Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By amorse Date 2006-09-09 Time 12:29 Rev Time 0.00
Received By amorse Date 2006-09-09 Time 12:29 Sent To PC
Notes
2006-09-09 00:00:00 
  
 DENIED
  
 1) ENGINEERING FOR THE FOOTER SIZE HAS
 NOT BEEN SIGNED AND SEALED
  
 2) PLEASE NOTE THAT THEIR IS A FOOTING
 SIZE TABLE ON PAGE ONE BUT WITH THE BEAM
 SPAN INDICATED A 12X12 FOOTER WITH 2- #5
 BARS WOULD BE REQUIRED. IF YOU WISH TO
 USE THE 8X9.5 SIZE THE ENGINEER IS
 REQUIRED TO SIGN AND SEAL THE
 CALCULATION SHEET
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:32 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:32 Sent To B
Notes
2006-09-05 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-09-09 Time   Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 15:05 Sent To  
Notes
2006-08-26 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-04 Cont ID  
Sent By mmclean Date 2006-09-04 Time 08:10 Rev Time 0.00
Received By mmclean Date 2006-09-04 Time 08:10 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved