2006-10-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-101.2.2 FBC 2004. |
| |
| 2- SITE PLAN TO HAVE ALL DIMENSIONS, INCLUDING LOT |
| SIZE,TO VERIFY COMPLIANCE WITH SETBACKS AND DISTANCE |
| BETWEEN BUILDINGS. |
| |
| 3-SHEET #5: |
| A) BUCK DETAILS DON'T APPLY. PROPOSED ADDITION IS |
| MASONRY CONSTRUCTION. DETAILS SHOWN ARE FOR WOOD FRAMED |
| WALLS. NEED DETAILS THAT MATCH PROPOSED CONSTRUCTION. |
| SEE SEC. R613.62 FOR SPECIFIC WINDOW AND DOOR BUCK |
| REQUIREMENTS. |
| B) ALSO, MAKE SURE DETAILS ARE FOR TYPE OF WINDOW |
| USED. SOME DETAILS ARE FOR CASEMENT WINDOWS. THERE ARE |
| NOT CASEMENT WINDOWS. REVISE AS REQUIRED. |
| |
| 4- SHEET #6: |
| A)SIZE OF BEAM SPECIFIED ON DETAILS S-2 AND S-3 |
| DON'T MATCH SIZE SPECIFIED ON ROOF FRAMING PLAN. REVISE |
| AS REQUIRED. |
| |
| B)CLARIFY DETAIL S-1.IS THIS NEW CONSTRUCTION OR |
| EXISTING. DRAWINGS CALL FOR NEW FOOTING AND NEW STUDS |
| AT 16". OC. REVISE/CLARIFY AS REQUIRED. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| C)THERE ARE 2 DIFFERENT DETAILS F/6.0. |
| CLARIFY/REVISE AS REQUIRED. ALSO, PROVIDE ONLY THE |
| DETAILS THAT APPLY TO THIS JOB AND CLEARLY KEY THEM IN |
| THE FLOOR PLANS AND FRAMING PLANS. |
| |
| D)PROVIDE COMPLETE SPECS FOR DETAILS S-2 AND S-3: |
| NEED COMPLETE WALL SPECS, INCLUDING PLYWOOD SHEATHING |
| SIZE FATENER TYPE AND SPACING. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| E) SEE SIMPSONG ANCHORSSPECIFIED ON DETAILS. SEE |
| CURRENT SIMPSON CATALOGUEAND UPDATE NUMBER AND TYPE |
| OFFASTENERS AS REQUIRED TO MATCH PUBLISHED VALUES. |
| OTHERWISE, PROVIDE COMPLETE ENGINEERING ANALYSIS IF |
| NUMBERS DIFFER FROM THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| F)DETAIL S-1: SPECIFY STUDS CONNECTORS AT TOP AND |
| BOTTOM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| PROVIDE COMPLETE SPECS FOR WALL INSTALLATION. SEC. |
| 106.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 4- SHEET #7.0: LOCATION AND NUMBEROF VERTICAL |
| REINFORCEMENTS SHOWN ON THIS FOUNDATION PLANDOENS'T |
| MATCHFLOOR PLAN REVISE AS REQUIRED TO MATCH EACH |
| OTHER. SEC. 106.1. 2 CITY AMENDMENTS TO FBC 2004. |
| |
| 5- SHEE 8.0: |
| A)UPDATE DESIGN CRITERIA. USEFBC 2004. EDITION. |
| DOORS AND WINDOWS ARE NOT IMPACT GLAZING. SEE PRODUCT |
| APPROVAL SUBMITTED AND REVISE AS REQUIRED. |
| |
| B) ROOF SHEATHING SIZE AND TYPE SHOWN ON ROOF |
| TRANSITION DETAIL DOESN'T MATCHSIZE AND TYPESHOWN |
| ON ROOF NAILING NOTE. REVISE AS REQUIRED. |
| |
| C) MISSING DETAILE/6.0. PROVIDE DETAIL AND SPECIFY |
| TRUSS CONNECTORS AT BOTH ENDS. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 6- NOTICE OF COMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| RECORDING IF WORK IS NOT STARTED. SEC. 713.13(2) |
| FLORIDA STATUTES. NEED RE-RECORDED NOC. |
| |
| 7- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| APPROVED IN WRITTING AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. INCLUDING THE STORM SHUTTERS. |
| |
| 8- ROOF TRUSSES ARE REQUIRED FOR REVIEW PRIOR TO |
| INSTALLATION AS REQUIRED BY SECTION R802.10 OF 2004 |
| RESIDENTIAL CODE. |
| |
| 9-ENGINEEROF RECORD TO SPECIFYROOF TILE FASTENING |
| AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC |
| 2004. |
| |
| 10- AS REQUIRED BY RULE 9B-72, PROVIDE FLORIDA/LOCAL |
| PRODUCT APPROVAL FOR: |
| A)FLAT ROOF SYSTEM. NOA 03-0212.12 SUBMITTED EXPIRED |
| ON 07/19/06. |
| |
| B) CONCRETE LINTELS.NOA 03-0605.04 SUBMITTED IS FOR |
| 4", 6" & 12" WIDE LINTELS. SPECIFY ON PLANS SIZES OF |
| LINTEL TO BE USED AND PROVIDE CORRECT PRODUCT |
| APPROVAL. |
| |
| C)ALL SIMPSON TRUSS CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. |
| |
| D)NOA FOR PGT OUTSWING ALUMINUM FRENCH DOOR THAT |
| MATCHES ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL. . |
| NOA 02-0625.01 SUBMITTED DOESN'T MATCH ONE SUBMITTED |
| FOR FLORIDA PRODUCT APPROVAL FL253. PROVIDE MATCHING |
| INFORMATION. |
| |
| E)NOA 02-0702.02 FOR"SH-4000" ALUMINUM SINGLE HUNG |
| WINDOWS IS EXPIRED. PROVIDE CURRENT ONE. |
| |
| 11-SOIL TEST REPORT: |
| A) PROVIDE 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND |
| DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| |
| B)REPORT NEEDS TO HAVE ENGINEERING FIRM CERTIFICATE |
| OF AUTHORIZATION # AS REQUIRED BY ADMINISTRATIVE CODE |
| 61G15-23.002. |
| |
| 12- STORM SHUTTERS: |
| A) PROVIDE FLORIDA PRODUCT APPROVAL WITH 2004 CODE |
| VERSION. ONE SUBMITTED IS FOR 2001. |
| |
| B) PROVIDE KEY PLAN AND COMPLETE INSTALLATION |
| SCHEDULE. SEE ATTACHED COPY OF CITY SAMPLE FOR |
| INSTALLATION SCHEDULE AND PROVIDE ALL REQUIRED |
| INFORMATION. |
| |
| 13- OWES $3.18 FOR RADON FEES. |
| |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |