Plan Review Stops For Permit 06081523 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-02-22 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-02-22 |
Time |
14:51 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-08-18 |
Time |
13:34 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2006-08-18 |
Time |
13:34 |
Sent To |
|
|
Notes |
2006-08-18 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL AS REQUIRED BY DCA RULE 9B-72 | | FOR FLAT ROOF SYSTEM TO BE INSTALLED. | | SEE ATTACHED COPY OF CITY POLICY FOR | | RE-ROOFING PERMITS AND PROVIDE ALL THE | | INFORMATION REQUESTED. | | | | 2- FLAT ROOFS ASSEMBLIES TYPICALLY | | REQUIRE NAIL ENHANCING AT PERIMETER AND | | CORNER AREAS. READ PRODUCT APPROVAL | | GENERAL LIMITATIONS. IF GENERAL | | LIMITATION #7 REQUIRES RAS 117 | | CALCULATIONS TO BE PREPARED BY ANY OF | | THE PROFESIONALS LISTED IN SUCH | | LIMITATION, THEN PROVIDE SUCH | | CALCULATIONS WITH ORIGINAL SEAL AND | | SIGNATURE. IF RAS 117 CALCULATIONS ARE | | NOT REQUIRED TO BE DONE BYREGISTERED | | PROFESSIONALS, THEN PROVIDE SUCH | | CALCULATIONS OR USE PALM BEACH COUNTY | | PRESCRIPTIVE METHOD. | | NOTE: GENERAL LIMITATION #9 DOESN'T | | ALLOW NAIL ENHANCING, THEREFORE, SYSTEM | | MAY NOT BE USED IN THIS AREA. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (5610805-6712 |
|
|
|