Plan Review Details - Permit 06081397
Plan Review Stops For Permit 06081397
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-14 Cont ID  
Sent By shill Date 2007-03-14 Time 17:30 Rev Time 0.00
Received By shill Date 2007-03-14 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-20 Cont ID  
Sent By shill Date 2007-02-20 Time 12:52 Rev Time 0.00
Received By shill Date 2007-02-20 Time 12:52 Sent To  
Notes
2007-02-20 12:54:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.)SHOW THE EMERGENCY MEANS OF ESCAPE FBC R310.THE
 FRONT DOOR IS SHOWN WITH A SHUTTER; NO OTHER HINGED
 DOORS SHOWN.PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By amorse Date 2006-10-20 Time 07:52 Rev Time 0.00
Received By amorse Date 2006-10-20 Time 07:52 Sent To PC
Notes
2006-10-20 07:58:38 
  
 DENIED
  
 1) PLEASE NOTE THE CORRECTION MADE TO PLAN AS PREVIOUS
 COMMENT REGUARDING SHUTTER SPAN WAS NOT CORRECTED,
 PANEL CANNOT BE MOUNTED HORIZONTALLY BECAUSE IT WOULD
 EXCEED THE MAXIMUM ALLOWABLE SPAN FOR THE PRESSURE
 SHOWN (MAX SPAN 85") OPENING IS 93" + 6" EDGE DISTANCE
 = 99" THEREFORE PANEL SHALL BE INSTALLED VERTICALLY
  
 2) ALSO THE SHUTTER SPANSON THE SCHEDULE INDICATE
 THAT THE PANELS ARE MOUNTED HORIZONTALLY AS THEY ARE 2"
 LARGER THAN THE WIDTH PLEASE VERIFY THIS
  
 3) PRODUCT APPROVALS SHOW AN EDGE DISTANCE OF 31/2"
 THEREFORE THE PANEL LENGTH/SPANS SHOULD BE APPROX 7"
 LARGER THAN THE OPENING SIZE (HORZ FOR WIDTH VERT FOR
 HEIGHT)
  
 4) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-27 Cont ID  
Sent By amorse Date 2006-08-27 Time 14:49 Rev Time 0.00
Received By amorse Date 2006-08-27 Time 14:49 Sent To PC
Notes
2006-08-27 00:00:00 
  
 DENIED
  
 1)PROVIDE LOCATION OF OPENING WITH
 CLEAR PANELS AND THE DIRETION THAT THE
 PANELS WILL RUN. BE AWARE THAT THE MAX
 PANEL LENGTHS FOR CLEAR PANELS WITH
 PRESSURES OVER -40 ARE ALL BELOW 8'-0"
 FOR EXAMPLE OPENING #16 HORIZONTAL LEGTH
 IS 95" THE PRESSURE IS -53.48 THE MAX
 PANEL LENGTH IS 7'-2" OR 85" THEREFORE
 IT WILL NOT WORK
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:07 Sent To B
Notes
2007-03-10 15:07:30TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 10:11 Sent To B
Notes
2007-02-13 10:12:15TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-19 Cont ID  
Sent By adarroug Date 2006-10-19 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-10-19 Time 10:48 Sent To B
Notes
2006-10-19 10:49:01TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-27 Time   Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 14:41 Sent To  
Notes
2006-08-16 00:00:00TO "MISC" BOX#1