Plan Review Details - Permit 06081741
Plan Review Stops For Permit 06081741
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-09-13 Cont ID  
Sent By mperson Date 2006-09-13 Time 09:05 Rev Time 0.33
Received By mperson Date 2006-09-13 Time 09:05 Sent To PC
Notes
2006-09-13 00:00:00 
  
 ******PROVISO******
 A) FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By mperson Date 2006-08-28 Time 09:48 Rev Time 0.55
Received By mperson Date 2006-08-28 Time 09:48 Sent To PC
Notes
2006-08-28 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW FOR A PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE FBC-2004 FUEL GAS SEC.
 402.4.1 LONGEST LENGTH METHOD AND
 402.4.2 BRANCH LENGTH METHOD. THE
 SUBMITTED ISOMETRIC DRAWING IS SIZED
 WRONG. PLEASE REFERENCE CORRECTED
 DRAWING IN RED INK AND ATTACHED SIZING
 TABLES FOR RESUBMITTAL.
  
 4. PLEASE INDICATE THE MAKE AND MODEL
 NUMBER OF THEMP REGULATOR ON THE
 DRAWING.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 17:30 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 17:30 Sent To P
Notes
2006-09-08 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-28 Cont ID  
Sent By mperson Date 2006-08-28 Time 10:21 Rev Time 0.00
Received By mperson Date 2006-08-22 Time 17:07 Sent To  
Notes
2006-08-22 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved