Plan Review Details - Permit 06081657
Plan Review Stops For Permit 06081657
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-09-24 Cont ID  
Sent By rnuquist Date 2006-09-24 Time 10:15 Rev Time 0.00
Received By rnuquist Date 2006-09-24 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-17 Cont ID  
Sent By btrobaug Date 2006-10-17 Time 14:36 Rev Time 0.33
Received By btrobaug Date 2006-10-17 Time 14:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By btrobaug Date 2006-09-01 Time 13:29 Rev Time 0.33
Received By btrobaug Date 2006-09-01 Time 13:29 Sent To M
Notes
2006-09-01 00:00:00 
  
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 2} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By mperson Date 2006-09-06 Time 15:55 Rev Time 0.15
Received By mperson Date 2006-09-06 Time 15:55 Sent To B
Notes
2006-09-06 00:00:00CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION
 (PARTICULARLY THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 14:49 Sent To E
Notes
2006-08-24 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-24 Cont ID  
Sent By rnuquist Date 2006-09-24 Time 10:16 Rev Time 0.00
Received By rnuquist Date 2006-08-18 Time 16:30 Sent To PC
Notes
2006-08-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-06 Cont ID  
Sent By tgordon Date 2006-09-06 Time 09:14 Rev Time 0.15
Received By tgordon Date 2006-09-06 Time 09:14 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-20 Cont ID  
Sent By mmclean Date 2006-08-20 Time 17:00 Rev Time 0.00
Received By mmclean Date 2006-08-20 Time 17:00 Sent To I
Notes
2006-08-22 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 3.5FT FROMSIDE PROPERTY
 LINE.


Account Summary | Usage Policy | Privacy Policy