Plan Review Details - Permit 06081920
Plan Review Stops For Permit 06081920
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-13 Cont ID  
Sent By lmartine Date 2007-09-13 Time 12:53 Rev Time 0.00
Received By lmartine Date 2007-09-13 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-30 Cont ID  
Sent By mjacobs Date 2007-07-30 Time 15:26 Rev Time 0.00
Received By mjacobs Date 2007-07-30 Time 11:18 Sent To  
Notes
2007-07-30 12:10:23PERMIT: 06081920
 ADD: 1750 N. FLORIDA MANGO RD. #302
 CONT: BILL MARTIN RENAVATIONS INC.
 TEL: (561)863-8227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)OK
  
 4) OK
  
 5)OK
  
 6)OK
  
 THE PLANS SHALL BE DESIGNED TO THE 2004 FLORIDA
 BUILDING CODE WITH THE 2006 REVISIONS.
 NEW*****
 A)THE OCCUPANCY GROUP INDICATED ON THE PLANS ARE
 INCORRECT. FBC 305.1GROUP 'E'THE USE OF A BUILDING
 OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE
 PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES
 THROUGH THE 12TH GRADE.SEE FBC 304.1 GROUP 'B' . FOR
 THE OCCUPANCIES WHICH INCLUDE EDUCATIONAL OCCUPANCIES
 ABOVE THE 12TH GRADE.
  
 B)SUBMIT A DOOR SCHEDULE AND A FINISH SCHEDULE FOR
 EACH ROOM LISTING THE TYPE OF MATERIAL FOR THE
 FLOORS/WALLS AND CEILINGS ETC. NOTE: FBC 1210.2 WALLS
 WITHIN 2 FEET OF UNIRALS AND WATERCLOSETS SHALL HAVE A
 SMOOTH "HARD", NON ABSORBENT SURFACE TO A HEIGHT 4 FEET
 ABOVE THE FLOOR. *****PAINT IS NOT A "HARD"
 SURFACE!!!!
  
 C)THE EXISTING WALL AND THE NEW WALL HAS THE SAME
 TYPE OF SYMBOL. THESE WALL SHALL HAVE DIFFERENT
 SYMBOLS.
  
 D)FBC.803.5INTERIOR WALL AND CEILINGFINISH SHALL
 HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT
 SPECIFIED IN TABLE 803.5. SHOW THIS INFORMATION ON THE
 FINISH SCHEDULE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 18:46 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 17:00 Sent To  
Notes
2007-03-30 17:32:05BUILDING PLAN REVIEW
 PERMIT: 06081920
 ADD: 1750 N. FLORIDA MANGO RD. #302
 CONT: BILL MARTIN RENAVATIONS INC.
 TEL: (561)863-8227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE INFORMATION SUBMITTED FOR THE HEAD + FLOOR
 DETAIL SHALL INDICATEHOW OR WHAT THE BLOCKING WILL BE
 ATTATCHED TO AND THE MATERIALS USED TO SECURE IT. WILL
 THE BLOCKING BE ATTATCHED TO THE CEILING OR THE
 STRUCTURE ABOVE? AND WHAT IS THE ROOF STRUCTURE?. SEE
 NOTE #2 FROM PREVIOUS REVIEW.
  
 3)THE INFORMATION FOR THE PARTITION WAS NOT
 RESUBMITTED. THE POCKET DOORS SHOWN ON THE DETAIL FOR
 THE MOVEABLE PARTIONS ARE NOT INDICATED ON THE
 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROSED AND SHOW IN DETAIL THAT IT WILL CONFORM
 TO THE CODE.PLEASE SEE NOTES FROM LAST REVIEW WERE
 NOT ADDRESSED.
  
 4) SHOW THE CLEAR FLOOR SPACE FOR THE TOILET AND
 BATHROOMS COMPLYING WITH SECTIONS 11-4.16,11-4.19,
 FIG. 28 AND 30E.
  
