Plan Review Stops For Permit 06081920 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2007-09-13 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2007-09-13 |
Time |
12:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-07-30 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-07-30 |
Time |
11:18 |
Sent To |
|
|
Notes |
2007-07-30 12:10:23 | PERMIT: 06081920 | | ADD: 1750 N. FLORIDA MANGO RD. #302 | | CONT: BILL MARTIN RENAVATIONS INC. | | TEL: (561)863-8227 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 4TH | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)OK | | | | 3)OK | | | | 4) OK | | | | 5)OK | | | | 6)OK | | | | THE PLANS SHALL BE DESIGNED TO THE 2004 FLORIDA | | BUILDING CODE WITH THE 2006 REVISIONS. | | NEW***** | | A)THE OCCUPANCY GROUP INDICATED ON THE PLANS ARE | | INCORRECT. FBC 305.1GROUP 'E'THE USE OF A BUILDING | | OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE | | PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES | | THROUGH THE 12TH GRADE.SEE FBC 304.1 GROUP 'B' . FOR | | THE OCCUPANCIES WHICH INCLUDE EDUCATIONAL OCCUPANCIES | | ABOVE THE 12TH GRADE. | | | | B)SUBMIT A DOOR SCHEDULE AND A FINISH SCHEDULE FOR | | EACH ROOM LISTING THE TYPE OF MATERIAL FOR THE | | FLOORS/WALLS AND CEILINGS ETC. NOTE: FBC 1210.2 WALLS | | WITHIN 2 FEET OF UNIRALS AND WATERCLOSETS SHALL HAVE A | | SMOOTH "HARD", NON ABSORBENT SURFACE TO A HEIGHT 4 FEET | | ABOVE THE FLOOR. *****PAINT IS NOT A "HARD" | | SURFACE!!!! | | | | C)THE EXISTING WALL AND THE NEW WALL HAS THE SAME | | TYPE OF SYMBOL. THESE WALL SHALL HAVE DIFFERENT | | SYMBOLS. | | | | D)FBC.803.5INTERIOR WALL AND CEILINGFINISH SHALL | | HAVE A FLAME SPREAD INDEX NOT GREATER THAN THAT | | SPECIFIED IN TABLE 803.5. SHOW THIS INFORMATION ON THE | | FINISH SCHEDULE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
18:46 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-03-30 |
Time |
17:00 |
Sent To |
|
|
Notes |
2007-03-30 17:32:05 | BUILDING PLAN REVIEW | | PERMIT: 06081920 | | ADD: 1750 N. FLORIDA MANGO RD. #302 | | CONT: BILL MARTIN RENAVATIONS INC. | | TEL: (561)863-8227 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 3RD | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)THE INFORMATION SUBMITTED FOR THE HEAD + FLOOR | | DETAIL SHALL INDICATEHOW OR WHAT THE BLOCKING WILL BE | | ATTATCHED TO AND THE MATERIALS USED TO SECURE IT. WILL | | THE BLOCKING BE ATTATCHED TO THE CEILING OR THE | | STRUCTURE ABOVE? AND WHAT IS THE ROOF STRUCTURE?. SEE | | NOTE #2 FROM PREVIOUS REVIEW. | | | | 3)THE INFORMATION FOR THE PARTITION WAS NOT | | RESUBMITTED. THE POCKET DOORS SHOWN ON THE DETAIL FOR | | THE MOVEABLE PARTIONS ARE NOT INDICATED ON THE | | DRAWINGS. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | THE WORK PROSED AND SHOW IN DETAIL THAT IT WILL CONFORM | | TO THE CODE.PLEASE SEE NOTES FROM LAST REVIEW WERE | | NOT ADDRESSED. | | | | 4) SHOW THE CLEAR FLOOR SPACE FOR THE TOILET AND | | BATHROOMS COMPLYING WITH SECTIONS 11-4.16,11-4.19, | | FIG. 28 AND 30E. | | | | 5)NOTE FROM FIRST REVIEW (2)FBC. 11-4.22.2 ALL | | DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH SEC. | | 11-4.13 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR | | SPACE REQUIRED FOR ANY FIXTURE. SEE NEW STAFF | | BATH/MEN'S AND WOMEN'S TOILETS. | | | | 6)SHEET A-1. THE OCCUPANT LOAD INDICATED IS | | INCORRECT. CLARIFY.AND SEE FBC. 1004. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
17:59 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-12-07 |
Time |
15:03 |
Sent To |
|
|
Notes |
2006-12-07 16:57:43 | BUILDING PLAN REVIEW | | PERMIT:06081920 | | ADD:1750 N. FLORIDA MANGO RD #302 | | CONT: BILL MARTIN RENAVATIONS INC. | | TEL: (561)863-8227 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW : 2ND | | ACTION: DENIED | | | | 1) 110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED.------------------- | | ) NUMBER OF FLOORS | | ) NUMBER OF ROOMS | | ) SQ. FT. FOOTPRINT | | ) SQ. FT. UNDER ROOF (TOTAL) | | | | | | 2)W.P.B.AMENDMENTS. 106.1.2THE BUILDING OFFICIAL | | MAY REQUIRE DETAILS, COMPUTATUONS, STRESS DIAGRAMS, AND | | OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR | | INSTALLATION AND THE BASIS OF CALCULATIONS.MORE | | INFORMATION IS NEEDED FOR THE INSTALLATION OF THE | | MOVABLEPARTITIONS.A DETAIL DRAWING INDICATING ALL | | THE MATERIALS WHICH WILL BE USED TO HOLD THE PARTITIONS | | IN PLACE SHALL BE SUBMITTED TO OUR OFFICE. WHAT IS THE | | STRUCTURE ABOVE THE CEILING? IS IT WOOD | | JOIST/CONCRETE/BAR-JOIST OR LIGHT WEIGHT CONCRETE? | | | | 3) WHAT TYPE OF FINISH WILL BE ON THE PARTITIONS? THERE | | ARE FOUR OR FIVE DIFFEREND TYPES OF FINISH MENTION IN | | THE BROCHURE INDICATE WHICH ONE WILL BE USED ON THE | | DRAWINGS. THE POCKET FOR THE MOVABLE PATIONS ON THE | | DRAWINGS, DONOT MATCH THE ONES ON THE BROCHURE. CLARIFY | | THIS INFORMATION. SHOW THE CONTINUOS HEADER DETAIL FOR | | THE TOP TRACK. | | | | 4)FBC. 805.2WHERE REQUIRED TO BE FLAME RESISTANT, | | DECORATIVE MATERIALS SHALL BE TESTED BY AN APPROVED | | AGENCY AND PASS TEST 1 OR 2, AS APPROPRIATE,DESCRIBED | | IN NFPA 701 OR SUCH MATERIALS SHALL BE NONCOMBUSTIBLE. | | REPORTS OF TEST RESULTS SHALL BE PREPARED IN ACCORDANCE | | WITH NFPA 701 AND FURNISHED TO THE CODE OFFICIAL UPON | | REQUEST. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-09-08 |
Time |
18:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-09-08 |
Time |
17:20 |
Sent To |
PC |
|
Notes |
2006-09-08 00:00:00 | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, | | INFORMATION THAT IS REQUIRED FOR RECORD | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | ------------------------------------- | | ) NUMBER OF FLOORS | | ) NUMBER OF ROOMS | | ) SQ. FT. FOOTPRINT | | ) SQ. FT. UNDER ROOF (TOTAL) | | ) OCCUPANT LOAD | | ) FLOOD ZONE | | ) FLOOD ELEVATION | | ) L.O.M.R. | | | | 2) 11-4.22.2 | | ALL DOOS TO ACCESSIBLE TOILET ROOMS | | SHALL COMPLY WITH SECTION 11-4.13. DOORS | | SHALL NOT SWING INTO THE CLEAR FLOOR | | SPACE REQUIRED FOR ANY FIXTURE. | | | | 3) SUBMIT A DETAIL DRAWING FOR THE NEW | | MOVEABLE PARTIONS SHOWING THE CONNECTION | | TO THE CEILING AND HOW THE WILL BE HELD | | IN A CLOSED POSITION. SUBMIT THE PRODUCT | | APPROVALS OR THE MANUFACTURE SPECTS | | SHEETS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-11 |
