Plan Review Stops For Permit 06081546 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-09-27 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-09-27 |
Time |
10:09 |
Sent To |
|
|
Notes |
2006-09-27 00:00:00 | EXT #0026 WAS CREATED FOR THE UNIT 208 |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2006-09-15 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-09-12 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-09-12 |
Time |
15:02 |
Sent To |
|
|
Notes |
2006-09-12 00:00:00 | PROJECT UNDER REVIEW. | | THE PROJECT IS FAILED SINCE NO UNIT IS | | INDICATED ON THE APPLICATION. | 2006-09-08 00:00:00 | NEEDS FOR SUITE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2006-11-03 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2006-11-03 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2006-10-04 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2006-10-04 |
Time |
07:07 |
Sent To |
|
|
Notes |
2006-10-04 00:00:00 | DENIED BY BUILDING | | | | 1) THE FIRM LICENSE NUMBER OF THE | | ARCHITECTURAL BUSINESS (ASD) IS REQUIRED | | | | IN THE TITLE BLOCK PER FAC 61G1-16.004. | | | | 2) THE PROJECT IS NOT ADEQUATELY | | IDENTIFIED IN THE TITLE BLOCK AS | | REQUIRED BY FAC 61G1-16.004. THE PROJECT | | IS NOT THE ENTIRE SECOND FLOOR. SPECIFY | | THE SUITE NUMBER. | | | | 3) ON SHEET A2.51 THE SECTION ID TAGS | | HAVE BEEN CHANGED BY MARKING THE PLAN. | | ANY REDLINE CHANGES TO SIGNED AND SEALED | | DRAWINGS ARE REQUIRED TO BE DONE BY THE | | PERSON SIGNING AND SEALING THEM. THE | | CHANGES MUST BE INITIALED AND DATED BY | | THE DESIGN PROFESSIONAL. | | | | 4) ADDRESS COMMENTS OF OTHER REVIEWERS. | | | | 5) RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-09-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2006-09-13 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2006-09-13 |
Time |
16:43 |
Sent To |
|
|
Notes |
2006-09-13 00:00:00 | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) THE ARCHITECT'S TITLE BLOCK IS | | MISSING INFORMATION. SEE FAC 61G-15 FOR | | REQUIRED INFORMATION. | | | | 3) THE CODE ANALYSIS INFORMATION ON | | A0.00 LISTS INCORRECT CODE SECTION AND | | TABLE REFERENCES. PLEASE UPDATE TO 2004 | | EDITION OF THE FLORIDA BUILDING CODE. | | SEE NOTATIONS ON PLAN. | | | | 4) PLEASE SPECIFY THE NUMBER OF STORIES | | AND BUILDING HEIGHT. PLEASE CORRECT THE | | CONSTRUCTION TYPE LISTED ON SHEET A0.00. | | SPECIFY THE CONSTRUCTION TYPE USING THE | | 2004 FBC DESIGNATIONS. IF THIS IS A HIGH | | RISE STRUCTURE WITH OCCUPIED FLOORS MORE | | THAN 75 FEET ABOVE FIRE DEPARTMENT | | ACCESS (403.1), THE CONSTRUCTION TYPE | | PER TABLE 503 IS TYPE I-A OR I-B | | (DEPENDING ON THE BUILDING HEIGHT). | | | | 5) SPECIFY THE LEVEL OF ALTERATION FOR | | THE PROJECT. SEE THE 2004 EXISTING | | BUILDING CODE. | | | | 6) PLEASE CHANGE THE CODE REFERENCE IN | | DETAIL 4 ON A7.01 FROM IBC TO FBC. | | | | 7) DETAIL 10 ON SHEET A7.21 IS | | INCORRECTLY LABELED. IT SHOULD BE | | LABELED DETAIL 7. | | | | 8) PROVIDE ADDITIONAL STRUCTURAL DETAILS | | FOR THE ATTACHMENT OF THE MDF PANELS IN | | THE RECEPTION AREA CEILING. SPECIFY THE | | SPACING OF THE THREADED RODS, UNISTRUTS, | | BLOCKING Z-CLIPS, ETC. SPECIFY THE | | ATTACHMENT OF THE BLOCKING TO THE | | STRUTS. SPECIFY THE EMBED DEPTH OF THE | | ANCHORS FOR THE THREADED RODS. DETERMINE | | THAT THE SLAB THAT WILL BE DRILLED INTO | | IS NOT A TENSION SLAB. | | | | 9) SPECIFY THE SUITE NUMBER FOR THE | | PROJECT ON THE PERMIT APPLICATION. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-02-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-07 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-07 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-02-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-03 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-03 |
