Plan Review Details - Permit 06082000
Plan Review Stops For Permit 06082000 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-10-09 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-10-09 |
Time |
17:22 |
Sent To |
|
|
Notes |
2007-10-09 17:24:17 | THE EQUIPMENT IS LOCATED IN AN A9 FLOOD ZONE. AN | | ELEVATION CERTIFICATE IS REQUIRED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-03-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-03-28 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-03-28 |
Time |
07:05 |
Sent To |
|
|
Notes |
2007-03-28 08:34:21 | DENIED BY BUILDING (3RD REVIEW) | | | | 1) THE GENERATOR TO PAD ATTACHMENT IS SPECIFIED AS (4) | | 1/4" X 2-1/4" TAP-CONS. THIS IS NOT ADEQUATE. SEE THE | | SIGNED AND SEALED ENGINEERING FOR THE FEATHERLITE | | GENERATOR PAD WHICH SPECIFIES ALL ANCHORS TO BE 3/8 " | | DIAMETER GALVANIZED GRADE 2 BOLTS WITH GALVANIZED HEAVY | | FENDER WASHERS ON THE BOTTOM OF THE PAD. PLEASE REVISE. | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-02-12 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-02-12 |
Time |
17:52 |
Sent To |
|
|
Notes |
2007-02-12 18:16:19 | DENIED BY BUILDING | | | | 1) THE GENERATOR IS 115.2 INCHES LONG. THE ONLY PAD | | LISTED ON THE ENGINEERING LARGE ENOUGH IS FRCC GEN 5. | | THE CALCULATIONS FOR THIS PAD WERE NOT PROVIDED. | | | | 2)FS 471 REQUIRES EACH SHEET TO BE SIGNED AND SEALED | | OR A SIGNED AND SEALED COVER OR INDEX SHEET SPECIFING | | THE PAGES IN THE REPORT OR SPECIFICATIONS. ENGINEERING | | SUBMITTED DOES NOT COMPLY. SEE FAC 61G15-23. | | | | 3)THE SIGNATURE IS REQUIRED TO BE ORIGINAL. COLOR | | PHOTO COPIES ARE NOT ACCEPTABLE. ALSO THE DATE ON THE | | ENGINEERING IS THE DATE OF WHEN THE RAISE SEAL IS | | AFFIXED. SEE FS 471. | | | | 4) SUBMIT SIGNED AND SEALED PAD AND BOLT LAYOUTS AND | | CONNECTION DETAIL DRAWINGS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2006-08-28 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2006-08-28 |
Time |
11:24 |
Sent To |
|
|
Notes |
2006-08-28 00:00:00 | DENIED BY BUILDING | | | | 1) THE EQUIPMENT IS LOCATED IN AN "A9" | | FLOOD ZONE, AN ELEVATION CERTIFICATE | | WILL BE REQUIRED. BASE FLOOD ELEVATION | | IS 13 FEET PLUS THE ADDITIONAL .5 FEET | | REQUIRED BY CITY ORDINANCE. | | | | 2) THE CLADLITE PADS LISTED ON THE | | WEBSITE ARE 4" THICK AND HAVE SMALLER | | DIMENSIONS THAN SPECIFIED ON THE SLAB | | CUT SHEET, WHICH SPECIFIES A 6" THICK | | PAD. UNDER EXCLUSIONS AND LIMITATIONS | | THE CLADLITE PADS THE MANUFACTURER | | STATES THAT THEY ARE DESIGNED FOR LIGHT | | GROUND SUPPORTED EQUIPMENT SUCH AS AIR | | CONDITIONING CONDENSERS. ANCHORAGE FOR | | UNITS OVER 36" TALL SHALL BE DESIGNED IN | | ACCORDANCE WITH FBC MECHANICAL SECTION | | 301.13. SUBMIT INFORMATION FROM THE | | MANUFACTURER THAT SLAB WILL SUPPORT THIS | | GENERATOR AND CALCULATIONS FOR WIND | | LOADS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-09-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-22 |
Time |
12:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-22 |
Time |
11:10 |
Sent To |
|
|
Notes |
2007-09-22 12:12:38 | | | ** DENIED 4TH REVIEW** | | | | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW | | WHICH ARE STILL IN NEED OF ADDRESSING. | | PLEASE KNOW THERE ARE SOME ITEMS WHICH COULD BE | | REDLINED. | | | | 1) NOTE: PLEASE SEE CODE STATED IN THE 2005 WHEN | | PROJECT IS UNDER 2002 NEC> ALSO STATES 220.83 WHICH IS | | FOR RESIDENTIAL. | | THESE COULD BE REDLINED HOWEVER COMMENTS ARE MADE AT | | THIS TIME FOR OTHER ITEMS. | | | | 2) NOTE: PLEASE SEE THE LOAD BASED ON ONE YEAR IS | | ACTUALLY HIGHER THAN THE RATING OF THE GENERATOR. | | HOW WILL THIS BE ADDRESSED? WILL LOADS BE SHED? | | 702.5, 220.87 | | | | 3) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW. | | PLEASE PROVIDE DOCUMENTATION FOR THE NEW MTSAND | | WHETHER OR NOT THIS IS SERVICE ENTRANCE RATED. BASED ON | | THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED THERE IS | | NOT INFORMATION ON THIS. | | 230, 110.3, 90.7, 230.76, 230.79 ETC, | | | | 4) NOTE: PLEASE SEE THE RISER INDICATES *EQUIPMENT | | GROUNDING CONDUCTORS* FROM METER TO THE MTS. IF THE MTS | | IS SERVICE ENTRANCE RATED AND IS THE FIRST MEANS OF | | DISCONNECT, AN *EGC* IS NOT PERMITTED BEFORE THE FIRST | | MEANS OF DISCONNECT. | | THIS COULD BE REDLINED HOWEVER PLANS HAVE OTHER NOTES. | | | | 5) NOTE: PLEASE CLARIFY WHERE THE ELEVATION OF NEW SLAB | | IS LOCATED ON PLANS? | | PLEASE SEE BUILDING REVIEW COMMENTS ALSO, AS THIS IS | | REQUIRED TO BE 6INCHES ABOVE ANY BASE FLOOD ELEVATION | | IF THIS IS LOCATED IN A FLOOD ZONE A. | | ** IT WAS NOTED THE RESPONSE MENTIONS AN ELEVATION | | CERTIFICATE WILL BE SUBMITTED HOWEVER IT IS THE | | UNDERSTANDING THE ELEVATION WILL BE NEEDED ON SHEETS. | | ** SEE BUILDING REVIEW NOTES** | | | | 6) NOTE: PLEASE SEE NO VALUE FOR GAS SCOPE OF WORK | | APPLICATION IS STATED. | | PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK | | MUST INCLUDE ALL LABOR AND MATERIALS, INCLUDING | | EQUIPMENT ETC | | FBC 108.3 | | AS THE SCOPE OF WORK HAS INCREASED SINCE ORIGINAL | | PERMIT APPLICATION, PLEASE ADJUST. | | | | 7) NOTE: THE NOTICE OF COMMENCEMENT WHICH WAS SUBMITTED | | RECORDED ON 3/14/07 HAS BECOME VOID PER FS 713.13(2). | | WHEN WORK HAS NOT COMMENCES WITHIN 90DAYS OF RECORDING | | THE NOC, THE NOC BECOMES VOID. | | **THIS WILL ONLY NEED TO BE RE-RECORDED AND SUBMITTED | | PRIOR TO PICKING UP THE PERMIT ONCE ISSUED. | | | | 8) NOTE: PLANS NOW MENTIONS BUILDING OF NEW WALL, | | HOWEVER NO PLANS FOR WALL ETC WAS SUBMITTED. PLEASE SEE | | COMMENTS FROM OTHER TRADES AS THIS IS NOT AND | | ELECTRICAL REVIEW ITEM. PLEASE ONLY KNOW THE | | CONSTRUCTION OF WALL MAY NOT BE DONE UNDER THE | | ELECTRICAL U LICENSE. | | | | ** PLEASE KNOW SOME OF THE ABOVE ITEMS COULD HAVE BEEN | | REDLINED, HOWEVER PLANS NEEDED SOME OTHER ITEMS TO BE | | ADDRESSED AT THIS TIME. | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH | | MAY AFFECT ELECTRICAL PLANS OR DESIGN. | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS | | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. | | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY | | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND | | THIS REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-25 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-25 |
Time |
07:58 |
Sent To |
|
|
Notes |
2007-03-25 09:15:02 | | | | | ****** UNSAT 3ND REVIEW****** | | | | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 | | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE | | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY | | THE CITY OF WEST PALM BEACH. | | | | ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER | | THAN ELECTRICAL BY THIS REVIEW. THESE COMMENTS ARE | | REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER | | TRADE. | | | | ** IMPORTANT** | | DUE TO MANY OF THE COMMENTS BELOW ONE COMPLETE SET OF | | EACH PLAN SUBMITTED ARE BEING RETAINED BY THIS OFFICE. | | PLEASE ALSO SEE THAT COMMENTS FROM PREVIOUS REVIEW | | STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS DUE | | TO PLANS CHANGING. | | | | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS WITH | | ALL INFORMATION IN TWO NEAT AND ORDERLY SETS. PLEASE | | SEE THE SHEETS SUBMITTED ARE IN COMPLETE DISARRAY WITH | | MANY SHEETS LOOSE AND NOT IN ANY SETS OR BOUND | | TOGETHER?? | | ** PLEASE SEE THERE IS MULTIPLE ELECTRICAL RISERS YET | | SOME CONTAIN THE SAME DATE OF THE PREVIOUS RISER | | DIAGRAM SUBMITTED. PLEASE CORRELATE ALL PLANS, SHEETS, | | DATE THE REVISED SHEETS. THE PLANS WHICH SEEMED TO BE | | REVISED SHEETS CONTAIN A DATE OF JANUARY 10, 2007 | | HOWEVER THAT DATESBEFORE THE LAST ELECTRICAL REVIEW | | WHICH WAS DONE ON 2/2/07.THE PREVIOUS REVIEWED PLANS | | ALSO CONTAINED A DATE OF 1/10/07??? | | FBC 106.3 | | | | 2) NOTE: PLEASE SEE THE PLANS SUBMITTED STILL DO NOT | | INDICATE THE CORRECT CODES RELEVANT TO THE PLANS AND | | DESIGNS AT A MINIMUM AS REQUESTED ON THE TWO PREVIOUS | | REVIEWS. PLEASE SEE THE CODES REQUESTED ARE FOR THIS | | REVIEWER ONLY AND OTHER CODES FROM OTHER TRADES MAY BE | | NEEDED. | | | | 3) NOTE: PLEASE SEE THE REQUIRED GAS RISER PLANS WERE | | NOT SUBMITTED IN PACKAGE FOR PLUMBING REVIEW. SEE | | PLUMBING REVIEW COMMENTS. | | FBC 106.1.2 | | | | 4) NOTE: PLEASE SEE THE MODEL OF THE GENERATOR IS STILL | | NOT INDICATED ON THE MANUFACTURES SPECS/CUT SHEETS | | SUBMITTED AND NOW THE BREAKER ON THE RISER DIAGRAM ON | | THE GENERATOR HAS NOW INCREASED WHICH NOW CORRELATES TO | | THE SINGLE PHASE GENERATOR ON SPECS? | | PLEASE SPECIFY WHICH UNIT IS BEING INSTALLED, PLEASE | | HIGHLIGHT UNIT, PLEASE REVISE RISER IF INDEED THIS IS | | NOW THE SINGLE PHASE UNIT AS IT SEEMS.PLEASE SEE THE | | FOLLOWING COMMENT #5. | | 110.3, 90.7 | | FBC 106.3.5.1.2 | | | | 5) NOTE: PLEASE SEE THE CONDUCTORS ARE NOT THE CORRECT | | SIZE FROM THE GENERATOR TO THE MTS PER 310.16 BASED ON | | THE NEW 350AMP OVER CURRENT PROTECTION AS SHOWN. PLEASE | | SEE THE 300MCM IS ONLY RATED AT 285AMPS. | | 240.4, 310.16. | | | | 6) NOTE: PLEASE SEE A COMPLETE READABLE LAYOUT FOR ALL | | EQUIPMENT, LOCATIONS, SET-BACKS ETC WAS NOT SUBMITTED. | | THE DETAILS ON THE SHEETS ARE TOO SMALL, ARE NOT CLEAR | | AND DO NOT PROVIDE THE LOCATIONS OF ALL EQUIPMENT. | | AS THE NOW MTS IS NOT CLEAR IF IT IS SERVICE ENTRANCE | | RATED DUE THE SPECS WHICH MENTIONS EQUIPMENT RATED TO | | GO TO THE SERVICE ENTRANCE EQUIPMENT, IS THE EXISTING | | PANEL LOCATED IN CLOSE PROXIMITY AND DOES IT CONTAIN | | OVER CURRENT PROTECTION? | | IS THIS MTS SERVICE ENTRANCE RATE AND CONTAIN OVER | | CURRENT PROTECTION. THE SPECS MENTIONS FUSES AS PART OF | | THE FEATURES HOWEVER THE NOTES ON SAME SHEET SEEM TO | | CONTRADICT THIS. | | PLEASE SEE 230.76, 230.79, 230.70, 71, 230.90 ETC. | | IS THERE ANY FURTHER SPECS/CUT SHEETS WHICH INDICATE | | THE INTERNAL WIRING AND INFORMATION ON UNIT? | | 110.3, 90.7. | | FBC 106.1.2, 106.3.5.1.2 | | | | 7) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 AND BUILDING | | CODE REQUIREMENTS WHICH REQUIRE THIS UNIT TO BE MOUNTED | | A MINIMUM OF 6INCHES ABOVE THE BFE. THE PLANS/SHEETS | | SUBMITTED DO NOT INDICATE THE ELEVATIONS AND SO ON. SEE | | THE BUILDING REVIEW COMMENTS FOR THIS ALSO. | | | | 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE | | THE SAME AS SUBMITTED FROM PREVIOUS REVIEWED PLANS | | WHICH ARE FOR A RESIDENTIAL APPLICATION. | | PLEASE SUBMIT THE LOADS INTENDED FOR THIS UNIT AS | | COMMERCIAL.PLEASE ALSO SEE THAT BASED ON NOW A SINGLE | | PHASE UNIT BEING INSTALLED, THIS WILL REVISE SHEETS. | | PLEASE COORDINATE ALL SHEETS, PLANS, ETC. | | 220.3,220.10,220.11,220.13, 220.35 ETC | | FBC 106.1.2 | | | | 9) NOTE: PLEASE SEE WHAT APPEARS TO BE THE LATEST RISER | | DOES NOT CONTAIN AN CONDUCTOR SIZES FROM THE METER TO | | THE MTS?? | | PLEASE COMPLETE RISER. | | PLEASE SEE 310.16, 240.4. | | | | 10) NOTE: PLEASE KNOW SINCE THERE WERE COMMENTS AND | | PLANS HAVE FAILED THREE TIME FOR SOME OF THE SAME | | NOTES, THE PREVIOUS REVIEW MENTIONED FS 553.80(2)(B) | | WITH RESPECT TO REPEAT COMMENTS. A FEE IS NOW ASSESSED | | IN THE AMOUNT OF $771.50 WHICH WILL BE REQUIRED TO BE | | PAID BEFORE THE NEXT RE-SUBMITTAL. | | | | 11) NOTE: PLEASE SEE AS NOTED ON THE PREVIOUS REVIEW | | THE NOC WILL NEED TO BE RE-RECORDED AS IT HAS EXPIRED | | PER FS 713.13(2). | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCEA ND THESE SHEETS SHOULD BE ATTACHED IN | | ONE SET AND LABLED OLD/VOIDED SHEETS. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-02-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-02 |
Time |
08:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-01 |
Time |
19:17 |
Sent To |
|
|
Notes |