Time |
18:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-11 |
Time |
18:07 |
Sent To |
B |
|
Notes |
2007-09-11 18:08:15 | *** PROVISO*** | | | | 1) NOTE: PLEASE INSTALL AN ADDITIONAL BATTERY BACK | | LIGHT OF SOME KIND IN NEW LARGE CLASSROOM PER NFPA-101 | | 7.8, 7.9 | | ** CIRCUIT PER 700.12E OF THE 2002 NEC/700.12F OF THE | | 2005 NEC TO A LOCAL BRANCH LIGHTING CIRCUIT. | | ** OTHER EXIT AND EMERGENCY LIGHTING FIXTURES TO VERIFY | | CIRCUITING. | | | | 2) NOTE: PLEASE SUBMIT DETAILS AND TYPE OF SPECIFIC | | OCCUPANCY DEVICES PER 13-415.1.ABC.1.1. THIS WAS ONLY | | STATED IN A NOTE ON PLANS. NEED DETAIL. | | PLEASE DETERMINE AND INDICATE THE MAXIMUM LIGHTING | | POWER DENSITIES PER 13-415.2, TABLE 13-415.2.C.1, AND | | 13-415.2.B.1. | | FBC 106.1, 106.1.2 | | | | 3) NOTE: PLEASE REVISE CIRCUITING AND LOAD CALCULATIONS | | TO MEET THE MINIMUM PER NEC 220 AND 408.4. | | VERIFY CIRCUITING TO RECEPTACLES AND LIGHTING AS | | SHOWN. | | PLEASE SEE LOAD FOR LIGHTING IS UNCLEAR. | | | | *** PLEASE CALL TO GO OVER ANY OF THESE COMMENTS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-07-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-27 |
Time |
12:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-27 |
Time |
09:25 |
Sent To |
|
|
Notes |
2007-07-27 12:15:41 | | | *** UNSATREVIEW *** | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL | | REMAIN AND PLEASE SEE THERE ARE NEW COMMENTS BASED ON | | CHANGES MADE TO THE PLANS. | | | | | | 1) NOTE: PLEASE SEE THE SCOPE OF WORK SEEMS TO HAVE | | BEEN REDUCED HOWEVER THE CIRCUITING NOW SHOWN ON PLANS | | DOES NOT CORRELATE WITH EITHER OF THE PANEL SCHEDULES | | PROVIDED. | | PLEASE SEE THERE ARE 120V RECEPTACLE CIRCUITS SHOWN TO | | AIR CONDITIONING 220V LOADS. PLEASE SEE OTHER ROOMS AND | | AREAS WHICH DO NOT CORRELATE. | | PLEASE SEE PANEL SCHEDULE NOW SHOWS 20AMP SUB PANEL | | FEED. | | PLEASE VERIFY RISER AND ALL PANELS. | | FBC 106.3.5.1.2 | | NEC 408.4, 310.16, 240.4 ETC. | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW A *PROVISO* WAS | | GIVEN TO HAVE CORRECTIONS MADE TO PLANS IF THEY ARE | | REJECTED BY ANY OTHER TRADES FOR LIGHTING CONTROLS AS | | REQUIRED PER 13-415.1.ABC.1.1 AND .1.2. | | PLEASE SEE THE NEW LIGHTING CONTROLS NEED TO BE SHOWN. | | 13-101 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-24 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-24 |
Time |
14:31 |
Sent To |
|
|
Notes |
2007-03-24 15:12:10 | ** PROVISO ** | | | | 1) NOTE: PLEASE SEE NEW CLASSROOMS WITH NEW LIGHTING | | AND NEW LIGHTING CONTROLS SHALL MEET FBC 2004 CHAPTER | | 13. | | PLEASE SEE 13-415.1.ABC.1.1, AND .1.2 AS AUTOMATED | | CONTROLS FOR NEW LIGHTING IN THESE ROOMS IS REQUIRED. | | THIS CAN BE ACCOMPLISHED BY THE USE OF WALL CONTROL | | OCCUPANCY SENSORS WHICH WILL STAY ON FOR NO MORE THAN | | 30MINS AFTER THE LAST SENSING OF THE OCCUPANT. THIS WAS | | CONFIRMED WITH THE FLORIDA BUILDING COMMISSION SINCE | | THE LAST REVIEW THAT NEW INSTALLATIONS REGARDLESS OF | | THE TOTAL AMOUNT OF SPACE BEING RENOVATED STILL | | REQUIRES CONTROLS FOR NEW. THIS WOULD INCLUDE THE FIVE | | NEW CLASSROOMS, NEW MEN?S, WOMEN?S AND STAFF | | BATHROOMS. | | **PLEASE SUBMIT REVISED PLANS BEFORE ROUGH ELECTRICAL | | INSPECTION FOR REVIEW, STAMPING AND TO BE BACK ON THE | | SITE FOR INSPECTOR. | | | | | | ** IF PLANS ARE RETURNED FOR ANY CORRECTIONS FROM OTHER | | TRADES, PLEASE CORRECT. | | | | ** IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE | | IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-11-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-22 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-22 |
Time |
14:32 |
Sent To |
|
|
Notes |
2006-11-22 16:42:44 | ***** UNSAT 2ND REVIEW ******* | | | | | | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW AND | | SOME NEW NOTES BASED ON NEW PLANS SUBMITTED ARE IN NEED | | OF ADDRESSING. | | | | | | 1) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND | | CORRELATE WITH THE PANEL SCHEDULES NOW BEING SUBMITTED. | | PLEASE SEE CIRCUITS ARE NOTED WITH A NUMERICAL | | DESIGNATION ONLY AND NOTHING TO A PANEL LETTER OR | | NUMBER. | | PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH DO NOT | | MATCH WITH EITHER OF THE PANEL SCHEDULES. | | PLEASE SEE THE INSTA-HOT WHICH IS BEING SHOWN ON | | CIRCUIT 18/20 ON PANEL #1, HOWEVER PLANS INDICATE | | CIRCUIT # 36/38? | | PLEASE SEE OTHER CIRCUITS WHICH ARE BEING SHOWN AS | | EXISTING ON PANEL SCHEDULES; HOWEVER THESE ARE IN AREAS | | WHICH ARE NEW. | | PLEASE SEE SOME OTHER ELECTRICAL DEVICES/FIXTURES ON | | PLANS WHICH CONTAIN NO CIRCUITING. | | 408.4, 310.16, ETC | | FBC 106.1.2 ADMINISTRATIVE SECTION AS ADOPTED BY THE | | CITY OF WEST PALM BEACH. | | PREVIOUSLY NOTED. | | | | 2) NOTE: PLEASE SEE 700.12E FOR THE CIRCUITING OF THE | | EXIT AND EMERGENCY LIGHTS AS REQUIRED. | | PLEASE SEE THAT THE BRANCH CIRCUIT FEEDING THE UNIT | | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | AHEAD OF ANY LOCAL SWITCHES. | | | | 3) NOTE: PLEASE SHOW ALL MINIMUM CONDUCTOR SIZES ON | | PANEL SCHEDULES FOR CIRCUITS AS SHOWN BASED ON | | 240.4,310.16, 220.19-220.24 | | PLEASE SEE RESPONSE LETTER MENTIONS THIS IS DONE ON | | PLANS, HOWEVER NONE OF THESE WERE LOCATED ON PANEL | | SCHEDULES. UNABLE TO VERIFY COORDINATION OF ANY OVER | | CURRENT PROTECTIVE DEVICES AND CONDUCTOR SIZES AT THIS | | TIME. | | PREVIOUSLY NOTED. | | | | 4) NOTE: PLEASE INDICATE THE CURRENT CODES RELEVANT AND | | IN EFFECT FOR SAID PROJECT AS PREVIOUSLY REQUESTED. | | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101. | | | | 5) NOTE: PLEASE LOADS ON CIRCUITS SHALL BE SHOWN. | | PLEASE SEE RECEPTACLE CIRCUITS WHICH ARE SUBSTANTIALLY | | OVERLOADED. PLEASE SEE 220.13. | | PLEASE ALSO SEE NEW ADDED LOAD FOR TANK-LESS WATER | | HEATER WHICH IS NOT SHOWN IN ANY CALCULATIONS. | | PLEASE SUBMIT CALCULATIONS AND THE ACTUAL SIZE OF THE | | EXISTING SERVICE, NOT ONLY THE PANEL SIZES. | | PLEASE SEE 220.3,220.10,220.11,220.13,AND 215.3, | | 230.42 FOR CONTINUOUS LOADS. | | PLEASE SEE FBC ADMIN SECT. 106.3.5.1.2, 106.1.2 | | | | 6) NOTE: PLEASE SEE PANEL #1 AND #2 ARE BEING NOTED AS | | GOING DIRECTLY TO THE EXISTING METER, HOWEVER IF THESE | | CONTAIN MAINS, THEY ARE NOT GROUPED. PLEASE VERIFY | | THIS. | | 230.2, 230.72 ETC. | | | | 7) NOTE: PLEASE ALSO SEE A 50A SUB PANEL IS BEING SHOWN | | ON RISER BEING FED FROM PANEL #2 , YET THIS PANEL #3 ON | | THE PANEL SCHEDULE #2 IS BEING FROM TWO SEPARATE SINGLE | | POLE 20A BREAKERS??? | | PLEASE VERIFY THIS. | | PLEASE SEE 240.4,310.16,240,ETC. | | THERE ARE TOO MANY CODE SECTIONS TO LIST. | | | | 8) NOTE: PLEASE SEE GENERAL NOTES #5. PLEASE SEE THIS | | DOES NOT SEEM TO BE ACCURATE FOR THE WORK BEING DONE ON | | THIS PROJECT. | | FBC 106.1.2,NEC 310.16. | | | | 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH | | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. | | PLEASE KNOW ONE COPY OF ELECTRICAL PLANS ARE BEING | | RETAINED AND ONE SET OF RED-LINED PLANS WILL GO BACK TO | | CONTRACTOR ONCE ALL REVIEWS ARE DONE. | | | | 10) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS /CUT | | SHEETS FOR THE NEW TANK LESS WATER HEATER. PLEASE KNOW | | THIS MUST CONTAIN A LISTING FROM A NRTL. (NATIONALLY | | RECOGNIZED TESTING LABORATORY). | | | | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN | | SUBMITTED, PLEASE KNOW THERE MAY BE COMMENTSON NEXT | | REVIEW. | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF | | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE | | DO NOT HESITATEIN CONTACTING THIS REVIEWER. | | | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-07 |
Time |
18:18 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-07 |
Time |
18:06 |
Sent To |
|
|
Notes |
2006-09-07 00:00:00 | *** UNSAT ** | | | | 1) NOTE: PLEASE INDICATE ALL CIRCUITING | | ON PLANS FOR NEW ELECTRICAL. PLEASE | | CORRELATE WITH A NEW REVISED PANEL | | SCHEDULE TO BE PROVIDED. | | FBC 106.1.2,240.4,310.16 | | PLEASE BE SURE TO INDICATE THE CONDUCTOR | | SIZES, OCP ETC. | | | | 2) NOTE: PLEASE CLARIFY IF THIS IS A NEW | | USE FOR EDUCATION ? OCCUPANT LOAD,? | | PLACE OF ASSEMBLY? | | FBC 106.1, NFPA-70, ETC. | | | | 3) NOTE: PLEASE BE SURE THE PLANS STATE | | THE MIN CODES AS REQUIRED , 2004 FBC, | | 2002 NFPA-70, 2002 NFPA-72, AND 2003 | | NFPA-101. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-08-06 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-08-06 |
Time |
14:37 |
Sent To |
|
|
Notes |
2007-08-06 14:38:56 | ***PROVISO*** | | | | TAKEN FROM LAST FIRE PLAN REVIEW: | | | | 1) THE APPROPRIATE PLAN SHEET(S) TO BE STAMPED WHEN | | OTHER REVIEWS HAVE BEEN SATIFIED. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-12 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-12 |
Time |
15:04 |
Sent To |
|
|
Notes |
2007-04-12 15:28:00 | *****PROVISO***** | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE STAMPED WHEN OTHER | | REVIEWS HAVE BEEN SATISFIED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-09-08 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-09-08 |
Time |
13:06 |
Sent To |
|
|
Notes |
2006-09-08 00:00:00 | *****DENIED***** | | | | | | | | | | 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS | | SHALL COMPLY WITH NFPA 241. | | | | 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE | | MATERIAL AND DUST DEBRIS SHALL BE | | REMOVED FROM THE STRUCTURE AND ITS | | IMMEDIATE VICINITY AT THE END OF EACH | | SHIFT OR MORE FREQUENTLY AS NECESSARY | | FOR SAFE OPERATIONS. | | | | 3.) EXITS AND(OR) EXIT ACCESS CORRIDORS | | SHALL REMAIN CLEAR AND UNOBSTRUCTED. | | | | 4.) PLEASE INDICATE/DISPLAY/SHOW FIRE | | PROTECTION SYSTEMS (I.E. FIRE ALARM, | | SPRINKLER SYSTEM) ON THE EXIST/NEW FLOOR | | PLAN. HOW WILL THE SCOPE OF WORK AFFECT | | THESE SYSTEMS? | | | | 5.) IF THE SCOPE OF THE INTERIOR | | BUILDOUT REQUIRES MODIFICATION OF THE | | FIRE PROTECTION SYSTEM, PROVIDE SEPARATE | | PERMIT AND SHOP DRAWINGS/PLANS FOR | | REVIEW. | | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
wlehnhar |
Date |
2007-09-05 |
Time |
|
Rev Time |
0.00 |
Received By |
wlehnhar |
Date |
2007-09-05 |
Time |
|
Sent To |
E |
|
Notes |
2007-09-05 14:56:35 | ROUTED TO BILL TROBAUGH PER L MARTINEZ |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-16 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-16 |
Time |
11:07 |
Sent To |
|
|
Notes |
2007-07-27 08:25:51 | TO "BOB"#16 | 2007-07-16 11:08:15 | WAITING FOR "BOB" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-24 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-24 |
Time |
12:41 |
Sent To |
|
|
Notes |
2007-03-24 12:41:29 | TO "COMM" BD#9 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-12 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-12 |
Time |
14:01 |
Sent To |
|
|
Notes |
2006-11-22 14:32:31 | TO BOB BOARD #9 | 2006-11-12 14:02:07 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-09-08 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-26 |
Time |
12:52 |
Sent To |
|
|
Notes |
2006-09-06 00:00:00 | TO "BOB"#6 | 2006-08-26 00:00:00 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2007-09-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-12 |
Time |
10:00 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-09-12 |
Time |
10:00 |
Sent To |
|
|
Notes |
2007-09-12 10:01:36 | FOR BATHROOM EXHAUST FAN ONLY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2007-09-12 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-09-12 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-09-12 |
Time |
09:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2007-08-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-08-08 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-08-08 |
Time |
09:45 |
Sent To |
|
|
Notes |
2007-08-08 09:51:06 | DENIED; | | IF OCCUPANCY GROUP CHANGES FROM "B" TO "E" A SERVIC | | SINK IS REQUIRED, NOT SHOWN ON DRAWINGS. ALSO ON PAGE | | P-1 "PLUMBING FIXTURE CALCULATIONS", ARE NOT CORRECT. | | PLEASE CORRECT. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-09 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-09 |
Time |
16:07 |
Sent To |
|
|
Notes |
