Plan Review Details - Permit 06081700
Plan Review Stops For Permit 06081700
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-11-08 Cont ID  
Sent By mperson Date 2006-11-08 Time 11:45 Rev Time 0.33
Received By mperson Date 2006-11-08 Time 11:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2006-09-28 Cont ID  
Sent By mperson Date 2006-09-28 Time 11:13 Rev Time 0.33
Received By mperson Date 2006-09-28 Time 11:13 Sent To PC
Notes
2006-09-28 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW FROM THE
 PRIVIOUS COMMENTS:
  
 1. (OK)
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS STILL
 NOT AN ISOMETRIC AND DOES NOT CLEARLY
 SHOW ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS. PLEASE REFERENCE
 THE ATTACHED ISOMETIC EXAMPLE FOR
 RESUBMITTAL AND PLEASE INDICATE THE
 ABOVE GROUND PIPE LENGTHS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWING DOES NOT
 INDICATE ALL THE PIPE MATERIALS AND
 SIZES PLEASE INDICATE THE ABOVE GROUND
 PIPE MATERIALS AND SIZES FOR THE
 RESUBMITTAL.
  
 4. (OK)
  
 5. (OK)
  
 6. (OK)
  
 7. (OK)
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: STILL NEED MANUFAFTURER CUT SHEETS
 OF 1ST AND 2ND STAGE REGULATORS.
  
 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: DRAWINGS STILL DON'T HAVE THE
 PRINTED AND SIGNED NAME OF THE PERSON
 TAKING RESPONSIBILITY OF DRAWINGS AND
 THE DATE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By mperson Date 2006-09-12 Time 08:01 Rev Time 0.33
Received By mperson Date 2006-09-12 Time 08:01 Sent To PC
Notes
2006-09-12 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFOMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW FROM THE
 PREVIOUS COMMENTS:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING AND
 ELECTRICAL FOR THE GENERATOR LOCATION.
 NOTE: THERE ARE STILL ISSUES WITH
 ELECTRICAL.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOTE: THE RESUBMITTED
 DRAWING IS NOT AN ISOMETRIC AND DOES NOT
 CLEARLY SHOW ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE RESUBMITTED DRAWING DOES NOT
 INDICATE ALL THE PIPE MATERIALS AND
 SIZES.
  
 4. OK
  
 5. 0K
  
 6. OK
  
 7. OK
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: NEED MANUFACTURER CUT SHEETS OF
 REGULATORS AND GENERATOR. THERE AREN'T
 ANY APPROVED MANUFACTURER SHEETS TO
 VERIFY BTU LOAD OR ISTALLATION
 INSTRUCTIONS TO VERIFY GENERATOR
 PLACEMENT DUE TO THE FACT THE GEN/RES
 PERMIT APPLICATION WAS DENIED AND HAS
 NOT BEEN RESUBMITTED. PLEASE SEE THE
 ATTACHED PERMIT INFORMATION VERIFYING
 THE ABOVE INFORMATION.
  
 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By mperson Date 2006-08-22 Time 15:08 Rev Time 0.33
Received By mperson Date 2006-08-22 Time 15:08 Sent To PC
Notes
2006-08-22 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING FOR A PERMIT:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING AND
 ELECTRICAL FOR THE GENERATOR LOCATION.
 PLEASE SEE ATTACHED ZONING AND
 ELECTRICAL PERMIT PLAN REVIEWS ABOUT
 GENERATOR PERMIT APPLICATION.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 4. TYPE OF GAS, (LP OR NATURAL)
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 PROPANE 10LB PSI.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE:
 NEED MANUFACTURER CUT SHEETS OF
 REGULATORS.)
  
 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 15:54 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 15:54 Sent To P
Notes
2006-11-04 15:54:46TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:03 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:03 Sent To P
Notes
2006-09-23 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 11:18 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 11:18 Sent To P
Notes
2006-09-08 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By mperson Date 2006-08-22 Time 15:25 Rev Time 0.00
Received By mperson Date 2006-08-21 Time 13:07 Sent To  
Notes
2006-08-21 00:00:00TO "G" BOX