Time |
13:54 |
Sent To |
PC |
|
Notes |
2007-02-03 14:14:08 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED TO ADD | | AN ADDITIONAL METER AND SERVICE TO THE SAME TENANT. | | THIS NEEDS TO BE CLARIFIED.PLEASE PROVIDE LOAD | | CALCULATIONS FOR THE ADDITION OF LOADS TO THE EXISTING | | SERVICE GUTTER. PLEASE SEE THE PREVIOUS RISER SHOWED A | | NEW FEED FROM THE EXISTING 600A GUTTER TO NEW GUTTER, | | YET THIS RISER SHOWS THIS NOW AS EXISTING? | | PLEASE SEE THE SAME TENANT IS NOW SHOWING TWO METERS | | FOR THE SAME SPACE?220, 220.35 ETC | | | | ** PLEASE CLARIFY AND REVISE THE ABOVE. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-31 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-31 |
Time |
07:20 |
Sent To |
I |
|
Notes |
2006-10-31 09:27:04 | *** REDLINED *** | | | | 1) MAX TIME ON OC SENSOR DEVICES IS 30MINS AFTER THE | | LAST SENSING. 13-415.1.ABC.1.1. | | | | | | ** INCREASED VALUE BASED ON ACTUAL COST, APPLICATION | | ETC. FEES OWED WILL BE $4,464 BEFORE PERMIT CAN BE | | ISSUED. | | THEY MAY BE PAID AHEAD OF TIME TO AVOID ANY DELAYS IN | | PROCESSING THE FINAL ISSUANCE OF PERMIT AND PLANS. | | | | | | ELECTRICAL PLANS STAMPED. | 2006-10-31 07:21:16 | REMOVED FROM INCOMING, IN ELEC FOR REVIEW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-10-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-01 |
Time |
17:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-01 |
Time |
17:36 |
Sent To |
|
|
Notes |
2006-10-01 00:00:00 | ********* UNSAT 2ND REVIEW ********** | | | | ** PLEASE SEE SOME COMMENTS FROM | | PREVIOUS REVIEW ARE STILL IN NEED OF | | BEING ADDRESSED. | | | | NOTES BELOW ARE TAKEN DIRECTLY FROM | | PREVIOUS REVIEW. | | | | 1) NOTE: NO, PLEASE SEE MISSING LICENSE | | INFORMATION REQUIRED FOR ARCHITECTURAL | | FIRM AS PREVIOUSLY NOTED FOR ALL SHEETS | | AND ALL TITLE BLOCKS. | | REQUIRED FOR ALL, WHETHER OR NOT COMMENT | | IS MADE BY OTHER REVIEWER(S). | | | | ** PREVIOUS REVIEW NOTE ** PLEASE SEE | | MISSING INFORMATION | | ON TITLE BLOCKS REQUIRED FOR THE | | ARCHITECTURAL FIRM. PLEASE SEE MISSING | | CERTIFICATE OF AUTHORIZATION NUMBER, | | PRINTED NAME, LICENSE #S', ADDRESS FOR | | FIRM, ETC. PLEASE SEE FLORIDA | | ADMINISTRATIVE CODE 61G1-16.004 AND | | FLORIDA STATUES 481.221, AND FS 481.219. | | THIS IS REQUIRED FOR ALL SHEETS CONTAIN | | SAID ARCHITECTURAL TITLE BLOCK AND FOR | | ALL TRADES WHETHER OR NOT COMMENT IS | | MADE BY OTHER REVIEWER(S). | | | | 2) NOTE: OK. | | | | 3) NOTE: OK. | | | | 4) NOTE: NO, ALTHOUGHT ALL CONTROLS ETC | | ARE OK, PLEASE VERIFY THE LPD'S BEING | | USED , AND ALLOWED FOR IN BUILD OUT. | | THIS CAN BE DONE SEPARATELY , HOWEVER | | WOULD STILL BE REQUIRED TO BE SIGNED, | | DATED AND SEALED BY THE ENGINEER OF | | RECORD. PLEASE KNOW, AS IT APPEARS | | PERHAPS DUE TO COMMENT #1 ALL SHEETS MAY | | NEED TO BE RE-PRINTED, THIS MAY BE ADDED | | AT THIS TIME. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE MISSING REQUIRED | | LIGHTING CONTROLS PER FBC 2004 CHAPTER | | 13. 