2007-04-09 16:43:32 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEWS: | | | | 1. OK | | | | 2. DOORS SHALL NOT SWING INTO THE CLEAR | | FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | SECTION 11-4.22.3. | | ****COMMENT NOT ADDRESSED FOR THE NEW STAFF BATHROOM. | | THIS SHALL BE SHOWN ON ALL SHEETS, NOT JUST THE | | ARCHITECTURAL. | | | | 3. SUBMIT A DETAIL FOR THE TOILET ROOMS | | SHOWING COMPLIANCE WITH SECTIONS | | 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND | | ALL SUBSECTIONS. | | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE | | FOLLOWING: | | __FOR THE W/C'S: | | A. 11-4.16.2 CLEAR FLOOR SPACE. THIS SHALL BE SHOWN | | FOR THE W/C'S ON THE FLOOR PLAN OF EACH ROOM. | | B. 11-4.16.4 GRAB BARS. THE SECTION THRU BATHROOM | | INDICATES THE SIDE GRAB BAR AS 2'0". THE REQUIRED | | LENGTH IS 42" SEE FIG 29. | | C. 11-4.16.5 FLUSH CONTROLS | | D. 11-4.16.6 DISPENSERS | | __FOR THE URINAL: | | A. 11-4.18.3 CLEAR FLOOR SPACE | | B. 11-4.18.4 FLUSH CONTROLS | | __FOR THE LAVS: | | A. 11-4.19.2 HEIGHT & CLEARANCES | | B. 11-4.19.3 CLEAR FLOOR SPACE. SHOW IN EACH TOILET | | ROOM AND THE NEW BATHROOM. | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | D. 11-4.19.5 FAUCETS | | E. 11-4.19.6 MIRRORS | | __FOR THE SHOWER: | | A. 11-4.21.2 SIZE AND CLEARANCE | | B. 11-4.21.3 SEAT | | C. 11-4.21.4 GRAB BARS | | D. 11-4.21.5 CONTROLS | | E. 11-4.21.6 SHOWER UNIT | | F. 11-4.21.7 CURBS | | NOTE: ELEVATIONS FOR THE FIXTURES MAY BE REQUIRED TO | | INDICATE ALL CODE REQUIREMENTS. W/C'S SHALL BE SHOWN | | 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE, AND | | THE LAVS SHALL BE SHOWN 15" OFF THE WALL TO THE | | CENTERLINE OF THE FIXTURES FOR EACH TOILET ROOM. SEE | | FIGS. 28, 35B & 37B. | | | | 4. SUBMIT A DETAIL FOR THE NEW BATHROOM. | | SHOW COMPLIANCE WITH SECTIONS 11-4.16, | | 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS. | | ****NOT COMPLETLY ADDRESSED. SEE COMMENT #3.-THE | | TOILET SHALL BE SHOWN 18" OFF THE SHOWER OR LAV AND 15" | | OFF THE OTHER FIXTURE WITH A MINIMUM 33" OPENING | | BETWEEN THE LAV AND SHOWER. | | | | 5. OK | | 6. OK | | | | 7. SUBMIT A SANITARY RISER ISOMETRIC | | DIAGRAM THAT REFLECT THE FLOOR PLAN. | | SHOW ALL PIPE SIZES, TRAPS, VENTS ETC. | | SECTION 106.1.1. | | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE URINAL | | WASTE LINE CONNECTING TO THE BRANCH LINE PRIOR TO THE | | W/C'S AND LAVS, BUT THE RISER SHOWS THE URINAL | | CONNECTING UPSTREAM OF THE LAST W/C. (SEE EXAMPLE ON | | ONE P-1 SHEET). | | | | 8. SUBMIT A WATER RISER ISOMETRIC | | DIAGRAM THAT REFLECT THE FLOOR PLAN. | | SHOW ALL PIPE SIZES, VALVES, WATER | | HAMMER ARRESTORS (IF REQUIRED BY SECTION | | 604.9). SECTION 106.1.1 AND SECTION 606. ****RESPONSE | | NOTED, BUT THE PIPE SIZING IS NOT SUFFICIENT. ALL STUB | | OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT THE URINAL 3/4". | | THE URINAL IS NOT EVEN SHOWN ON THE WATER RISER | | DIAGRAM. SEE TABLES 603.1 & 709.1. SERVICE TO THE UNIT | | SHOULD BE 1" AND A SHUT OFF VALVE IS ALSO REQUIRED ON | | THE SERVICE TO THE UNIT. PLEASE INDICATE ON PLANS. | | | | ********NEW COMMENT******** | | | | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONAL AND FS 533.80(2)(B). THIS IS GIVEN AS A | | NOTICE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-12-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-12-09 |
Time |
06:57 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-12-09 |
Time |
06:57 |
Sent To |
|
|
Notes |
2006-12-09 07:25:18 | DENIED; | | SEE SOME NOTES FROM 1ST REVIEW WERE NOT ADDREESED; | | 1. OK | | 2. NO; DID NOT CHANGE DOOR SWING ON PAGE P-1. | | 3. NO; DETAIL NOT SHOWN FOR HANDICAP TOILET ROOMS, AND | | NEW STAFF BATH, THAT IS REQUIRED TO BE HANDICAPED. | | SECTION 11-4.1.3(11). ALSO SHOW A DETAIL OF URINAL, | | TURNING RADIUS AND CLEAR FLOOR SPACE ON DRAWINGS. | | 4. NO; SEE NOTE 3. COMPLIANCE TO SECTIONS 11-4.16, | | 11-4.18, 11-4.19 AND 11-4.22 ARE NOT SHOWN. | | 5. NO; OCCUPANCY SHOULD BE EDUCATIONAL, ONE SEVICE SINK | | IS REQUIRED TABLE 403.1 SECTION 3 E/D. | | 6. OK | | 7. OK WITH CHANGES SEE ONE SET OF PLANS MARKED IN RED. | | 8. WATER RISER SUBMITED BUT DOES NOT MEET CODE. ALL | | STUB OUTS TO FIXTURES ARE TO BE 1/2" EXCEPT URINAL 3/4" | | REQUIRED. PIPE SIZING IS INCORRECT. SEE TABLES 603.1 | | AND 709.1. SEVICE TO UNIT SHOULD BE 1". A SHUTOFF VALVE | | IS ALSO REQUIRED ON SERVICE TO UNIT. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-09-07 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-09-07 |
Time |
16:46 |
Sent To |
|
|
Notes |
2006-09-07 00:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | | | 1. SHT A-1 TOILET ROOMS ARE NOT WIDE | | ENOUGH. MINIMUM 5'3" REQUIRED FOR | | ACCESSIBLE TOILET ROOMS. | | | | 2. DOORS SHALL NOT SWING INTO THE CLEAR | | FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | SECTION 11-4.22.3 | | | | 3. SUBMIT A DETAIL FOR THE TOILET ROOMS | | SHOWING COMPLIANCE WITH SECTIONS | | 11-4.16, 11-4.18, 11-4.19, 11-4.22 AND | | ALL SUBSECTIONS. | | | | 4. SUBMIT A DETAIL FOR THE NEW BATHROOM. | | SHOW COMPLIANCE WITH SECTIONS 11-4.16, | | 11-4.19, 11-4.21, AND 11-4.22 AND ALL SUBSECTIONS. | | | | 5. SUBMIT CALCULATIONS FOR MINIMUM | | PLUMBING FIXTURES PER TABLES 1004.1.2 | | AND 401.3. INDICATE OCCUPANCY. INDICATE | | AGE AND NUMBER OF STUDENTS. | | | | 6. DEMOLITION NOTES ON SHT A-1 INDICATES | | THE CAPING OFF OF PLUMBING. THIS IS NOT | | INDICATED ON THE FLOOR PLAN. PLEASE | | INDICATE WHERE THE PLUMBING PIPES WILL | | BE CAPPED OFF AND BE AWARE THAT DEAD | | ENDS ARE PROHIBITED PER SECTION 704.5. | | | | 7. SUBMIT A SANITARY RISER ISOMETRIC | | DIAGRAM THAT REFLECT THE FLOOR PLAN. | | SHOW ALL PIPE SIZES, TRAPS, VENTS ETC. | | SECTION 106.1.1. | | | | 8. SUBMIT A WATER RISER ISOMETRIC | | DIAGRAM THAT REFLECT THE FLOOR PLAN. | | SHOW ALL PIPE SIZES, VALVES, WATER | | HAMMER ARRESTORS (IF REQUIRED BY SECTION | | 604.9). SECTION 106.1.1 AND SECTION 606. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-07-30 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-07-30 |
Time |
17:49 |
Sent To |
|
|
Notes |
2007-07-30 17:49:44 | *VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|