2007-02-02 08:07:46 | ***** UNSAT 2ND REVIEW******* | | | | **** IMPORTANT**** | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. | | | | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY | | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE | | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE | | #1** | | | | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A | | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW | | NOTE WILL BE REMOVED. | | | | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF | | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. | | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS | | REVIEW NOTE #1** | | | | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** | | NEW NOTES **. | | | | | | | | 1) NOTE: NO, PLEASE SEE PLANS DO NOT CONTAIN ANY CODE | | INFORMATION AS REQUIRED. | | FBC 106.1.2, 106.5.3.1.2 ETC. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE SUBMIT PLANS WHICH REFLECT THE 2002 NFPA-70 | | (NEC), THE 2002 | | NFPA-110, 2004 FBC. | | | | 2) NOTE: OK/NO, PLEASE SEE THE SPECS FOR THE UNIT ARE | | OK, HOWEVER PLEASE SEE THE ENGINEERING SUBMITTED FOR | | THE SLAB CONTAINS A RAISED SEAL OVER A COLOR | | PHOTO-COPIED SIGNATURE WHICH IS NOT PERMITTED UNDER FS | | 471.025. | | PLEASE SEE THE STRUCTURAL CONNECTION WITH THE USE OF 4- | | 2 1/4 INCH TAPCONS DO NOT SEEM SUFFICIENT, PLEASE SEE | | BUILDING REVIEW COMMENTS. | | | | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** | | PLEASE CORRELATE SLAB DETAIL AND SPECS FROM | | MANUFACTURE. PLEASE SEE SIZE INDICATED FOR THIS 80KW | | UNIT DOES NOT EXIST ON SHEETS FROM THIS MANUFACTURE AND | | HAS NOT BEEN LOCATED ON THEIR WEBSITE. | | PLEASE SEE NFPA-110 CHAPTER 7 FOR MOUNTING AND | | LOCATIONS OF GEN.. | | FBC CHAPTER 27. 2004. | | ** PLEASE SEE BUILDING REVIEW COMMENTS AS UNIT IS BEING | | PROPOSED IN A FLOOD ZONE "A", WHICH WILL REQUIRE UNIT | | AT A MIN OF 6" ABOVE BFE. PLEASE KNOW, ENGINEERING ON | | SLAB, FOUNDATION AND MOUNTING IS NEEDED AS THE | | INFORMATION SUBMITTED IS NOT SUFFICIENT. | | FBC 106.1.2 | | | | 3) NOTE:NO, SAME COMMENT, PLEASE PROVIDE LOAD | | CALCULATIONS FOR THE EXISTING SERVICE. | | 220.35, 215.5, ETC. PLEASE SEE THE SEC AND FEEDERS TO | | EXISTING PANEL. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE SEE RISER SUBMITTED IS SHOWING SEC'S AND FEEDERS | | WHICH ARE NOT LARGE ENOUGH FOR THE GENERATOR FEEDERS OR | | THE 600A SERVICE BEING SHOWN. | | PLEASE SEE 240.4, 310.16 AND ADJUST. | | | | 4) NOTE: NO, SAME COMMENT, NO EGC IS TO BE INSTALLED | | FROM METER TO FIRST MEANS OF DISCONNECT, THIS IS | | PARALLELING THE NEUTRAL. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE SEE RISER IS SHOWING AN "EQUIPMENT GROUNDING | | CONDUCTOR" FROM METER TO MAIN/FIRST MEANS OF DISCONNECT | | WHICH WILL CREATE OBJECTIONABLE CURRENTS. 250.6, | | 250.24B | | | | 5) NOTE: NO, PLEASE SEE THE SITE PLAN SUBMITTED IN NOT | | SUFFICIENT WITH COMPLETE DETAILS LAYOUTS ETC. THIS MUST | | SHOW ALL IN DETAIL, NO WHITE OUT, OR HAND DRAWN CHANGES | | WHICH DEFER FROM EACH SHEET. PLEASE SEE FBC 106.1.3 FOR | | MINIMUM REQUIRED DETAILS. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE BE SURE UNIT IS BEING SHOWN ON SITE/SURVEY PLANS | | SHOWING THE EXACT LOCATIONS AND SETBACKS FROM ALL | | SURROUNDING STRUCTURAL WALLS, FENCES ETC. | | PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE | | WHICH SPECIFIES THE MINIMUM CLEARANCES. PLEASE KNOW, AS | | THE SPEC FOR THE GEN WAS NOT SUBMITTED, IT IS BEING | | ASSUMED THIS UNIT IS A GENERAC UNIT, AND THE | | INFORMATION OBTAINED FROM THIS OFFICE IS THAT THEY | | REQUIRE A MIN OF 5FT FOR THE LARGER LIQUID COOLED | | UNITS. | | 110.3, 90.7 | | | | 6) NOTE: NO, THIS WAS STILL NOT SUBMITTED IN PACKAGE | | AND WILL BE REQUIRED AT STATED. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE KNOW AS TO DATE THE SUBMITTED GENERATOR | | PACKAGE MUST CONTAIN THE GAS INFORMATION RISER ETC, | | PLEASE SEE PLUMB REVIEW COMMENTS. | | | | 7) NOTE: NO, THE PARTIAL LAYOUT ON ONE SHEET IN THE | | PACKAGE DOES NOT PROVIDE THE DETAIL REQUESTED. PLEASE | | SEE THE MANUFACTURE SPEC/CUT SHEETS DO NOT INDICATE ANY | | LISTING FROM A NRTL. | | PLEASE SEE MODEL, UNIT, VOLTAGE, TYPE OF UNIT IS NOT | | HIGHLIGHTED ON SPECS. | | 110.3, 90.7. | | FBC 106.1.2 | | | | **PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE PROVIDE A LAYOUT/OVERVIEW ON PLANS WHICH SHOWS | | THE LOCATIONS OF ALL SERVICE EQUIPMENT AS SHOWN ON | | RISER DIAGRAM. | | PLEASE SEE SPECS FOR ATS DO NOT SEEM TO INDICATE THE | | NEMA RATING IF THE ATS IS OUTSIDE. | | PLEASE ALSO HIGH-LIGHT UNIT. | | FBC 106.1.2, 110.3 | | | | 8) NOTE: NO/OK, THIS SEEMS TO BE OK, HOWEVER PLEASE | | KNOW AT THIS TIME AS THE LISTING ON EQUIPMENT CAN NOT | | VERIFIED BASED ON THE DOCUMENTATION SUBMITTED THIS | | COMMENT REMAINS. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE SEE NO DISCONNECT GROUPED WITH THE EXISTING MAIN | | COULD BE LOCATED ON PLANS OR ON RISER. PLEASE SEE | | 225.31-225.39, 230.72. | | PLEASE KNOW THE BREAKER LOCATED INSIDE THE GENERATOR IS | | NOT ACCEPTABLE FOR THIS. | | PLEASE KNOW THE ATS AS SUBMITTED DOES NOT CONTAIN A | | MAIN DISCONNECT RATED FOR THE LOAD SERVED AS REQUIRED | | FOR THE FEEDERS COMING FROM THE GENERATOR. THIS TYPE | | UNIT MAY ONLY CONTAIN "TOGGLE" TYPE DEVICE WHICH IS NOT | | RATED. | | | | 9) NOTE: NO, SEE NOTE #3 ABOVE. PLEASE ALSO SEE NOT | | LOAD CALCULATIONS ARE SUBMITTED AT THIS TIME. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | PLEASE SUBMIT COMPLETE ELECTRICAL LOAD CALCULATIONS FOR | | THIS COMMERCIAL BUILDING. PLEASE SEE THE LOAD CALCS | | SUBMITTED ARE FOR A RESIDENTIAL HOUSE WHEN THIS IS A | | COMM BLDG.???? 220.3, 220.10, 220.11, 220.13, ETC | | CONTINUOUS LOADS AT 125% 215.3, 230.42 ETC. | | | | 10) NOTE: OK, HOWEVER THIS COMMENT WILL REMAIN AS ANY | | NEW SHEETS SHOULD CONTAIN THE SAME. | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | WHEN SUBMITTING PLANS/DESIGNS WHICH ARE NOT DONE BY AN | | ENGINEER, PLEASE SEE THAT ALL PLANS/DESIGNS MUST | | CONTAIN THE PRINTED NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR PLANS AND DESIGNS. | | FBC 106.1.2 | | | | | | **** NEW NOTES**** | | | | 11) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT HAS | | EXPIRED SINCE ITS RECORDING IN AUGUST. PLEASE SEE THAT | | THE NOC WILL ONLY NEED TO BE RE-RECORDED BEFORE PICKING | | UP THE PERMIT. FS 713.13(2). | | | | 12) NOTE: PLEASE SEE AS THE SCOPE OF WORK AND EQUIPMENT | | HAS INCREASED SO THE VALUE FOR COMPELTE SCOPE OF WORK | | NEEDS TO BE INCREASED. | | FBC 108.3 | | | | 13) NOTE: PLEASE SEE 553.80(2)(B) WITH RESPECT TO | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | NOTICE AT THIS TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-09-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-05 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-05 |
Time |
10:14 |
Sent To |
|
|
Notes |
2006-09-05 00:00:00 | ********** UNSAT ************* | | | | 1) NOTE: PLEASE SUBMIT PLANS WHICH | | REFLECT THE 2002 NFPA-70 (NEC), THE 2002 | | NFPA-110, 2004 FBC. | | | | 2) NOTE: PLEASE CORRELATE SLAB DETAIL | | AND SPECS FROM MANUFACTURE. PLEASE SEE | | SIZE INDICATED FOR THIS 80KW UNIT DOES | | NOT EXIST ON SHEETS FROM THIS | | MANUFACTURE AND HAS NOT BEEN LOCATED ON | | THEIR WEBSITE. | | PLEASE SEE NFPA-110 CHPATER 7 FOR | | MOUNTING AND LOCATIONS OF GEN.. | | FBC CHAPTER 27. 2004. | | ** PLEASE SEE BUILDING REVIEW COMMENTS | | AS UNIT IS BEING PROPOSED IN A FLOOD | | ZONE "A", WHICH WILL REQUIRE UNIT AT A | | MIN OF 6" ABOVE BFE. PLEASE KNOW, | | ENGINEERING ON SLAB, FOUNDATION AND | | MOUNTING IS NEEDED AS THE INFORMATION | | SUBMITTED IS NOT SUFFICIENT. | | FBC 106.1.2 | | | | 3) NOTE: PLEASE SEE RISER SUBMITTED IS | | SHOWING SEC'S AND FEEDERS WHICH ARE NOT | | LARGE ENOUGH FOR THE GENERATOR FEEDERS | | OR THE 600A SERVICE BEING SHOWN. | | PLEASE SEE 240.4,310.16 AND ADJUST. | | | | 4) NOTE: PLEASE SEE RISER IS SHOWING AN | | " EQUIPMENT GROUNDING CONDUCTOR" FROM | | METER TO MAIN/FIRST MEANS OF DISCONNECT | | WHICH WILL CREATE OBJECTIONAL CURRENTS. 250.6,250.24B | | | | 5) NOTE: PLEASE BE SURE UNIT IS BEING | | SHOWN ON SITE/SURVEY PLANS SHOWING THE | | EXACT LOCATIONS AND SETBACKS FROM ALL | | SURROUNDING STRUCTURAL WALLS, FENCES | | ETC. | | PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE | | WHICH SPECIFIES THE MIN | | CLEARENCES. PLEASE KNOW, AS THE SPEC FOR | | THE GEN WAS NOT SUBMITTED, IT IS BEING | | ASSUMED THIS UNIT IS A GENERAC UNIT, AND | | THE INFORMATION OBTAINED FROM THIS | | OFFICE IS THAT THEY REQUIRE A MIN OF 5FT | | FOR THE LARGER LIQUID COOLED UNITS. | | 110.3,90.7 | | | | 6) NOTE: PLEASE KNOW AS TO DATE THE | | SUBMITTED GENERATOR PACKAGE MUST CONTAIN | | THE GAS INFORMATION RISER ETC, PLEASE | | SEE PLUMB REVIEW COMMENTS. | | | | 7) NOTE: PLEASE PROVIDE A | | LAYOUT/OVERVIEW ON PLANS WHICH SHOWS THE | | LOCATIONS OF ALL SERVICE EQUIPMENT AS | | SHWON ON RISER DIAGRAM. | | PLEASE SEE SPECS FOR ATS DO NOT SEEM TO | | INDICATE THE NEMA RATING IF THE ATS IS | | OUTSIDE. | | PLEASE ALSO HIGH-LIGHT UNIT. | | FBC 106.1.2, 110.3 | | | | 8) NOTE: PLEASE SEE NO DISCONNECT | | GROUPED WITH THE EXISTING MAIN COULD BE | | LOCATED ON PLANS OR ON RISER. PLEASE SEE 225.31-225.39, | | 230.72. | | PLEASE KNOW THE BREAKER LOCATED INSIDE | | THE GENERATOR IS NOT ACCEPTABLE FOR | | THIS. | | PLEASE KNOW THE ATS AS SUBMITTED DEOS | | NOT CONTAIN A MAIN DISCONNECT RATED FOR | | THE LOAD SERVED AS REQUIRED FOR THE | | FEEDERS COMING FROM THE GENERATOR. THIS | | TYPE UNIT MAY ONLY CONTAINA "TOGGLE" | | TYPE DEVICE WHICH IS NOT RATED. | | | | 9) NOTE: PLEASE SUBMIT COMPLETE | | ELECTRICAL LOAD CALCULATIONS FOR THIS | | COMMERCIAL BUILDING. PLEASE SEE THE LOAD | | CALCS SUBMITTED ARE FOR A RESIDENTIAL | | HOUSE WHEN THIS IS A COMM BLDG.???? | | 220.3,220.10,220.11,220.13, ETC | | CONTINUOUS LOADS AT 125% 215.3,230.42 | | ETC. | | | | 10) NOTE: WHEN SUBMITTING PLANS/DESIGNS | | WHICH ARE NOT DONE BY AN ENGINEER, | | PLEASE SEE THAT ALL PLANS/DESIGNS MUST | | CONTAIN THE PRINTED NAME AND SIGNATURE | | OF THE PERSON RESPONSIBEL FOR PLANS AND | | DESIGNS. | | FBC 106.1.2 | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-10-23 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-10-23 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-12 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-12 |
Time |
16:24 |
Sent To |
E |
|
Notes |
2007-04-12 16:27:35 | *****DENIED***** | | | | | | PLEASE ADDRESS COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-23 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-23 |
Time |
16:55 |
Sent To |
|
|
Notes |
2007-02-23 16:58:55 | *****UNSAT***** | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER | | SYSTEMS, SHALL BE REFERENCED. | | | | 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION | | OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL | | IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE | | SAID PROPERTY AND/OR VICINITY THEREOF. | | | | 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR | | (CAR AND/OR TRUCK) DAMAGE? | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-11 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-11 |
Time |
13:24 |
Sent To |
|
|
Notes |
2006-10-11 13:49:11 | *****UNSAT***** | | | | | | | | 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER | | SYSTEMS, SHALL BE REFERENCED. | | | | 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION | | OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL | | IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE | | SAID PROPERTY AND/OR VICINITY THEREOF. | | | | 4.)PROVIDE MANUFACTURER SPECS SHEETS FOR THE | | GENERATOR AND ASSOCIATED EQUIPMENT. | | | | 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR | | (CAR AND/OR TRUCK) DAMAGE? | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-11 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-11 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
F |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-02 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-02 |
Time |
16:05 |
Sent To |
|
|
Notes |