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE ALSO PROVIDE ENERGY CALCULATIONS | | AND LIGHTING POWER DENSITIES AS | | REQUIRED. | | 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES | | 415.2.C.1 AND 415.2.B.1. | | PLEASE SHOW AND INDICATE SCHEDULING, | | TYPES AND LOCATIONS FOR CONTROLS AND | | OVER RIDES DEVICES. PLEASE INDICATE THE | | AMOUNT OF TIME ON OVER RIDE DEVICES. | | (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR | | TYPE 30 MINS MAX) ETC. | | ETC. AS NO SYSTEM IS BEING SHOWN AT THIS | | TIME, REVIEW OF SUCH SYSTEM FOR CODE | | COMPLIANCE CAN NOT BE DONE. | | | | 5) NOTE: NO, VALUE WAS NOT CHANGED OR | | ADJUSTED. THIS SOMMENT IS NOT FOR | | ENGINEERING RO ARCHITECTURAL FIRM. | | IF NOT ADJUSTED, AN ASSESSED VALUE WILL | | BE APPLIED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE COMPLETE VALUATION | | FOR COMPLETE SCOPE OF WORK AS INDICATED | | ON PLANS SHALL INCLUDE ALL LABOUR AND | | MATERIALS WHETHER OR NOT AN EUIPMENT/ | | MATERIALS ARE OWNER SUPPLIED. FBC 108.3 | | PLEASE SEE APPLIED VALUE SEEMS LOW FOR | | SCOPE SHOWN AND NEW EQUIPMENT BEING | | INDICATED. PLEASE KNOW, IF THE VALUE IS | | NOT ADJUSTED, ONE WILL BE ADJUSTED PER | | 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED | | ON THE FBC. | | | | 6) NOTE: NO, NONE SUBMITTED, ENGINEER'S | | RESPONSE MENTIONS TO BE DONE BY OTHERS. | | HOWEVER NOT SUBMITTED. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE INCLUDE AND SUBMIT | | MANUFACTURES SPECS/CUT SHEETS FOR ALL | | THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT. | | PLEASE BE SURE THE SPECS INDICATE A | | LISTING FROM A NRTL. | | | | 7) NOTE: OK. | | | | 8) NOTE: OK. | | | | 9) NOTE: OK. | | | | 10) NOTE: OK. | | | | | | ** NEW NOTE ** | | | | 11) NOTE: PLEASE SEE FS 553.80(2)(B) | | WITH RESPECT TO REPEAT COMMENTS FOR CODE | | COMPLIANCE. | | THIS IS ONLY A NOTICE GIVEN AT THIS | | TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-08 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-08 |
Time |
12:54 |
Sent To |
|
|
Notes |
2006-09-08 00:00:00 | ********* UNSAT ********** | | | | 1) NOTE: PLEASE SEE MISSING INFORMATION | | ON TITLE BLOCKS REQUIRED FOR THE | | ARCHITECTURAL FIRM. PLEASE SEE MISSING | | CERTIFICATE OF AUTHORIZATION NUMBER, | | PRINTED NAME, LICENSE #S', ADDRESS FOR | | FIRM, ETC. PLEASE SEE FLORIDA | | ADMINISTRATIVE CODE 61G1-16.004 AND | | FLORIDA STATUES 481.221, AND FS 481.219. | | THIS IS REQUIRED FOR ALL SHEETS CONTAIN | | SAID ARCHITECTURAL TITLE BLOCK AND FOR | | ALL TRADES WHETHER OR NOT COMMENT IS | | MADE BY OTHER REVIEWER(S). | | | | 2) NOTE: PLEASE LIST THE LATEST ADOPTED | | EDITION OF NFPA-75 (2002). | | | | 3) NOTE: PLEASE SEE COLOR CODING FOR | | 277/480V SHALL BE AS FOLLOWS. BROWN, | | PURPLE, YELLOW. | | PLEASE KNOW, "ORANGE" AS INDICATED IS | | REQUIRED FOR 120/240V OPEN DELTA, FOR | | SYSTEMS WITH A HIGH-LEG. | | THE NEC DOES NOT INCLUDE COLOR CODING | | FOR 277/480 AND SUCH SYSTEMS LOCATED IN | | THIS JURISDICTION HAVE PREVIOUSLY BEEN | | COLOR CODED PER ABOVE PER LOCAL | | AMENDMENTS. 90.4, 215.5 | | | | 4) NOTE: PLEASE SEE MISSING REQUIRED | | LIGHTING CONTROLS PER FBC 2004 CHAPTER | | 13. 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE ALSO PROVIDE ENERGY CALCULATIONS | | AND LIGHTING POWER DENSITIES AS | | REQUIRED. | | 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES | | 415.2.C.1 AND 415.2.B.1. | | PLEASE SHOW AND INDICATE SCHEDULING, | | TYPES AND LOCATIONS FOR CONTROLS AND | | OVER RIDES DEVICES. PLEASE INDICATE THE | | AMOUNT OF TIME ON OVER RIDE DEVICES. | | (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR | | TYPE 30 MINS MAX) ETC. | | ETC. AS NO SYSTEM IS BEING SHOWN AT THIS | | TIME, REVIEW OF SUCH SYSTEM FOR CODE | | COMPLIANCE CAN NOT BE DONE. | | | | 5) NOTE: PLEASE SEE COMPLETE VALUATION | | FOR COMPLETE SCOPE OF WORK AS INDICATED | | ON PLANS SAHLL INCLUDE ALL LABOUR AND | | MATERIALS WHETHER OR NOT AN EUIPMENT/ | | MATERIALS ARE OWNER SUPPLIED. FBC 108.3 | | PLEASE SEE APPLIED VALUE SEEMS LOW FOR | | SCOPE SHOWN AND NEW EQUIPMENT BEING | | INDICATED. PLEASE KNOW, IF THE VALUE IS | | NOT ADJUSTED, ONE WILL BE ADJUSTED PER | | 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED | | ON THE FBC. | | | | 6) NOTE: PLEASE INCLUDE AND SUBMIT | | MANUFACTURES SPECS/CUT SHEETS FOR ALL | | THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT. | | PLEASE BE SURE THE SPECS INDICATE A | | LISTING FROM A NRTL. | | | | 7) NOTE: PLEASE SEE NFPA-75, AND | | NFPA-70, 645 AS THE MDF ROOM SEEMS TO | | CLEARLY INDICATE AN "IT" ROOM. PLEASE | | SEE MECHANICAL REQUIREMENTS FOR RATED | | DMAPERS, SD'S. | | PLEASE SEE AN EPO IS BEING SHOWN, | | HOWEVER HOW THIS IS BEIGN TIED IN AND | | SHUNTING THE POWER COMING FROM "L2A1, | | L2A2 AND URL" IS UNCLEAR AT THIS TIME. | | PLEASE SEE NO MENTION IN THESE PANELS | | COULD BE LCOATED FOR SHUNT AND | | DISCONNECTING MEANS. | | 645.1-.16 | | | | 8) NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | AS ACCESS CONTROL SYSTEM(S) NEEDS TO BE | | VERIFIED. PLEASE SEE NFPA-101 AS A FAIL | | SAFE MODE/ BACK-UP IS REQUIRED SO THAT | | MEANS OF EGRESS MAY NOT BE IMPEDED. | | 7.2.1.5 | | PLEASE SEE THAT SYSTEM AS SHOWN IS NOT | | CLEAR OF CODE COMPLIANCE AT THIS TIME. | | PLEASE SEE THAT ANY COMMENTS FORM FIRE | | REVIEW WILL BE REQUIRED TO BE ADJUSTED | | ON ELECTRICAL PLANS. | | | | 9) NOTE: PLEASE COMPLETE PANEL SCHEDULES | | INDICATING ALL CONDUCTOR SIZES AND | | CORRELATING WIHT THE OCP AS SHOWN. | | PLEASE SEE 240.4,310.16,408.4. | | THIS IS REQUIRED AT THIS TIME. | | FBC 106.1.2 | | | | 10) NOTE: PLEASE SUBMIT COMPLETED LOAD | | CALCULATIONS PER 220.3,220.10,220.11, | | 210.13, ETC AND PLEASE SHOW ALL | | CONTINUOUS LOADS AT 125% 215.3,230.42 | | ETC. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | | | | | 5) |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-02 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-02 |
Time |
14:41 |
Sent To |
|
|
Notes |
2006-11-02 14:42:43 | ****APPROVED**** | | | | | | | | ALL PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-10-11 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-11 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-11 |
Time |
14:40 |
Sent To |
|
|
Notes |
2006-10-11 14:46:15 | *****ACCEPTABLE W/ PROVISO***** | | | | ** A REVIEW OF YOUR RESPONSES TO THE PREVIOUS FIRE PLAN | | REVIEW COMMENTS (09/14/06) REVEAL THAT: | | | | | | | | 1.)NFPA 101, 2003 EDITION SHALL BE REFERENCED.OMIT | | THE WORDAGE " W/ 2005 AMENDMENTS". | | | | 2.)OK | | | | 3.)OK | | | | 4.)OK | | | | 5.)OK | | | | 6.)REPLACE THE WORD "EXISTS" WITH THE CORRECT | | SPELLING OF EXITS. | | | | 7.)OK | | | | 8.)OK | | | | 9.)SO NOTED | | | | 10) OK | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-09-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-09-14 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-09-14 |
Time |
14:54 |
Sent To |
|
|
Notes |
