2006-08-21 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06081404 |
| ADD: 2100 45TH STREET |
| CONT: ROOFING UNLIMITED & SHEET |
| METAL, INC. |
| TEL: (561)842-0075 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) ROOFING PERMIT SHOULD NOT HAVE BEEN |
| APPLIED FOR UNTIL THE BUILDING PERMIT |
| (06011121) IS ISSUED. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) THIS ROOF IS MISSING OR NOT IN |
| COMPLIANCE WITH THE FOLLOW ITEMS: |
| |
| _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| |
| ROOF HEIGHT. |
| |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| PITCH. |
| |
| _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| SYSTEM TO BE USED. |
| |
| _X__ THE SYSTEM PROVIDED HAS A LOW |
| PRESSURE FOR ZONE _3__ . |
| |
| _X__ THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER |
| RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| ___THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| FASTENING ALLOWED. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |