Plan Review Details - Permit 06080658
Plan Review Stops For Permit 06080658
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-09-23 Cont ID  
Sent By rnuquist Date 2006-09-23 Time 13:39 Rev Time 0.00
Received By rnuquist Date 2006-09-23 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-12 Cont ID  
Sent By btrobaug Date 2007-04-12 Time 08:53 Rev Time 0.50
Received By btrobaug Date 2007-04-12 Time 07:07 Sent To PC
Notes
2007-04-12 08:45:07 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE TWO METERS SHOWN ON THIS REVISION. REDRAW
 THE PLAN TO INDICATE SITE CONDITIONS.
  
 2} THE ATS IS NOW BEING SHOWN AS FED FROM THE METER,
 AND NOW BECOMES SERVICE EQUIPMENT. PROVIDE THE AIC
 RATING OF THIS SWITCH : PER 110.9 AND 110.10: OBTAIN
 THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH,
 INDICATING NUMBER OF POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE DISCONNECTED.
  
 4} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 5} THE ATS IS SHOWN IN A PVC BOX. DEPENDING ON HOW
 ACCESSIBLE THE DISCONNECTING MEANS ARE, THIS MAY NOT BE
 ALLOWED. PLEASE EXPLAIN THE PURPOSE OF THE PVC BOX.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 07:08 Rev Time 0.25
Received By btrobaug Date 2006-10-12 Time 07:00 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By btrobaug Date 2006-09-01 Time 07:58 Rev Time 0.50
Received By btrobaug Date 2006-09-01 Time 07:56 Sent To M
Notes
2006-09-01 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 2} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By mperson Date 2006-09-06 Time 11:34 Rev Time 0.15
Received By mperson Date 2006-09-06 Time 11:34 Sent To B
Notes
2006-09-06 00:00:00CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPROTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION
 (PARTICULARLY THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:29 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:29 Sent To E
Notes
2007-04-04 17:29:18TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 08:58 Sent To E
Notes
2006-10-10 08:58:40TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-03 Cont ID  
Sent By adarroug Date 2006-10-03 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-10-03 Time 15:11 Sent To Z
Notes
2006-10-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 10:42 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 10:42 Sent To E
Notes
2006-08-21 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-23 Cont ID  
Sent By rnuquist Date 2006-09-23 Time 13:40 Rev Time 0.00
Received By rnuquist Date 2006-08-11 Time 18:01 Sent To  
Notes
2006-08-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-12 Cont ID  
Sent By tgordon Date 2006-10-12 Time 09:12 Rev Time 0.20
Received By tgordon Date 2006-10-12 Time 09:12 Sent To B
Notes
2006-10-12 09:14:54*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR. MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 15:25 Rev Time 0.15
Received By tgordon Date 2006-09-05 Time 15:25 Sent To G
Notes
2006-09-05 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW NOTES.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-05 Cont ID  
Sent By kdfreema Date 2006-10-05 Time 14:44 Rev Time 0.00
Received By kdfreema Date 2006-10-05 Time 14:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By mmclean Date 2006-08-18 Time 16:19 Rev Time 0.00
Received By mmclean Date 2006-08-18 Time 16:19 Sent To I
Notes
2006-08-18 00:00:00DENIED,
 1. PLEASE MARK THE GENERATOR LOCATION
 CLEARLY ON THE TWO COPY OF SURVEYS.
 2. PLEASE PROVIDE THE DISTANCE OF THE
 PROPOSED GENERATOR FROM PROPERTY LINE.
  
 NOTE:SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720