROPOSED
 GENERATOR WILL TAKE ANY REQUIRED
 PARKING SPACE.
 2. PLEASE INDICATE THE DISTANCE OF THE
 PROPSED GENERATOR FROM THE FRONT
 PROPERTY LINE.
  
 NOTE: THE PROPOSED EQUIPMENT MUST BE
 SCREEN FROM PUBLIC VIEW. IT CAN BE
 SCREENED WITH EITHER BRICK, DECORATIVE
 CONCRETE OR OTHER DECORATIVE MASONRY OR
 COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCPAED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.
 SEC 94-444(B)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720