2006-09-14 00:00:00 | *****COMMENTS TO BE ADDRESSED***** | | | | | | | | | | 1.) NFPA 101, 2003 EDITION TO BE | | REFERENCED. | | | | 2.) COMPLIANCE WITH FLORIDA FIRE | | PREVENTION CODE, 2004 EDITION. | | | | 3.) STRUCTURES UNDERGOING CONSTRUCTION, | | ALTERATION, OR DEMOLITION OPERATIONS | | SHALL COMPLY WITH NFPA 241. | | | | 4.) WHERE THE BUILDING IS PROTECTED BY | | FIRE PROTECTION SYSTEMS, SUCH SYSTEMS | | SHALL BE MAINTAINED OPERATIONAL AT ALL | | TIMES. | | | | 5.) WHEN IT IS NECESSARY TO SHUT DOWN A | | FIRE PROTECTION SYSTEM, THE FIRE | | DEPARTMENT SHALL BE NOTIFIED. WPBFR WILL | | ALSO BE NOTIFIED WHEN THE SYSTEM IS | | RETURNED TO SERVICE. | | | | 6.) EXITS ARE TO REMAIN CLEAR AND | | UNOBSTRUCTED. | | | | 7.) IF THE SCOPE OF THE INTERIOR | | BUILDOUT REQUIRES MODIFICATION OF THE | | FIRE SPRINKLER OR FIRE ALARM SYSTEM, | | SEPARATE PERMIT AND SHOP DRAWINGS/PLANS | | ARE REQUIRED FOR REVIEW. | | | | 8.) PLEASE INDICATE INTERIOR FINISH FOR | | WALLS AND CEILINGS. CLASS A OR B IS | | REQUIRED IN THE MEANS OF EGRESS AREAS. | | | | 9.) IN RELATION TO PROPOSED ACCESS | | CONTROL SYSTEM(S), SEPARATE PERMIT AND | | PLANS ARE REQUIRED. REFERENCE NFPA 101, | | 2003 EDITION, 7.2.1.6, SPECIAL LOCKING | | ARRANGEMENTS. | | | | 10.)PLEASE INDICATE SUITE NUMBER AND | | THEIR DIMENSIONS AS PER WEST PALM BEACH | | CODE. | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-31 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-31 |
Time |
13:54 |
Sent To |
E |
|
Notes |
2007-01-31 13:54:17 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-01-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-29 |
Time |
18:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-29 |
Time |
18:17 |
Sent To |
M |
|
Notes |
2007-01-29 18:18:09 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-27 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-27 |
Time |
09:05 |
Sent To |
|
|
Notes |
2006-11-01 11:20:47 | TO "BOB"#16 | 2006-10-27 09:05:54 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-27 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-27 |
Time |
13:24 |
Sent To |
|
|
Notes |
2006-09-28 00:00:00 | TO "BOB"#3 | 2006-09-27 00:00:00 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-09-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-09-14 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-08-17 |
Time |
15:15 |
Sent To |
|
|
Notes |
2006-09-06 00:00:00 | TO "BOB"#12 | 2006-08-17 00:00:00 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-30 |
Time |
10:51 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2007-01-30 |
Time |
10:51 |
Sent To |
|
|
Notes |
2007-01-30 10:53:38 | REVISION TO OUTSIDE AIR DUCT LOCATED ON PAGES M1.02 AND | | MD.02. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-11-01 |
Time |
14:51 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2006-11-01 |
Time |
14:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-04 |
Time |
11:50 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-10-04 |
Time |
11:50 |
Sent To |
|
|
Notes |
2006-10-04 00:00:00 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-09-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-09-11 |
Time |
10:25 |
Rev Time |
0.35 |
Received By |
tgordon |
Date |
2006-09-11 |
Time |
10:25 |
Sent To |
|
|
Notes |
2006-09-11 00:00:00 | *** DENIED *** | | 1) SEE PAGE M1.02 ROOM MDF #02103 (IT | | ROOM) LEFT SIDE OF PAGE SHOWS CR-1 FOR | | THIS ROOM, RIGHT SIDE OF PAGE SHOWS DUCT | | WORK FROM HP-3 FOR THIS ROOM, PLEASE | | CORRECT. | | | | 2) SEE PLUMBING AND ELECTRICAL REVIEW | | NOTES REGARDING TITLE BLOCK, PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2006-11-18 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-11-18 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-11-18 |
Time |
10:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-10-17 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-10-17 |
Time |
09:27 |
Sent To |
|
|
Notes |
2006-10-17 09:36:16 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ALL ARCHITECTURAL SHEETS. THE | | FOLLOWING INFORMATION IS REQUIRED IN THE | | TITLE BLOCK: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE | | NUMBER. | | ****RESPONSE NOTED, BUT SHT A8.01 DOES NOT COMPLY | | (2) FIRM LICENSE NUMBER. | | ****NO RESPONSE NOT ADDRESSED | | (3) NAME OR IDENTIFICATION OF PROJECT. | | ****RESPONSE NOTED, BUT SPACE/UNIT REQUIRED | | (4) OK | | (5) A SPACE FOR THE SIGNATURE AND DATED | | SEAL. | | ****RESPONSE NOTED, BUT DATE NOT ON SEAL SHT A8.01 | | (6) A SPACE FOR THE PRINTED NAME OF THE | | PERSON SEALING THE DOCUMENT. | | ****RESPONSE NOTED, BUT PRINTED NAME NOT SHOWN ON SHT | | A8.01 | | FAS 61G1-16.004 & FS 481.219 - 481.2055. | | | | 2. OK | | | | 3. SHT BETWEEN A6.01 & A7.01, (NOT | | NUMBERED), DETAIL #2 ELEVATION COMMONS | | EAST. SHOW THE FOLLOWING INFORMATION: | | A. OK | | B. OK | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD | | APPROACH REQUIRED) | | ****RESPONSE NOTED, BUT LENGTH IS SHOWN AS 42" (48" | | REQD). CLEAR FLOOR SPACE NOT SHOWN ON FLOOR PLAN. | | CABINET DOORS ARE NOT APPROVED IN THE CLEAR FLOOR | | SPACE. DELETE CABINET DOORS. | | D. OK | | E. OK | | | | 4. OK | | 5. OK | | 6. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-09-07 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-09-07 |
Time |
06:58 |
Sent To |
|
|
Notes |
2006-09-07 00:00:00 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ALL ARCHITECTURAL SHEETS. THE | | FOLLOWING INFORMATION IS REQUIRED IN THE | | TITLE BLOCK: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE | | NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED | | SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE | | PERSON SEALING THE DOCUMENT. | | FAS 61G1-16.004 & FS 481.219 - 481.2055. | | | | 2. SEAL SHALL BE SIGNED AND DATED. NO | | DATE IS ON SEAL, AND IT APPEARS TO BE | | INITIALS. IF THIS IS YOUR LEGAL | | SIGNATURE, THEN A NOTORIZED LETTER | | INDICATING YOUR LEGAL SIGNATURE IS | | REQUIRED FOR OUR FILES. FAC | | 61G1-16.004(5) & FS 481.2055. | | | | 3. SHT BETWEEN A6.01 & A7.01, (NOT | | NUMBERED), DETAIL #2 ELEVATION COMMONS | | EAST. SHOW THE FOLLOWING INFORMATION: | | A. 11-4.24.3 KNEE CLEARANCE | | B. 11-4.24.4 SINK DEPTH | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD | | APPROACH REQUIRED) | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | E. 11-4.24.7 FAUCETS | | | | 4. SHT P1.02 WATER PIPING ISOMETRIC. | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | NEAR THE FIXTURES IN AN "EFFECTIVE | | RANGE" AND NOT IN THE CEILING AS SHOWN. | | PDI-WH 201 AND MANUF. INSTALLATION | | INSTRUCTIONS. - WATER HAMMER ARRESTORS | | ARE REQUIRED AT THE ICE MAKER AND THE | | DISH WASHER PER SECTION 604.9. | | | | 5. SHT P1.02 WATER PIPING ISOMETRIC. A | | FULL OPEN VALVE IS REQUIRED ON THE TOP | | OF ALL WATER DOWN-FEED PIPES. SECTION | | 606.1(4). | | | | 6. SHT P1.02 GENERAL NOTES #1. AIR | | CHAMBERS ARE NOT APPROVED. DELETE | | REFERENCE. SECTION 604.9. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|