Plan Review Details - Permit 06081546
Plan Review Stops For Permit 06081546
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-09-27 Cont ID  
Sent By lursu Date 2006-09-27 Time 10:09 Rev Time 0.00
Received By lursu Date 2006-09-27 Time 10:09 Sent To  
Notes
2006-09-27 00:00:00EXT #0026 WAS CREATED FOR THE UNIT 208

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By lursu Date 2006-09-12 Time 15:02 Rev Time 0.00
Received By lursu Date 2006-09-12 Time 15:02 Sent To  
Notes
2006-09-12 00:00:00PROJECT UNDER REVIEW.
 THE PROJECT IS FAILED SINCE NO UNIT IS
 INDICATED ON THE APPLICATION.
2006-09-08 00:00:00NEEDS FOR SUITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-03 Cont ID  
Sent By rmcdouga Date 2006-11-03 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2006-11-03 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-04 Cont ID  
Sent By rmcdouga Date 2006-10-04 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2006-10-04 Time 07:07 Sent To  
Notes
2006-10-04 00:00:00DENIED BY BUILDING
  
 1) THE FIRM LICENSE NUMBER OF THE
 ARCHITECTURAL BUSINESS (ASD) IS REQUIRED
  
 IN THE TITLE BLOCK PER FAC 61G1-16.004.
  
 2) THE PROJECT IS NOT ADEQUATELY
 IDENTIFIED IN THE TITLE BLOCK AS
 REQUIRED BY FAC 61G1-16.004. THE PROJECT
 IS NOT THE ENTIRE SECOND FLOOR. SPECIFY
 THE SUITE NUMBER.
  
 3) ON SHEET A2.51 THE SECTION ID TAGS
 HAVE BEEN CHANGED BY MARKING THE PLAN.
 ANY REDLINE CHANGES TO SIGNED AND SEALED
 DRAWINGS ARE REQUIRED TO BE DONE BY THE
 PERSON SIGNING AND SEALING THEM. THE
 CHANGES MUST BE INITIALED AND DATED BY
 THE DESIGN PROFESSIONAL.
  
 4) ADDRESS COMMENTS OF OTHER REVIEWERS.
  
 5) RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By rmcdouga Date 2006-09-13 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2006-09-13 Time 16:43 Sent To  
Notes
2006-09-13 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ARCHITECT'S TITLE BLOCK IS
 MISSING INFORMATION. SEE FAC 61G-15 FOR
 REQUIRED INFORMATION.
  
 3) THE CODE ANALYSIS INFORMATION ON
 A0.00 LISTS INCORRECT CODE SECTION AND
 TABLE REFERENCES. PLEASE UPDATE TO 2004
 EDITION OF THE FLORIDA BUILDING CODE.
 SEE NOTATIONS ON PLAN.
  
 4) PLEASE SPECIFY THE NUMBER OF STORIES
 AND BUILDING HEIGHT. PLEASE CORRECT THE
 CONSTRUCTION TYPE LISTED ON SHEET A0.00.
 SPECIFY THE CONSTRUCTION TYPE USING THE
 2004 FBC DESIGNATIONS. IF THIS IS A HIGH
 RISE STRUCTURE WITH OCCUPIED FLOORS MORE
 THAN 75 FEET ABOVE FIRE DEPARTMENT
 ACCESS (403.1), THE CONSTRUCTION TYPE
 PER TABLE 503 IS TYPE I-A OR I-B
 (DEPENDING ON THE BUILDING HEIGHT).
  
 5) SPECIFY THE LEVEL OF ALTERATION FOR
 THE PROJECT. SEE THE 2004 EXISTING
 BUILDING CODE.
  
 6) PLEASE CHANGE THE CODE REFERENCE IN
 DETAIL 4 ON A7.01 FROM IBC TO FBC.
  
 7) DETAIL 10 ON SHEET A7.21 IS
 INCORRECTLY LABELED. IT SHOULD BE
 LABELED DETAIL 7.
  
 8) PROVIDE ADDITIONAL STRUCTURAL DETAILS
 FOR THE ATTACHMENT OF THE MDF PANELS IN
 THE RECEPTION AREA CEILING. SPECIFY THE
 SPACING OF THE THREADED RODS, UNISTRUTS,
 BLOCKING Z-CLIPS, ETC. SPECIFY THE
 ATTACHMENT OF THE BLOCKING TO THE
 STRUTS. SPECIFY THE EMBED DEPTH OF THE
 ANCHORS FOR THE THREADED RODS. DETERMINE
 THAT THE SLAB THAT WILL BE DRILLED INTO
 IS NOT A TENSION SLAB.
  
 9) SPECIFY THE SUITE NUMBER FOR THE
 PROJECT ON THE PERMIT APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-02-07 Cont ID  
Sent By dpalmer Date 2007-02-07 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2007-02-07 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-03 Cont ID  
Sent By dpalmer Date 2007-02-03 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2007-02-03 Time 13:54 Sent To PC
Notes
2007-02-03 14:14:08*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED TO ADD
 AN ADDITIONAL METER AND SERVICE TO THE SAME TENANT.
 THIS NEEDS TO BE CLARIFIED.PLEASE PROVIDE LOAD
 CALCULATIONS FOR THE ADDITION OF LOADS TO THE EXISTING
 SERVICE GUTTER. PLEASE SEE THE PREVIOUS RISER SHOWED A
 NEW FEED FROM THE EXISTING 600A GUTTER TO NEW GUTTER,
 YET THIS RISER SHOWS THIS NOW AS EXISTING?
 PLEASE SEE THE SAME TENANT IS NOW SHOWING TWO METERS
 FOR THE SAME SPACE?220, 220.35 ETC
  
 ** PLEASE CLARIFY AND REVISE THE ABOVE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By dpalmer Date 2006-10-31 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 07:20 Sent To I
Notes
2006-10-31 09:27:04*** REDLINED ***
  
 1) MAX TIME ON OC SENSOR DEVICES IS 30MINS AFTER THE
 LAST SENSING. 13-415.1.ABC.1.1.
  
  
 ** INCREASED VALUE BASED ON ACTUAL COST, APPLICATION
 ETC. FEES OWED WILL BE $4,464 BEFORE PERMIT CAN BE
 ISSUED.
 THEY MAY BE PAID AHEAD OF TIME TO AVOID ANY DELAYS IN
 PROCESSING THE FINAL ISSUANCE OF PERMIT AND PLANS.
  
  
 ELECTRICAL PLANS STAMPED.
2006-10-31 07:21:16REMOVED FROM INCOMING, IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 17:36 Sent To  
Notes
2006-10-01 00:00:00********* UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL IN NEED OF
 BEING ADDRESSED.
  
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1) NOTE: NO, PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTURAL
 FIRM AS PREVIOUSLY NOTED FOR ALL SHEETS
 AND ALL TITLE BLOCKS.
 REQUIRED FOR ALL, WHETHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE
 MISSING INFORMATION
 ON TITLE BLOCKS REQUIRED FOR THE
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, LICENSE #S', ADDRESS FOR
 FIRM, ETC. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.221, AND FS 481.219.
 THIS IS REQUIRED FOR ALL SHEETS CONTAIN
 SAID ARCHITECTURAL TITLE BLOCK AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, ALTHOUGHT ALL CONTROLS ETC
 ARE OK, PLEASE VERIFY THE LPD'S BEING
 USED , AND ALLOWED FOR IN BUILD OUT.
 THIS CAN BE DONE SEPARATELY , HOWEVER
 WOULD STILL BE REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD. PLEASE KNOW, AS IT APPEARS
 PERHAPS DUE TO COMMENT #1 ALL SHEETS MAY
 NEED TO BE RE-PRINTED, THIS MAY BE ADDED
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 LIGHTING CONTROLS PER FBC 2004 CHAPTER
 13. 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO PROVIDE ENERGY CALCULATIONS
 AND LIGHTING POWER DENSITIES AS
 REQUIRED.
 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE SHOW AND INDICATE SCHEDULING,
 TYPES AND LOCATIONS FOR CONTROLS AND
 OVER RIDES DEVICES. PLEASE INDICATE THE
 AMOUNT OF TIME ON OVER RIDE DEVICES.
 (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR
 TYPE 30 MINS MAX) ETC.
 ETC. AS NO SYSTEM IS BEING SHOWN AT THIS
 TIME, REVIEW OF SUCH SYSTEM FOR CODE
 COMPLIANCE CAN NOT BE DONE.
  
 5) NOTE: NO, VALUE WAS NOT CHANGED OR
 ADJUSTED. THIS SOMMENT IS NOT FOR
 ENGINEERING RO ARCHITECTURAL FIRM.
 IF NOT ADJUSTED, AN ASSESSED VALUE WILL
 BE APPLIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE COMPLETE VALUATION
 FOR COMPLETE SCOPE OF WORK AS INDICATED
 ON PLANS SHALL INCLUDE ALL LABOUR AND
 MATERIALS WHETHER OR NOT AN EUIPMENT/
 MATERIALS ARE OWNER SUPPLIED. FBC 108.3
 PLEASE SEE APPLIED VALUE SEEMS LOW FOR
 SCOPE SHOWN AND NEW EQUIPMENT BEING
 INDICATED. PLEASE KNOW, IF THE VALUE IS
 NOT ADJUSTED, ONE WILL BE ADJUSTED PER
 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED
 ON THE FBC.
  
 6) NOTE: NO, NONE SUBMITTED, ENGINEER'S
 RESPONSE MENTIONS TO BE DONE BY OTHERS.
 HOWEVER NOT SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE AND SUBMIT
 MANUFACTURES SPECS/CUT SHEETS FOR ALL
 THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT.
 PLEASE BE SURE THE SPECS INDICATE A
 LISTING FROM A NRTL.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
  
 ** NEW NOTE **
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 12:54 Sent To  
Notes
2006-09-08 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS REQUIRED FOR THE
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, LICENSE #S', ADDRESS FOR
 FIRM, ETC. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND
 FLORIDA STATUES 481.221, AND FS 481.219.
 THIS IS REQUIRED FOR ALL SHEETS CONTAIN
 SAID ARCHITECTURAL TITLE BLOCK AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE LIST THE LATEST ADOPTED
 EDITION OF NFPA-75 (2002).
  
 3) NOTE: PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE AS FOLLOWS. BROWN,
 PURPLE, YELLOW.
 PLEASE KNOW, "ORANGE" AS INDICATED IS
 REQUIRED FOR 120/240V OPEN DELTA, FOR
 SYSTEMS WITH A HIGH-LEG.
 THE NEC DOES NOT INCLUDE COLOR CODING
 FOR 277/480 AND SUCH SYSTEMS LOCATED IN
 THIS JURISDICTION HAVE PREVIOUSLY BEEN
 COLOR CODED PER ABOVE PER LOCAL
 AMENDMENTS. 90.4, 215.5
  
 4) NOTE: PLEASE SEE MISSING REQUIRED
 LIGHTING CONTROLS PER FBC 2004 CHAPTER
 13. 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO PROVIDE ENERGY CALCULATIONS
 AND LIGHTING POWER DENSITIES AS
 REQUIRED.
 113-415.1.AB.1, 13-415.2.ABC.1,; TABLES
 415.2.C.1 AND 415.2.B.1.
 PLEASE SHOW AND INDICATE SCHEDULING,
 TYPES AND LOCATIONS FOR CONTROLS AND
 OVER RIDES DEVICES. PLEASE INDICATE THE
 AMOUNT OF TIME ON OVER RIDE DEVICES.
 (TIMER TYPE4HRS MAX, OCCUPANCY SENSOR
 TYPE 30 MINS MAX) ETC.
 ETC. AS NO SYSTEM IS BEING SHOWN AT THIS
 TIME, REVIEW OF SUCH SYSTEM FOR CODE
 COMPLIANCE CAN NOT BE DONE.
  
 5) NOTE: PLEASE SEE COMPLETE VALUATION
 FOR COMPLETE SCOPE OF WORK AS INDICATED
 ON PLANS SAHLL INCLUDE ALL LABOUR AND
 MATERIALS WHETHER OR NOT AN EUIPMENT/
 MATERIALS ARE OWNER SUPPLIED. FBC 108.3
 PLEASE SEE APPLIED VALUE SEEMS LOW FOR
 SCOPE SHOWN AND NEW EQUIPMENT BEING
 INDICATED. PLEASE KNOW, IF THE VALUE IS
 NOT ADJUSTED, ONE WILL BE ADJUSTED PER
 'MARSHALL'S & SWIFT" GUIDES AS ADOPTED
 ON THE FBC.
  
 6) NOTE: PLEASE INCLUDE AND SUBMIT
 MANUFACTURES SPECS/CUT SHEETS FOR ALL
 THE NEW UPS/ LEIBERT SYSTEM EQUIPMENT.
 PLEASE BE SURE THE SPECS INDICATE A
 LISTING FROM A NRTL.
  
 7) NOTE: PLEASE SEE NFPA-75, AND
 NFPA-70, 645 AS THE MDF ROOM SEEMS TO
 CLEARLY INDICATE AN "IT" ROOM. PLEASE
 SEE MECHANICAL REQUIREMENTS FOR RATED
 DMAPERS, SD'S.
 PLEASE SEE AN EPO IS BEING SHOWN,
 HOWEVER HOW THIS IS BEIGN TIED IN AND
 SHUNTING THE POWER COMING FROM "L2A1,
 L2A2 AND URL" IS UNCLEAR AT THIS TIME.
 PLEASE SEE NO MENTION IN THESE PANELS
 COULD BE LCOATED FOR SHUNT AND
 DISCONNECTING MEANS.
 645.1-.16
  
 8) NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS ACCESS CONTROL SYSTEM(S) NEEDS TO BE
 VERIFIED. PLEASE SEE NFPA-101 AS A FAIL
 SAFE MODE/ BACK-UP IS REQUIRED SO THAT
 MEANS OF EGRESS MAY NOT BE IMPEDED.
 7.2.1.5
 PLEASE SEE THAT SYSTEM AS SHOWN IS NOT
 CLEAR OF CODE COMPLIANCE AT THIS TIME.
 PLEASE SEE THAT ANY COMMENTS FORM FIRE
 REVIEW WILL BE REQUIRED TO BE ADJUSTED
 ON ELECTRICAL PLANS.
  
 9) NOTE: PLEASE COMPLETE PANEL SCHEDULES
 INDICATING ALL CONDUCTOR SIZES AND
 CORRELATING WIHT THE OCP AS SHOWN.
 PLEASE SEE 240.4,310.16,408.4.
 THIS IS REQUIRED AT THIS TIME.
 FBC 106.1.2
  
 10) NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS PER 220.3,220.10,220.11,
 210.13, ETC AND PLEASE SHOW ALL
 CONTINUOUS LOADS AT 125% 215.3,230.42
 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
 5)

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-02 Cont ID  
Sent By mawillia Date 2006-11-02 Time 14:41 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 14:41 Sent To  
Notes
2006-11-02 14:42:43****APPROVED****
  
  
  
 ALL PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-11 Cont ID  
Sent By mawillia Date 2006-10-11 Time 14:41 Rev Time 0.00
Received By mawillia Date 2006-10-11 Time 14:40 Sent To  
Notes
2006-10-11 14:46:15*****ACCEPTABLE W/ PROVISO*****
  
 ** A REVIEW OF YOUR RESPONSES TO THE PREVIOUS FIRE PLAN
 REVIEW COMMENTS (09/14/06) REVEAL THAT:
  
  
  
 1.)NFPA 101, 2003 EDITION SHALL BE REFERENCED.OMIT
 THE WORDAGE " W/ 2005 AMENDMENTS".
  
 2.)OK
  
 3.)OK
  
 4.)OK
  
 5.)OK
  
 6.)REPLACE THE WORD "EXISTS" WITH THE CORRECT
 SPELLING OF EXITS.
  
 7.)OK
  
 8.)OK
  
 9.)SO NOTED
  
 10) OK
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-14 Time 15:18 Rev Time 0.00
Received By mawillia Date 2006-09-14 Time 14:54 Sent To  
Notes
2006-09-14 00:00:00*****COMMENTS TO BE ADDRESSED*****
  
  
  
  
 1.) NFPA 101, 2003 EDITION TO BE
 REFERENCED.
  
 2.) COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION.
  
 3.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 4.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES.
  
 5.) WHEN IT IS NECESSARY TO SHUT DOWN A
 FIRE PROTECTION SYSTEM, THE FIRE
 DEPARTMENT SHALL BE NOTIFIED. WPBFR WILL
 ALSO BE NOTIFIED WHEN THE SYSTEM IS
 RETURNED TO SERVICE.
  
 6.) EXITS ARE TO REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 7.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE SPRINKLER OR FIRE ALARM SYSTEM,
 SEPARATE PERMIT AND SHOP DRAWINGS/PLANS
 ARE REQUIRED FOR REVIEW.
  
 8.) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS. CLASS A OR B IS
 REQUIRED IN THE MEANS OF EGRESS AREAS.
  
 9.) IN RELATION TO PROPOSED ACCESS
 CONTROL SYSTEM(S), SEPARATE PERMIT AND
 PLANS ARE REQUIRED. REFERENCE NFPA 101,
 2003 EDITION, 7.2.1.6, SPECIAL LOCKING
 ARRANGEMENTS.
  
 10.)PLEASE INDICATE SUITE NUMBER AND
 THEIR DIMENSIONS AS PER WEST PALM BEACH
 CODE.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 13:54 Sent To E
Notes
2007-01-31 13:54:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 18:17 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 18:17 Sent To M
Notes
2007-01-29 18:18:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 09:05 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 09:05 Sent To  
Notes
2006-11-01 11:20:47TO "BOB"#16
2006-10-27 09:05:54WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-27 Cont ID  
Sent By adarroug Date 2006-09-27 Time 13:24 Rev Time 0.00
Received By adarroug Date 2006-09-27 Time 13:24 Sent To  
Notes
2006-09-28 00:00:00TO "BOB"#3
2006-09-27 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-14 Time 16:21 Rev Time 0.00
Received By mawillia Date 2006-08-17 Time 15:15 Sent To  
Notes
2006-09-06 00:00:00TO "BOB"#12
2006-08-17 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-01-30 Cont ID  
Sent By tgordon Date 2007-01-30 Time 10:51 Rev Time 0.45
Received By tgordon Date 2007-01-30 Time 10:51 Sent To  
Notes
2007-01-30 10:53:38REVISION TO OUTSIDE AIR DUCT LOCATED ON PAGES M1.02 AND
 MD.02.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 14:51 Rev Time 0.25
Received By tgordon Date 2006-11-01 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-04 Cont ID  
Sent By tgordon Date 2006-10-04 Time 11:50 Rev Time 0.30
Received By tgordon Date 2006-10-04 Time 11:50 Sent To  
Notes
2006-10-04 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 10:25 Rev Time 0.35
Received By tgordon Date 2006-09-11 Time 10:25 Sent To  
Notes
2006-09-11 00:00:00*** DENIED ***
 1) SEE PAGE M1.02 ROOM MDF #02103 (IT
 ROOM) LEFT SIDE OF PAGE SHOWS CR-1 FOR
 THIS ROOM, RIGHT SIDE OF PAGE SHOWS DUCT
 WORK FROM HP-3 FOR THIS ROOM, PLEASE
 CORRECT.
  
 2) SEE PLUMBING AND ELECTRICAL REVIEW
 NOTES REGARDING TITLE BLOCK, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 10:22 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By kstevens Date 2006-10-17 Time 09:27 Rev Time 0.00
Received By kstevens Date 2006-10-17 Time 09:27 Sent To  
Notes
2006-10-17 09:36:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE
 FOLLOWING INFORMATION IS REQUIRED IN THE
 TITLE BLOCK:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 ****RESPONSE NOTED, BUT SHT A8.01 DOES NOT COMPLY
 (2) FIRM LICENSE NUMBER.
 ****NO RESPONSE NOT ADDRESSED
 (3) NAME OR IDENTIFICATION OF PROJECT.
 ****RESPONSE NOTED, BUT SPACE/UNIT REQUIRED
 (4) OK
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 ****RESPONSE NOTED, BUT DATE NOT ON SEAL SHT A8.01
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 ****RESPONSE NOTED, BUT PRINTED NAME NOT SHOWN ON SHT
 A8.01
 FAS 61G1-16.004 & FS 481.219 - 481.2055.
  
 2. OK
  
 3. SHT BETWEEN A6.01 & A7.01, (NOT
 NUMBERED), DETAIL #2 ELEVATION COMMONS
 EAST. SHOW THE FOLLOWING INFORMATION:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
 ****RESPONSE NOTED, BUT LENGTH IS SHOWN AS 42" (48"
 REQD). CLEAR FLOOR SPACE NOT SHOWN ON FLOOR PLAN.
 CABINET DOORS ARE NOT APPROVED IN THE CLEAR FLOOR
 SPACE. DELETE CABINET DOORS.
 D. OK
 E. OK
  
 4. OK
 5. OK
 6. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 07:58 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 06:58 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE
 FOLLOWING INFORMATION IS REQUIRED IN THE
 TITLE BLOCK:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FAS 61G1-16.004 & FS 481.219 - 481.2055.
  
 2. SEAL SHALL BE SIGNED AND DATED. NO
 DATE IS ON SEAL, AND IT APPEARS TO BE
 INITIALS. IF THIS IS YOUR LEGAL
 SIGNATURE, THEN A NOTORIZED LETTER
 INDICATING YOUR LEGAL SIGNATURE IS
 REQUIRED FOR OUR FILES. FAC
 61G1-16.004(5) & FS 481.2055.
  
 3. SHT BETWEEN A6.01 & A7.01, (NOT
 NUMBERED), DETAIL #2 ELEVATION COMMONS
 EAST. SHOW THE FOLLOWING INFORMATION:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 4. SHT P1.02 WATER PIPING ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" AND NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS. - WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE ICE MAKER AND THE
 DISH WASHER PER SECTION 604.9.
  
 5. SHT P1.02 WATER PIPING ISOMETRIC. A
 FULL OPEN VALVE IS REQUIRED ON THE TOP
 OF ALL WATER DOWN-FEED PIPES. SECTION
 606.1(4).
  
 6. SHT P1.02 GENERAL NOTES #1. AIR
 CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved