Plan Review Stops For Permit 06081989 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-09-12 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-09-12 |
Time |
07:29 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-09-12 |
Time |
07:29 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-27 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-08-27 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-08-27 |
Time |
13:54 |
Sent To |
PC |
|
Notes |
2006-08-27 00:00:00 | | | | | DENIED | | | | 1) PROVIDE NEW NOA FOR TAMKO BUR PRODUCT | | AS THE ONE SUBMITTED HAS EXPIRED | | | | 2) BE SURE TO CHOOSE A SYSTEM FROM THE | | PRODUCT APPROVAL THAT WILL BE USED | | | | 3) PER 1609.6.1 THE SIMPLIFIED | | CALCULATION METHOD FOR WIND LOADS SHALL | | NOT BE USED TO DETERMINE WIND PRESSURES | | FOR BUILDINGS OVER 60 FT IN HEIGHT. | | PLEASE SUBMIT ENGINEERED CALCULATIONS | | | | 4) PROVIDE THE CALCULATIONS FOR THE | | ENHANCED FASTENING THAT WILL BE USED FOR | | THE PERIMETER AND CORNER ZONES | | | | ADRIAN MORSE | | BLDG PLAN REVIEW | | 561-805 6716 |
|
|
|