 5)NOTE FROM FIRST REVIEW (2)FBC. 11-4.22.2 ALL
 DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH SEC.
 11-4.13 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE. SEE NEW STAFF
 BATH/MEN'S AND WOMEN'S TOILETS.
  
 6)SHEET A-1. THE OCCUPANT LOAD INDICATED IS
 INCORRECT. CLARIFY.AND SEE FBC. 1004.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 17:59 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 15:03 Sent To  
Notes
2006-12-07 16:57:43BUILDING PLAN REVIEW
 PERMIT:06081920
 ADD:1750 N. FLORIDA MANGO RD #302
 CONT: BILL MARTIN RENAVATIONS INC.
 TEL: (561)863-8227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 2ND
 ACTION: DENIED
  
 1) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.-------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
  
  
 2)W.P.B.AMENDMENTS. 106.1.2THE BUILDING OFFICIAL
 MAY REQUIRE DETAILS, COMPUTATUONS, STRESS DIAGRAMS, AND
 OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR
 INSTALLATION AND THE BASIS OF CALCULATIONS.MORE
 INFORMATION IS NEEDED FOR THE INSTALLATION OF THE
 MOVABLEPARTITIONS.A DETAIL DRAWING INDICATING ALL
 THE MATERIALS WHICH WILL BE USED TO HOLD THE PARTITIONS
 IN PLACE SHALL BE SUBMITTED TO OUR OFFICE. WHAT IS THE
 STRUCTURE ABOVE THE CEILING? IS IT WOOD
 JOIST/CONCRETE/BAR-JOIST OR LIGHT WEIGHT CONCRETE?
  
 3) WHAT TYPE OF FINISH WILL BE ON THE PARTITIONS? THERE
 ARE FOUR OR FIVE DIFFEREND TYPES OF FINISH MENTION IN
 THE BROCHURE INDICATE WHICH ONE WILL BE USED ON THE
 DRAWINGS. THE POCKET FOR THE MOVABLE PATIONS ON THE
 DRAWINGS, DONOT MATCH THE ONES ON THE BROCHURE. CLARIFY
 THIS INFORMATION. SHOW THE CONTINUOS HEADER DETAIL FOR
 THE TOP TRACK.
  
 4)FBC. 805.2WHERE REQUIRED TO BE FLAME RESISTANT,
 DECORATIVE MATERIALS SHALL BE TESTED BY AN APPROVED
 AGENCY AND PASS TEST 1 OR 2, AS APPROPRIATE,DESCRIBED
 IN NFPA 701 OR SUCH MATERIALS SHALL BE NONCOMBUSTIBLE.
 REPORTS OF TEST RESULTS SHALL BE PREPARED IN ACCORDANCE
 WITH NFPA 701 AND FURNISHED TO THE CODE OFFICIAL UPON
 REQUEST.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By mjacobs Date 2006-09-08 Time 18:12 Rev Time 0.00
Received By mjacobs Date 2006-09-08 Time 17:20 Sent To PC
Notes
2006-09-08 00:00:001) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 ) L.O.M.R.
  
 2) 11-4.22.2
 ALL DOOS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SECTION 11-4.13. DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 3) SUBMIT A DETAIL DRAWING FOR THE NEW
 MOVEABLE PARTIONS SHOWING THE CONNECTION
 TO THE CEILING AND HOW THE WILL BE HELD
 IN A CLOSED POSITION. SUBMIT THE PRODUCT
 APPROVALS OR THE MANUFACTURE SPECTS
 SHEETS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 18:07 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 18:07 Sent To B
Notes
2007-09-11 18:08:15*** PROVISO***
  
 1) NOTE: PLEASE INSTALL AN ADDITIONAL BATTERY BACK
 LIGHT OF SOME KIND IN NEW LARGE CLASSROOM PER NFPA-101
 7.8, 7.9
 ** CIRCUIT PER 700.12E OF THE 2002 NEC/700.12F OF THE
 2005 NEC TO A LOCAL BRANCH LIGHTING CIRCUIT.
 ** OTHER EXIT AND EMERGENCY LIGHTING FIXTURES TO VERIFY
 CIRCUITING.
  
