Plan Review Details - Permit 06081144
Plan Review Stops For Permit 06081144
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-18 Cont ID  
Sent By lursu Date 2006-08-18 Time 09:12 Rev Time 0.00
Received By lursu Date 2006-08-17 Time 13:45 Sent To  
Notes
2006-08-18 00:00:00EXT #0003 WAS ADDED FOR THIS UNIT
2006-08-17 00:00:00NEED AN ADDRESS EXTENSION FOR # 306

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-16 Cont ID  
Sent By btrobaug Date 2006-10-16 Time 11:11 Rev Time 1.00
Received By btrobaug Date 2006-10-16 Time 11:03 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By btrobaug Date 2006-08-21 Time 07:21 Rev Time 0.50
Received By btrobaug Date 2006-08-21 Time 07:09 Sent To E
Notes
2006-08-21 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 THIS APPLICATION WAS GIVEN TO THE
 CHIEF ELECTRICAL INSPECTOR TO DETERMINE
 COMPLIANCE WITH ARTICLE 230.2 2002 NEC.
  
 THE CHIEF ELECTRICAL INSPECTOR WILL NOT
 GRANT PERMISSION TO ADD AN ADDITIONAL
 SERVICE TO THIS BUILDING WITHOUT THE
 APPLICANT SHOWING CAUSE UNDER 230.2(A)
 THROUGH (D). A COMPLETE LOAD CALCULATION
 FOR THE EXISTING SERVICE, INCLUDING
 CALCULATIONS ON ALL SEPARATE BUSINESSES,
 ON THE SERVICE NOW SUPPLYING THE UNIT.
  
 A VOLTAGE DROP CALCULATION IS ALSO
 REQUIRED TO BE SUBMITTED, FROM FPL VAULT
 TO THE FIRST OVERCURRENT DEVICE ON THE
 LOAD SIDE OF THE METER IF GRANTED
 PERMISSION TO INSTALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 10:43 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 10:43 Sent To E
Notes
2006-10-10 10:44:15TO "BTROBAUG" DESK/RESUB