2007-11-02 16:25:14 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | A SEPARATE GAS PERMIT IS REQUIRED | | | | FROM THE PREVIOUS REVIEWS: | | ****FROM PREVIOUS REVIEWS: | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR THE GAS PERMIT: | | | | 1. OK | | 2. OK | | | | 3. TYPE OF GAS (NATURAL SHOWN ON | | GENERATOR SPECIFICATION SHEETS. INDICATE | | ON ISOMETRIC). | | ****RESPONSE NOTED, BUT THERE IS A CONFLICT OF | | INFORMATION SUBMITTED, APPLICATION AND PLANS INDICATE | | AND LP SYSTEM WITH AN UNDERGROUND 1000 GAL LP TANK. THE | | INFORMATION SUBMITTED UNDER THE RISER DIAGRAM STATES | | NATURAL GAS. PLEASE CLARIFY. | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | ****RESPONSE NOTED, BUT THE BTU'S INDICATED ON THE | | INFORMATION UNDER THE RISER DIAGRAM STATES 273,120 | | BTU"S/PER HR, BUT THE MANUF. SPECIFICATIONS SHEETS | | INDICATE 1,100 CUBIC FT/HR. . MANUF SPECIFICATION | | SHEETS ALSO INDICATE NATURAL GAS. NO LP GAS IS | | INDICATED. PLEASE CLARIFY. | | | | 5. OK | | 6.OK | | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION REQUIREMENTS SHALL BE | | SUBMITTED TO VERIFY CLEARANCES FROM | | ADJACENT STRUCTURES. | | ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED | | WITH THE MANUF. SPECIFICATION SHEETS. | | ******INSTALLATION INSTRUCTIONS WITH REQUIRED | | CLEARANCES HAV NOT BEEN SUBMITTED. | | | | ************NEW COMMENT************* | | | | 1B. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-07 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-07 |
Time |
13:06 |
Sent To |
|
|
Notes |
2007-04-07 13:07:38 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | A SEPARATE GAS PERMIT IS REQUIRED | | | | FROM THE PREVIOUS REVIEWS: | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR THE GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | 3. TYPE OF GAS (NATURAL SHOWN ON | | GENERATOR SPECIFICATION SHEETS. INDICATE | | ON ISOMETRIC). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION REQUIREMENTS SHALL BE | | SUBMITTED TO VERIFY CLEARANCES FROM | | ADJACENT STRUCTURES. | | ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED | | WITH THE MANUF. SPECIFICATION SHEETS | | | | ************NEW COMMENT************* | | | | 1B. THE GAS PERMIT APPLICATION SHALL BE SUBMITTED WITH | | THE APPLICATION FOR THE COMMERICAL GENERATOR AND ALL | | INFORMATION REQUESTED SHALL BE SUBMITTED WITH THE GAS | | PERMIT APPLICATION. | | ******NOT ADDRESSED | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-02-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-15 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-14 |
Time |
18:51 |
Sent To |
|
|
Notes |
2007-02-15 07:32:09 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | A SEPARATE GAS PERMIT IS REQUIRED | | | | FROM THE PREVIOUS REVIEW: | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR THE GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | 3. TYPE OF GAS (NATURAL SHOWN ON | | GENERATOR SPECIFICATION SHEETS. INDICATE | | ON ISOMETRIC). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION REQUIREMENTS SHALL BE | | SUBMITTED TO VERIFY CLEARANCES FROM | | ADJACENT STRUCTURES. | | ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED | | WITH THE MANUF. SPECIFICATION SHEETS | | | | ************NEW COMMENT************* | | | | 1B. THE GAS PERMIT APPLICATION SHALL BE SUBMITTED WITH | | THE APPLICATION FOR THE COMMERICAL GENERATOR AND ALL | | INFORMATION REQUESTED SHALL BE SUBMITTED WITH THE GAS | | PERMIT APPLICATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-09-06 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-09-06 |
Time |
18:25 |
Sent To |
|
|
Notes |
2006-09-06 00:00:00 | THE FOLLOWING INFORMATION IS REQUIRED | | FOR THE GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | 3. TYPE OF GAS (NATURAL SHOWN ON | | GENERATOR SPECIFICATION SHEETS. INDICATE | | ON ISOMETRIC). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION REQUIREMENTS SHALL BE | | SUBMITTED TO VERIFY CLEARANCES FROM | | ADJACENT STRUCTURES. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-30 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-30 |
Time |
16:49 |
Sent To |
|
|
Notes |
2007-09-22 11:10:52 | TO COMM BOARD SPACE #61, DVP. | 2007-08-30 16:50:44 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-03-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-22 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-22 |
Time |
10:21 |
Sent To |
|
|
Notes |
2007-03-22 10:23:02 | TO "COMM" BD#15 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-18 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-18 |
Time |
12:06 |
Sent To |
|
|
Notes |
2007-01-30 09:53:56 | TO "COMM" BD#20 | 2007-01-18 12:07:07 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-11 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-08-26 |
Time |
16:33 |
Sent To |
|
|
Notes |
2006-08-31 00:00:00 | TO "COMM" BD#50 | 2006-08-26 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2007-10-02 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2007-10-02 |
Time |
19:58 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2007-10-02 |
Time |
19:58 |
Sent To |
|
|
Notes |
2007-10-02 20:00:31 | PLANNING AND ZONING: **** FAILED **** | | | | 1. PROVIDE RESPONSE IN WRITING AND SUBMIT ALL RESPONSES | | TOGETHER WITH THE RE-SUBMITTAL OF THE PERMIT. | | | | 2. PURSUANT TO SECTION 94-444(B): SCREENING OF THE | | MECHANICAL EQUIPTMENT SHALL BE CONSTRUCTED OF BRICK, | | DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR | | COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE | | LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT | | INTERVALS.A NOTATION IS MADE THAT A WALL AND | | LANDSCAPING WILL BE ADDED WITH NO DETAILS OF WALL OR | | LANDSCAPING.PLEASE PROVIDE AN ELEVATION OF THE WALL | | AND THE TYPE, HEIGHT, WIDTH, ALONG WITH THE | | LANDSCAPING.PROVIDE A SITE PLAN WITH ALL DIMENSIONS | | AT A LARGER SCALE WHICH INCLUDES THE WHOLE SITE PLAN IN | | RESPECT TO THE BUILDING. | | | | IF YOU HAVE ANY QUESTIONS, CALL ME AT THE NUMBER | | BELOW. | | | | LINDA MIA FRANCO | | SENIOR PLANER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1443 | | EMAIL: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2007-03-22 |
|
|
Cont ID |
|
Sent By |
jbabcock |
Date |
2007-03-22 |
Time |
17:50 |
Rev Time |
0.00 |
Received By |
jbabcock |
Date |
2007-03-22 |
Time |
17:46 |
Sent To |
I |
|
Notes |
2007-03-22 17:50:47 | PLANNING AND ZONING **FAILED** | | | | 1. PROVIDE RESPONSES TO COMMENTS IN WRITING AND SUBMIT | | ALL RESPONSES TOGETHER WITH RE-SUBMITTAL OF PERMIT. | | | | 2. PURSUANT TO SECTION 94-444 (B) STATES THAT ALL | | MECHANICAL EQUIPMENT SHALL BE SCREENED. | | | | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE | | CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY | | DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH | | SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2007-02-08 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2007-02-08 |
Time |
12:05 |
Sent To |
|
|
Notes |
2007-02-08 13:44:55 | DENIED, | | 1. SEE ELECTRICAL COMMENT #5 | | 2. THE EXISTING HEDGES IS SHOWN ON THE SURVEYS AS 5.2FT | | AND THE DISTANCE OF THE PROPOSED GENERATOR IS 5FT FROM | | SIDE PROPERTY LINE.PLEASE CLARIFY. | | 3. PLEASE PROVIDE A LARGER COPY OF SURVEYS, THE ONES | | SUBMITTED IS NOT VISIBLE TO READ. | | | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-09-19 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-09-19 |
Time |
10:20 |
Sent To |
I |
|
Notes |
2006-09-19 00:00:00 | DENIED, | | 1. PLEASE INDICATE IF THE PROPOSED | | GENERATOR WILL TAKE ANY REQUIRED | | PARKING SPACE. | | 2. PLEASE INDICATE THE DISTANCE OF THE | | PROPSED GENERATOR FROM THE FRONT | | PROPERTY LINE. | | | | NOTE: THE PROPOSED EQUIPMENT MUST BE | | SCREEN FROM PUBLIC VIEW. IT CAN BE | | SCREENED WITH EITHER BRICK, DECORATIVE | | CONCRETE OR OTHER DECORATIVE MASONRY OR | | COMPARABLY DURABLE WOOD AND STEEL. WALLS | | SHALL BE LANDSCPAED WITH SHRUBS AND | | HEDGES PLANTED AT TWO-FOOT INTERVALS. | | SEC 94-444(B) | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|
|