 2) NOTE: PLEASE SUBMIT DETAILS AND TYPE OF SPECIFIC
 OCCUPANCY DEVICES PER 13-415.1.ABC.1.1. THIS WAS ONLY
 STATED IN A NOTE ON PLANS. NEED DETAIL.
 PLEASE DETERMINE AND INDICATE THE MAXIMUM LIGHTING
 POWER DENSITIES PER 13-415.2, TABLE 13-415.2.C.1, AND
 13-415.2.B.1.
 FBC 106.1, 106.1.2
  
 3) NOTE: PLEASE REVISE CIRCUITING AND LOAD CALCULATIONS
 TO MEET THE MINIMUM PER NEC 220 AND 408.4.
 VERIFY CIRCUITING TO RECEPTACLES AND LIGHTING AS
 SHOWN.
 PLEASE SEE LOAD FOR LIGHTING IS UNCLEAR.
  
 *** PLEASE CALL TO GO OVER ANY OF THESE COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-27 Cont ID  
Sent By dpalmer Date 2007-07-27 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2007-07-27 Time 09:25 Sent To  
Notes
2007-07-27 12:15:41 
 *** UNSATREVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 REMAIN AND PLEASE SEE THERE ARE NEW COMMENTS BASED ON
 CHANGES MADE TO THE PLANS.
  
  
 1) NOTE: PLEASE SEE THE SCOPE OF WORK SEEMS TO HAVE
 BEEN REDUCED HOWEVER THE CIRCUITING NOW SHOWN ON PLANS
 DOES NOT CORRELATE WITH EITHER OF THE PANEL SCHEDULES
 PROVIDED.
 PLEASE SEE THERE ARE 120V RECEPTACLE CIRCUITS SHOWN TO
 AIR CONDITIONING 220V LOADS. PLEASE SEE OTHER ROOMS AND
 AREAS WHICH DO NOT CORRELATE.
 PLEASE SEE PANEL SCHEDULE NOW SHOWS 20AMP SUB PANEL
 FEED.
 PLEASE VERIFY RISER AND ALL PANELS.
 FBC 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 ETC.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW A *PROVISO* WAS
 GIVEN TO HAVE CORRECTIONS MADE TO PLANS IF THEY ARE
 REJECTED BY ANY OTHER TRADES FOR LIGHTING CONTROLS AS
 REQUIRED PER 13-415.1.ABC.1.1 AND .1.2.
 PLEASE SEE THE NEW LIGHTING CONTROLS NEED TO BE SHOWN.
 13-101
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-24 Cont ID  
Sent By dpalmer Date 2007-03-24 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 14:31 Sent To  
Notes
2007-03-24 15:12:10** PROVISO **
  
 1) NOTE: PLEASE SEE NEW CLASSROOMS WITH NEW LIGHTING
 AND NEW LIGHTING CONTROLS SHALL MEET FBC 2004 CHAPTER
 13.
 PLEASE SEE 13-415.1.ABC.1.1, AND .1.2 AS AUTOMATED
 CONTROLS FOR NEW LIGHTING IN THESE ROOMS IS REQUIRED.
 THIS CAN BE ACCOMPLISHED BY THE USE OF WALL CONTROL
 OCCUPANCY SENSORS WHICH WILL STAY ON FOR NO MORE THAN
 30MINS AFTER THE LAST SENSING OF THE OCCUPANT. THIS WAS
 CONFIRMED WITH THE FLORIDA BUILDING COMMISSION SINCE
 THE LAST REVIEW THAT NEW INSTALLATIONS REGARDLESS OF
 THE TOTAL AMOUNT OF SPACE BEING RENOVATED STILL
 REQUIRES CONTROLS FOR NEW. THIS WOULD INCLUDE THE FIVE
 NEW CLASSROOMS, NEW MEN?S, WOMEN?S AND STAFF
 BATHROOMS.
 **PLEASE SUBMIT REVISED PLANS BEFORE ROUGH ELECTRICAL
 INSPECTION FOR REVIEW, STAMPING AND TO BE BACK ON THE
 SITE FOR INSPECTOR.
  
