Plan Review Details - Permit 06080902
Plan Review Stops For Permit 06080902
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-27 Cont ID  
Sent By lursu Date 2006-09-27 Time 11:18 Rev Time 0.00
Received By lursu Date 2006-09-27 Time 11:18 Sent To  
Notes
2006-09-27 00:00:00EXT #0012 WAS CREATED FOR UNIT 600
2006-09-22 00:00:00NEEDS EXT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-22 Cont ID  
Sent By rmcdouga Date 2006-09-22 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2006-09-22 Time 16:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By rmcdouga Date 2006-08-24 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2006-08-24 Time 15:26 Sent To  
Notes
2006-08-24 00:00:00BUILDING DENIED
  
 1) FAC 61G1-16 REQUIRES THE FIRM'S
 LICENSE NUMBER IN THE TITLE BLOCK.
  
 2) SPECIFY THE TYPE OF CONSTRUCTION PER
 FBC 602.
  
 3) SPECIFY THE LEVEL OF ALTERATION PER
 2004 EXISTING BUILDING CODE 301.5.
  
 4) IF THIS IS A TYPE I OR II
 CONSTRUCTION COMBUSTIBLE MATERIALS MUST
 COMPLY WITH FBC 603.1. PLEASE REVISE THE
 NOTES FOR WOOD AND PLASTICS ON SHEET A4.
  
 5) SPECIFY THE LOCATIONS OF THE EXITS
 REQUIRED FOR THE OFFICE THAT WILL BE
 REVISED TO OPEN INTO THE ADJACENT TENANT
 SPACE.
  
 6) THE DOOR HARDWARE SHALL COMPLY WITH
 FBC 11-4.13.9.
  
 7) FIRE SPRINKLER PLANS WILL BE REQUIRED
 FOR ANY HEADS THAT REQUIRE RLOCATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By dpalmer Date 2006-10-19 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2006-10-18 Time 21:02 Sent To  
Notes
2006-10-18 21:03:11IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 20:26 Sent To  
Notes
2006-09-22 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE LICENSURE OF THE
 FIRM ON TITLE BLOCK IS STILL IN
 QUESTION. PLEASE KNOW, UPON CONVERSATION
 WITH TEH STATE'S LEGAL COUNSEL TO THE
 BOARD OF ARCHITECT'S, IT DOES NOT APPEAR
 A "DESIGN" OR "DRAFTING" FIRM MAY
 PROVIDE ARCHITECTURAL SERVICES
 PROVIDING SIGNED, AND SEALED PLANS.
 PLEASE SEE 481.229(1)(C), 481.223(1)(A),
 481.203(6).
 PLEASE CONTACT STATE'S LEGAL COUNSEL AS
 ONE SET OF PLANS ARE BEING RETAINED
 UNTIL THIS MATTER IS CLEARED.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE
 OR MR. DAVID MINACCI STATE'S PROSECUTING
 ATTORNEY TO THE BOARD OF ARCHITECT'S.
  
 ** THIS COMMENT CURRENTLY STANDS FOR ALL
 SHEETS AND FOR ALL REVIEWS WHETHER OR
 NOT COMMENT IS MADE BY THE OTHER
 REVIEWER(S).
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 08:19 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 07:28 Sent To  
Notes
2006-08-24 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE MISSING LICENS
 INFORMATION REQUIRED ON TITLE BLOCKS FOR
 PA AND FIRM AS LISTED. PLEASE SEE PRINT
 OUT FROM THE STATE WHERE ONLY AN
 APPLICATION HAS BEEN MADEONLY FOR THE
 MANUEL J DIAZ P.A. PLEASE KNOW, IF
 LISTING A COMPANY, INC, FICTICIOUS NAME
 ETC., A CERTIFICATE OF AUTHORIZATION
 NUMBER IS REQUIRED. PLEASE KNOWONCE
 THE CA IS OBTAINED THE TITLE BLOCKS MUST
 MATCH THE COMPANY/LISTING WITH THE STATE
 OF FLORIDA. WE HAVE ATTACHED THE PRINT
 OUT FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 PLEASE SEE FAC 61G1-16.004, FS 481.219
 PLEASE KNOW, HAVING APPLICATION WITH THE
 STATE DOES NOT AUTHORIZE USE OF COMPANY
 /PA.
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT(S)
 ARE MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE NOTES WHICH MENTIONS
 LOADS ON PANELS ARE "ASSUMED", AS A
 RESPONSIBLE ARCHITECT /OR ENGINEER THAT
 PERSON IS REQUIRED TO VERIFY ALL LOADS
 BEFORE CONSTRUCTION BEGINS. THOSE LOADS
 ARE THEN STATED ON PLANS AS REQUIRED.
 PLEASE SEE NOTE MENTIONS THE ELECTRICAL
 CONTRACTOR IS TO VERIFY BEFORE
 CONSTRUCTION, WHICH CAN BE DONE, HOWEVER
 VERIFICATION BEFORE PERMIT ISSUANCE IS
 REQUIRED AT THIS TIME.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC.
  
 3) NOTE: PLEASE SEE PLANS MENTIONS WORK
 PER THE LATEST EDITION OF THE
 CODES.PLEASE KNOW, THE LATEST EDITION
 HAS NOT YET BEEN ADOPTED BYT THE STATE.
 PLEASE BE SURE PLANS REFLECT THE
 FOLLOWING CODES AT A MIN 2003 NFPA-101,
 2002 NFPA-72, 2002 NFPA-70 (NEC), AND
 THE 2004 FBC.
  
 **THIS IS ONLY A NOTE FOR
 INFORMATIONAL PURPOSES ONLY.
 PLEASE KNOW, EVEN IN EXISTING
 BUILDINGS, COMPLIANCE WITH FBC CHAPTER
 13, 413 AND 415 MAY BE REQUIRED, WHICH
 WOULD DEPEND ON SCOPE OF WORK AND EXTENT
 OF REMODEL ETC.
 PLEASE KNOW THIS IS FOR INFORMATION
 PURPOSES ONLY AS THE SCOPE OF WORK ON
 THIS PARTICULAR PROJECT DOES NOT REQUIRE
 MEETING THE CURRENT 2004 FBC CHAPTER 13.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-22 Cont ID  
Sent By mawillia Date 2006-09-22 Time 10:36 Rev Time 0.00
Received By mawillia Date 2006-09-22 Time 10:36 Sent To  
Notes
2006-09-22 00:00:00*****PASSED W/PROVISO*****
  
  
  
  
  
 COMPLIANCE WITH FIRE PLAN REVIEW OF
 8/31/2006 HAS BEEN ADDRESSED PENDING THE
 MATTER WITH FAC AND F.S. IS APPROVED BY
 OTHER PLAN REVIEWERS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 10:55 Sent To  
Notes
2006-08-31 00:00:00***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL. PLEASE INDICATE SCOPE OF
 WORK IN THOSE AREAS.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 16:19 Sent To M
Notes
2006-12-06 16:19:42TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:43 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:42 Sent To M
Notes
2006-11-29 19:43:21SENT TO TOM GORDON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-17 Cont ID  
Sent By adarroug Date 2006-10-17 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-10-17 Time 11:32 Sent To  
Notes
2006-10-18 16:59:07TO "BOB"#9
2006-10-17 11:32:41WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 13:54 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 13:54 Sent To  
Notes
2006-09-20 00:00:00TO "BOB"#14
2006-09-18 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-07 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 08:40 Sent To  
Notes
2006-08-22 00:00:00TO "BOB"#18
2006-08-14 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-12-11 Cont ID  
Sent By tgordon Date 2006-12-11 Time 16:45 Rev Time 0.25
Received By tgordon Date 2006-12-11 Time 16:45 Sent To  
Notes
2006-12-11 16:46:40REVISION TO MECH. PLAN PAGE M-E2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-11-30 Cont ID  
Sent By tgordon Date 2006-11-30 Time 08:31 Rev Time 0.30
Received By tgordon Date 2006-11-30 Time 08:31 Sent To  
Notes
2006-11-30 08:32:43REVISION TO MECHANICAL PLANS PAGE M-E2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-10-19 Time 16:36 Rev Time 0.20
Received By tgordon Date 2006-10-19 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 10:30 Rev Time 0.40
Received By tgordon Date 2006-09-28 Time 11:46 Sent To  
Notes
2006-09-28 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE REGARDING
 LICENSE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-23 Cont ID  
Sent By tgordon Date 2006-08-23 Time 14:40 Rev Time 0.15
Received By tgordon Date 2006-08-23 Time 14:40 Sent To  
Notes
2006-08-23 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06080905 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 06:04 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 06:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-27 Cont ID  
Sent By kstevens Date 2006-09-27 Time 17:31 Rev Time 0.00
Received By kstevens Date 2006-09-27 Time 17:31 Sent To  
Notes
2006-09-27 00:00:00DENIED
 REFERENCE: FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED PER FAC 61G1-16.004(2) AND FS
 481.219. THIS IS REQUIRED IN THE TITLE
 BLOCK OF ALL SHEETS.
 ****RESPONSE NOTED, BUT THE CERTIFICATE
 OF AUTHORIZATION FOR IS NOT SHOWN. SEE
 COMMENT #1 OF THE ELECTRICAL PLAN REVIEW
 FOR INFORMATION ON THIS SUBJECT.
  
 2. SHT A2 PROVIDE A DETAIL FOR THE BREAK
 ROOM SINK SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS STILL REQUIRED:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH REQUIRED. CABINET DOORS
 NOT ALLOWED IN CLEAR FLOOR SPACE
 C/ 11-4.24.7 FAUCETS
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 16:30 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 16:30 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED PER FAC 61G1-16.004(2) AND FS
 481.219. THIS IS REQUIRED IN THE TITLE
 BLOCK OF ALL SHEETS.
  
 2. SHT A2 PROVIDE A DETAIL FOR THE BREAK
 ROOM SINK SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]