Plan Review Details - Permit 06081985
Plan Review Stops For Permit 06081985
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-31 Cont ID  
Sent By mawillia Date 2006-08-31 Time 10:35 Rev Time 0.00
Received By mawillia Date 2006-08-31 Time 10:35 Sent To  
Notes
2006-08-31 00:00:00**APPROVED**
  
  
  
  
 1.) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION.
 INSTALL UL CERTIFICATE AT THE FIRE ALARM
 CONTROL PANEL AND PROVIDE A COPY TO
 WPBFR BY FINAL FIRE ALARM INSPECTION.
  
 2.) AS PER WPBFR, WATERFLOW TO ACTIVATE
 A GENERAL ALARM WITHIN 45 TO 60 SECONDS.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW