Plan Review Details - Permit 06081660
Plan Review Stops For Permit 06081660
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:43 Rev Time 0.00
Received By alange Date 2006-10-23 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-24 Cont ID  
Sent By rnuquist Date 2006-09-24 Time 10:30 Rev Time 0.00
Received By rnuquist Date 2006-09-24 Time 10:30 Sent To  
Notes
2006-09-24 00:00:00ONLY ONE COPY SUBMITTED WITH
 APPLICATION. 2 ARE REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-19 Cont ID  
Sent By btrobaug Date 2006-10-19 Time 17:37 Rev Time 0.33
Received By btrobaug Date 2006-10-19 Time 17:35 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By btrobaug Date 2006-09-01 Time 13:45 Rev Time 0.33
Received By btrobaug Date 2006-09-01 Time 13:44 Sent To M
Notes
2006-09-01 00:00:00 
  
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 2} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By mperson Date 2006-09-06 Time 16:16 Rev Time 0.15
Received By mperson Date 2006-09-06 Time 16:16 Sent To B
Notes
2006-09-06 00:00:00CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION
 (PARTICULARLY THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 13:58 Sent To E
Notes
2006-10-06 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 14:50 Sent To E
Notes
2006-08-24 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-24 Cont ID  
Sent By rnuquist Date 2006-09-24 Time 10:32 Rev Time 0.00
Received By rnuquist Date 2006-08-18 Time 16:31 Sent To PC
Notes
2006-08-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By tgordon Date 2006-10-20 Time 09:01 Rev Time 0.20
Received By tgordon Date 2006-10-20 Time 09:01 Sent To B
Notes
2006-10-20 09:05:54*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-06 Cont ID  
Sent By tgordon Date 2006-09-06 Time 09:34 Rev Time 0.25
Received By tgordon Date 2006-09-06 Time 09:34 Sent To G
Notes
2006-09-06 00:00:00*** DENIED ***
 1) SITE PLAN SHOWS A FORM BOARD
 LOCATION, PLEASE SHOW WHAT IS TO BE
 BUILT ON THET SITE.
  
 2) GENERATOR LOCATION NEEDS TO BE
 LABELED.
  
 3) PLEASE SHOW BUILDING OPENINGS ON SITE
 PLAN. GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS). PER
 2004 FBC/M 401.5.1 .
  
 4) GENERATOR MAY BE TO CLOSE TO
 STRUCTURE THAT WILL BE BUILT ON FORM
 BOARD LOCATION.
  
 5)NEED TO SUBMIT TWO COPIES OF ALL
 DOCUMENTS. ALL INFORMATION,
 DRAWINGS,SPECIFICATIONS AND ACCOMPANYING
 DATA SHELL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. PER 2004 WPB(A) FBC 106.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-20 Cont ID  
Sent By mmclean Date 2006-08-20 Time 17:02 Rev Time 0.00
Received By mmclean Date 2006-08-20 Time 17:02 Sent To I
Notes
***NONE***