  
 ** IF PLANS ARE RETURNED FOR ANY CORRECTIONS FROM OTHER
 TRADES, PLEASE CORRECT.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE
 IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By dpalmer Date 2006-11-22 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2006-11-22 Time 14:32 Sent To  
Notes
2006-11-22 16:42:44***** UNSAT 2ND REVIEW *******
  
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND
 SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED
 OF ADDRESSING.
  
  
 1) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES NOW BEING SUBMITTED.
 PLEASE SEE CIRCUITS ARE NOTED WITH A NUMERICAL
 DESIGNATION ONLY AND NOTHING TO A PANEL LETTER OR
 NUMBER.
 PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH DO NOT
 MATCH WITH EITHER OF THE PANEL SCHEDULES.
 PLEASE SEE THE INSTA-HOT WHICH IS BEING SHOWN ON
 CIRCUIT 18/20 ON PANEL #1, HOWEVER PLANS INDICATE
 CIRCUIT # 36/38?
 PLEASE SEE OTHER CIRCUITS WHICH ARE BEING SHOWN AS
 EXISTING ON PANEL SCHEDULES; HOWEVER THESE ARE IN AREAS
 WHICH ARE NEW.
 PLEASE SEE SOME OTHER ELECTRICAL DEVICES/FIXTURES ON
 PLANS WHICH CONTAIN NO CIRCUITING.
 408.4, 310.16, ETC
 FBC 106.1.2 ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
 PREVIOUSLY NOTED.
  
 2) NOTE: PLEASE SEE 700.12E FOR THE CIRCUITING OF THE
 EXIT AND EMERGENCY LIGHTS AS REQUIRED.
 PLEASE SEE THAT THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
  
 3) NOTE: PLEASE SHOW ALL MINIMUM CONDUCTOR SIZES ON
 PANEL SCHEDULES FOR CIRCUITS AS SHOWN BASED ON
 240.4,310.16, 220.19-220.24
 PLEASE SEE RESPONSE LETTER MENTIONS THIS IS DONE ON
 PLANS, HOWEVER NONE OF THESE WERE LOCATED ON PANEL
 SCHEDULES. UNABLE TO VERIFY COORDINATION OF ANY OVER
 CURRENT PROTECTIVE DEVICES AND CONDUCTOR SIZES AT THIS
 TIME.
 PREVIOUSLY NOTED.
  
 4) NOTE: PLEASE INDICATE THE CURRENT CODES RELEVANT AND
 IN EFFECT FOR SAID PROJECT AS PREVIOUSLY REQUESTED.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
  
 5) NOTE: PLEASE LOADS ON CIRCUITS SHALL BE SHOWN.
 PLEASE SEE RECEPTACLE CIRCUITS WHICH ARE SUBSTANTIALLY
 OVERLOADED. PLEASE SEE 220.13.
 PLEASE ALSO SEE NEW ADDED LOAD FOR TANK-LESS WATER
 HEATER WHICH IS NOT SHOWN IN ANY CALCULATIONS.
 PLEASE SUBMIT CALCULATIONS AND THE ACTUAL SIZE OF THE
 EXISTING SERVICE, NOT ONLY THE PANEL SIZES.
 PLEASE SEE 220.3,220.10,220.11,220.13,AND 215.3,
 230.42 FOR CONTINUOUS LOADS.
 PLEASE SEE FBC ADMIN SECT. 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE PANEL #1 AND #2 ARE BEING NOTED AS
 GOING DIRECTLY TO THE EXISTING METER, HOWEVER IF THESE
 CONTAIN MAINS, THEY ARE NOT GROUPED. PLEASE VERIFY
 THIS.
 230.2, 230.72 ETC.
  
 7) NOTE: PLEASE ALSO SEE A 50A SUB PANEL IS BEING SHOWN
 ON RISER BEING FED FROM PANEL #2 , YET THIS PANEL #3 ON
 THE PANEL SCHEDULE #2 IS BEING FROM TWO SEPARATE SINGLE
 POLE 20A BREAKERS???
 PLEASE VERIFY THIS.
 PLEASE SEE 240.4,310.16,240,ETC.
 THERE ARE TOO MANY CODE SECTIONS TO LIST.
  
 8) NOTE: PLEASE SEE GENERAL NOTES #5. PLEASE SEE THIS
 DOES NOT SEEM TO BE ACCURATE FOR THE WORK BEING DONE ON
 THIS PROJECT.
 FBC 106.1.2,NEC 310.16.
  
 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED AND ONE SET OF RED-LINED PLANS WILL GO BACK TO
 CONTRACTOR ONCE ALL REVIEWS ARE DONE.
  
 10) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS /CUT
 SHEETS FOR THE NEW TANK LESS WATER HEATER. PLEASE KNOW
 THIS MUST CONTAIN A LISTING FROM A NRTL. (NATIONALLY
 RECOGNIZED TESTING LABORATORY).
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED, PLEASE KNOW THERE MAY BE COMMENTSON NEXT
 REVIEW.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 18:06 Sent To  
Notes
2006-09-07 00:00:00*** UNSAT **
  
 1) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS FOR NEW ELECTRICAL. PLEASE
 CORRELATE WITH A NEW REVISED PANEL
 SCHEDULE TO BE PROVIDED.
 FBC 106.1.2,240.4,310.16
 PLEASE BE SURE TO INDICATE THE CONDUCTOR
 SIZES, OCP ETC.
  
 2) NOTE: PLEASE CLARIFY IF THIS IS A NEW
 USE FOR EDUCATION ? OCCUPANT LOAD,?
 PLACE OF ASSEMBLY?
 FBC 106.1, NFPA-70, ETC.
  
 3) NOTE: PLEASE BE SURE THE PLANS STATE
 THE MIN CODES AS REQUIRED , 2004 FBC,
 2002 NFPA-70, 2002 NFPA-72, AND 2003
 NFPA-101.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By mwennerg Date 2007-08-06 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2007-08-06 Time 14:37 Sent To  
Notes
2007-08-06 14:38:56***PROVISO***
  
 TAKEN FROM LAST FIRE PLAN REVIEW:
  
 1) THE APPROPRIATE PLAN SHEET(S) TO BE STAMPED WHEN
 OTHER REVIEWS HAVE BEEN SATIFIED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 15:52 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 15:04 Sent To  
Notes
2007-04-12 15:28:00*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE STAMPED WHEN OTHER
 REVIEWS HAVE BEEN SATISFIED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By mawillia Date 2006-09-08 Time 14:50 Rev Time 0.00
Received By mawillia Date 2006-09-08 Time 13:06 Sent To  
Notes
2006-09-08 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) EXITS AND(OR) EXIT ACCESS CORRIDORS
 SHALL REMAIN CLEAR AND UNOBSTRUCTED.
  
 4.) PLEASE INDICATE/DISPLAY/SHOW FIRE
 PROTECTION SYSTEMS (I.E. FIRE ALARM,
 SPRINKLER SYSTEM) ON THE EXIST/NEW FLOOR
 PLAN. HOW WILL THE SCOPE OF WORK AFFECT
 THESE SYSTEMS?
  
 5.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE PROTECTION SYSTEM, PROVIDE SEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS FOR
 REVIEW.
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-05 Cont ID  
Sent By wlehnhar Date 2007-09-05 Time   Rev Time 0.00
Received By wlehnhar Date 2007-09-05 Time   Sent To E
Notes
2007-09-05 14:56:35ROUTED TO BILL TROBAUGH PER L MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 11:07 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 11:07 Sent To  
Notes
2007-07-27 08:25:51TO "BOB"#16
2007-07-16 11:08:15WAITING FOR "BOB" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 12:41 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 12:41 Sent To  
Notes
2007-03-24 12:41:29TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 14:01 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 14:01 Sent To  
Notes
2006-11-22 14:32:31TO BOB BOARD #9
2006-11-12 14:02:07WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-09-08 Time   Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 12:52 Sent To  
Notes
2006-09-06 00:00:00TO "BOB"#6
2006-08-26 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 10:00 Rev Time 0.20
Received By tgordon Date 2007-09-12 Time 10:00 Sent To  
Notes
2007-09-12 10:01:36FOR BATHROOM EXHAUST FAN ONLY.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-09-12 Cont ID  
Sent By jleech Date 2007-09-12 Time 09:40 Rev Time 0.00
Received By jleech Date 2007-09-12 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-08-08 Cont ID  
Sent By jleech Date 2007-08-08 Time 09:45 Rev Time 0.00
Received By jleech Date 2007-08-08 Time 09:45 Sent To  
Notes
2007-08-08 09:51:06DENIED;
 IF OCCUPANCY GROUP CHANGES FROM "B" TO "E" A SERVIC
 SINK IS REQUIRED, NOT SHOWN ON DRAWINGS. ALSO ON PAGE
 P-1 "PLUMBING FIXTURE CALCULATIONS", ARE NOT CORRECT.
 PLEASE CORRECT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 16:07 Rev Time 0.00
Received By kstevens Date 2007-04-09 Time 16:07 Sent To  
Notes
2007-04-09 16:43:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.3.
 ****COMMENT NOT ADDRESSED FOR THE NEW STAFF BATHROOM.
 THIS SHALL BE SHOWN ON ALL SHEETS, NOT JUST THE
 ARCHITECTURAL.
  
 3. SUBMIT A DETAIL FOR THE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 __FOR THE W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE. THIS SHALL BE SHOWN
 FOR THE W/C'S ON THE FLOOR PLAN OF EACH ROOM.
 B. 11-4.16.4 GRAB BARS. THE SECTION THRU BATHROOM
 INDICATES THE SIDE GRAB BAR AS 2'0". THE REQUIRED
 LENGTH IS 42" SEE FIG 29.
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 __FOR THE URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 __FOR THE LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE. SHOW IN EACH TOILET
 ROOM AND THE NEW BATHROOM.
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 __FOR THE SHOWER:
 A. 11-4.21.2 SIZE AND CLEARANCE
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 NOTE: ELEVATIONS FOR THE FIXTURES MAY BE REQUIRED TO
 INDICATE ALL CODE REQUIREMENTS. W/C'S SHALL BE SHOWN
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, AND
 THE LAVS SHALL BE SHOWN 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURES FOR EACH TOILET ROOM. SEE
 FIGS. 28, 35B & 37B.
  
 4. SUBMIT A DETAIL FOR THE NEW BATHROOM.
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS.
 ****NOT COMPLETLY ADDRESSED. SEE COMMENT #3.-THE
 TOILET SHALL BE SHOWN 18" OFF THE SHOWER OR LAV AND 15"
 OFF THE OTHER FIXTURE WITH A MINIMUM 33" OPENING
 BETWEEN THE LAV AND SHOWER.
  
 5. OK
 6. OK
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, TRAPS, VENTS ETC.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE URINAL
 WASTE LINE CONNECTING TO THE BRANCH LINE PRIOR TO THE
 W/C'S AND LAVS, BUT THE RISER SHOWS THE URINAL
 CONNECTING UPSTREAM OF THE LAST W/C. (SEE EXAMPLE ON
 ONE P-1 SHEET).
  
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, VALVES, WATER
 HAMMER ARRESTORS (IF REQUIRED BY SECTION
 604.9). SECTION 106.1.1 AND SECTION 606. ****RESPONSE
 NOTED, BUT THE PIPE SIZING IS NOT SUFFICIENT. ALL STUB
 OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT THE URINAL 3/4".
 THE URINAL IS NOT EVEN SHOWN ON THE WATER RISER
 DIAGRAM. SEE TABLES 603.1 & 709.1. SERVICE TO THE UNIT
 SHOULD BE 1" AND A SHUT OFF VALVE IS ALSO REQUIRED ON
 THE SERVICE TO THE UNIT. PLEASE INDICATE ON PLANS.
  
 ********NEW COMMENT********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A
 NOTICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 06:57 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 06:57 Sent To  
Notes
2006-12-09 07:25:18DENIED;
 SEE SOME NOTES FROM 1ST REVIEW WERE NOT ADDREESED;
 1. OK
 2. NO; DID NOT CHANGE DOOR SWING ON PAGE P-1.
 3. NO; DETAIL NOT SHOWN FOR HANDICAP TOILET ROOMS, AND
 NEW STAFF BATH, THAT IS REQUIRED TO BE HANDICAPED.
 SECTION 11-4.1.3(11). ALSO SHOW A DETAIL OF URINAL,
 TURNING RADIUS AND CLEAR FLOOR SPACE ON DRAWINGS.
 4. NO; SEE NOTE 3. COMPLIANCE TO SECTIONS 11-4.16,
 11-4.18, 11-4.19 AND 11-4.22 ARE NOT SHOWN.
 5. NO; OCCUPANCY SHOULD BE EDUCATIONAL, ONE SEVICE SINK
 IS REQUIRED TABLE 403.1 SECTION 3 E/D.
 6. OK
 7. OK WITH CHANGES SEE ONE SET OF PLANS MARKED IN RED.
 8. WATER RISER SUBMITED BUT DOES NOT MEET CODE. ALL
 STUB OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT URINAL 3/4"
 REQUIRED. PIPE SIZING IS INCORRECT. SEE TABLES 603.1
 AND 709.1. SEVICE TO UNIT SHOULD BE 1". A SHUTOFF VALVE
 IS ALSO REQUIRED ON SERVICE TO UNIT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 16:46 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 16:46 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 TOILET ROOMS ARE NOT WIDE
 ENOUGH. MINIMUM 5'3" REQUIRED FOR
 ACCESSIBLE TOILET ROOMS.
  
 2. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SECTION 11-4.22.3
  
 3. SUBMIT A DETAIL FOR THE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
  
 4. SUBMIT A DETAIL FOR THE NEW BATHROOM.
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM
 PLUMBING FIXTURES PER TABLES 1004.1.2
 AND 401.3. INDICATE OCCUPANCY. INDICATE
 AGE AND NUMBER OF STUDENTS.
  
 6. DEMOLITION NOTES ON SHT A-1 INDICATES
 THE CAPING OFF OF PLUMBING. THIS IS NOT
 INDICATED ON THE FLOOR PLAN. PLEASE
 INDICATE WHERE THE PLUMBING PIPES WILL
 BE CAPPED OFF AND BE AWARE THAT DEAD
 ENDS ARE PROHIBITED PER SECTION 704.5.
  
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, TRAPS, VENTS ETC.
 SECTION 106.1.1.
  
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, VALVES, WATER
 HAMMER ARRESTORS (IF REQUIRED BY SECTION
 604.9). SECTION 106.1.1 AND SECTION 606.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By choops Date 2007-07-30 Time 17:49 Rev Time 0.00
Received By choops Date 2007-07-30 Time 17:49 Sent To  
Notes
2007-07-30 17:49:44*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved