Plan Review Details - Permit 06080639
Plan Review Stops For Permit 06080639
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-06 Cont ID  
Sent By jgomez Date 2007-08-06 Time 09:54 Rev Time 0.00
Received By jgomez Date 2007-08-06 Time 09:54 Sent To  
Notes
2007-08-06 09:56:26FOUNDATION REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-06-11 Cont ID  
Sent By jgomez Date 2007-06-11 Time 11:44 Rev Time 0.00
Received By jgomez Date 2007-06-11 Time 11:43 Sent To PC
Notes
2007-06-11 11:44:43ROOF FRAMING PLAN REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-14 Cont ID  
Sent By jgomez Date 2007-05-14 Time 14:08 Rev Time 0.00
Received By jgomez Date 2007-05-14 Time 12:24 Sent To PC
Notes
2007-05-14 13:15:28BUILDING REVIEW APPROVED WITH PROVISO:
 1-AS AGREED WITH CONTRACTOR, PROVIDE COMPLETE AND
 CORRECT INFORMATION FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT AND FEES.
  
 2- TRUSS PACKAGE TO BE SUBMITTED AT TIME OF
 INSPECTION.
  
 *** NOTES:
 A) ARCHITECT TO REVIEW AND APPROVE TRUSS PACKAGE.
 B) CORRECT INFORMATION ON TRUSS INDEX PAGE. THERE IS
 A DESIGNER OF RECORD ON THIS JOB. REVISEINFORMATION
 AS REQUIRED.
  
 3- ARCHITECT TO REVISECONNECTORS TORESIST ALL
 LOADS CALCULATED ON THE ENGINEERED TRUSSES. SEE
 ENGINEERED TRUSSES. SOME TRUSS GIRDERS HAVE HIGHER
 UPLIFT LOADS THAN THOSE SPECIFIED ON ARCHITECT'S PLANS.
 REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-14 Cont ID  
Sent By jgomez Date 2007-03-14 Time 10:45 Rev Time 2.00
Received By jgomez Date 2007-03-13 Time 17:27 Sent To Z
Notes
2007-03-14 10:58:10BUILDING REVIEW THIRD CHECKLIST:
 1-A) COMPLETE TRUSS PACKAGE NEEDS TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 B) TRUSS ENGINEER NEEDS TO HAVE ORIGINAL SIGNATURE
 AND SEAL IN ALL GENERAL DETAILS SHEETS SUBMITTED WITH
 TRUSS PACKAGE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE.
  
 2- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE KEY PLAN AND INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE. NEED TO
 CLEARLY IDENTIFY SPECIFIC PANEL MOUNTING CONDITIONS,
 DESIGN PRESSURES, EDGE DISTANCE, GLASS SEPARATION,
 ANCHOR TYPE AND SPACING AND STRUCTURE TO BE ATTACHED TO
 VERIFY COMPLIANCE WITH THE PROPOSED INSTALLATION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 STORM PANEL PRODUCT APPROVAL TO BE REVIEWED AND
 APPROVED BY DESIGNER OF RECORD.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS.TWODIFFERENT PRODUCT
 APPROVALS WERE SUBMITTED, BUT NONE OF THEM IS
 ACCEPTABLE.ONE OF THEM IS NOA 03-0605.05 WHICH
 EXPIRED ON 05/21/06. THE OTHER ONE NOA 03-0605.04 IS
 FOR 4", 6" AND 12" ONLY. NEED TO PROVIDE CORRECT AND
 CURRENT PRODUCT APPROVAL.
  
 B) SLIDING GLASS DOORS. NEED ONE WITH LEGIBLE
 DRAWINGS.ONLY ONE COPY WAS SUBMITTED. NEED TWO
 COPIES.
  
 C) ENTRY DOOR. IF USING SAME MODEL AS GARAGE SIDE
 DOOR, THEN CLEARLY INDICATE SO.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. LETTER SUBMITTED STATINGTHAT
 HE REVIEWED "ALL" PRODUCT APPROVALS IS NOT ACCEPTABLE.
 THIS STATEMENT DOESN'T IDENTIFY EXACTLY WHAT PRODUCT
 APPROVALS WERE REVIEWED. NEED TO IDENTIFY IN WRITING
 (NOT SIGNING AND SEALING) EACH SPECIFIC PRODUCT
 APPROVAL.
  
 5- NEED TO PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 THERMA-TRU CONSTRUCTION SERIES OUTSWING DOOR NOA
 01-0828.10.PRODUCT APPROVAL SUBMITTED REQUIRES 2X
 STRUCTURAL BUCK. SEE PRODUCT APPROVAL.ARCHITECT'S
 LETTER STATES THAT HIS ENGINEER TOLD HIM THAT 2X4 BUCKS
 ARE NOT REQUIRED. PRODUCT APPROVAL SHOWS 2XSTRUCTURAL
 BUCK DETAIL, THEREFORE DETAIL FOR 2X STRUCTURAL BUCK
 DETAIL ATTACHMENT IS REQUIRED.PROVIDE SUCH DETAIL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- ARCHITECT TO SPECIFY OPENING PROTECTION AS REQUIRED
 BY SEC. R309.1. NOTE IN DRAWING 1 OF 6STATING"GAR
 DOOR PROTECTION SHALL COMPLY WITH R309 2004 RES FBC.
 SEE NOA"IS NOT ACCEPTABLE.ARCHITECT NEEDS TO READ
 THIS CODE SECTION AND SPECIFY HOW IS COMPLYING WITH
 THIS CODE SECTION. ALSO,WHICH ONE IS THE NOA
 REFERENCED IN THIS NOTE?.
  
 7- ARCHITECT'S TRUSS LOADING ON DRAWING 1 OF 6 AND
 TRUSS LOADING SPECIFIED ON TRUSS DRAWINGS DON'T MATCH.
 REVISE AS REQUIRED.
  
 8- SHEET 5 OF 6:
 A) ARCHITECT STATES ON REVISED ITEM 13(B) THAT
 "(1)HTSM20 ISEQUIV TO (1)HETA20.THIS IS INCORRECT
 THIS TWO CONNECTORS ARE NOT EQUIVALENT. SEE CATALOG.
 REVISE AS REQUIRED.
  
 B) ARCHITECT TO REVIEW TRUSS DRAWINGS. CONNECTORS
 NEED TO RESIST THE CALCULATED UPLIFT AND LATERAL LOADS.
 REVISE ALL CONNECTORS AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) ARCHITECT TO REVIEW GIRDER TRUSSA-13G ABOVE
 INTERIOR BEARING WALL AND SPECIFY CONNECTORS TO RESIST
 LOADS AT DESIGNED BEARING POINTS.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 9- NEED RECORDED NOTICE OF COMMENCEMENT.SEC. 713.13
 FLORIDA STATUTE.
 NOTE: NOTICE OF COMMENCEMENTEXPIRESAFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-08 Cont ID  
Sent By jgomez Date 2007-01-08 Time 17:25 Rev Time 3.00
Received By jgomez Date 2007-01-08 Time 07:42 Sent To  
Notes
2007-01-08 17:28:33BUILDING REVIEW SECOND CHECKLIST:
 1- ARCHITECT NEEDS TO PROVIDE ALL REQUIRED INFORMATION
 IN THE TITLE BLOCK AS REQUIRED BYFLORIDA
 ADMINISTRATIVE CODE SEC. 61G1-16.004.
  
 2- IMPACT FEES STAMP STATES ADDITION TO BE 166SF, WHILE
 SHEET 2 OF 6 CALLS FOR NEW LIVING AREA TO BE 1528SF.
 BRING DRAWINGS TO PALM BEACH COUNTY TO REVISE IMPACT
 FEES STAMP WITH CORRECT ADDITIONAL SQUARE FOOTAGE.
 BRING BACK RE-STAMPED DRAWINGS AND COPY OF PAID RECEIPT
 IF ADDITIONAL FEES ARE DUE.
  
 3- SPECIFY ATTIC ACCESS SIZE AS REQUIRED BY SEC. R807
 2004 FLORIDA RESIDENTIAL CODE.
  
 4- LEVEL OF ALTERATION NEEDS TO BE IDENTIFIED AS
 REQUIRED BY SEC. 301.5 OF 2004 FLORIDA EXISTING CODE.
  
 5- ARCHITECT TO SPECIFY ALL DESIGN CRITERIA AS REQUIRED
 BY SEC. R301 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL
 DEAD LOADS, LIVE LOADS, ETC.
 ALSO, SHEET 3 OF 6 DOESN'T IDENTIFY THE BUILDING CODE
 AND SPECIFIC EDITION. IT'S ALSO MISSING THE DESIGN
 PRESSURES FOR WINDOW OPENINGS. ONLY DOORS DESIGN
 PRESSURES WERE GIVEN.
  
 6- PROVIDE TRUSS DRAWINGS COMPLETE PACKAGE REVIEWED AND
 APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION AS
 REQUIRED BY SEC. R802.10.1 2004 FLORIDA RESIDENTIAL
 CODE. SEE THIS SECTION TO MAKE SURE ALL REQUIRED
 INFORMATION IS SUBMITTED. THIS INFORMATION NO NEED TO
 BE SUBMITTED RIGHT AWAY, BUT BEFORE INSTALLATION TO
 AVOID DELAYS OR CONFLICTS.
  
 7- A) PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE KEY PLAN AND COMPLETE INSTALLATION SCHEDULE
 (SEE ATTACHED SAMPLE) OR ANY WAY THAT WILL PROVIDE ALL
 REQUIRED INFORMATION FOR PLAN REVIEW AS SHOWN ON
 INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 B) PRODUCT APPROVAL TO BE REVIEWED AND APPROVED IN
 WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- ENERGY CALCULATIONS:
 A) PROVIDE SPECIFICATIONS/CALCULATIONS SHOWINGOF
 HOW R2.5 INSULATION IS ACHIEVED ON CONCRETE SLAB.
  
 B) CEILING FANS CREDIT IS TAKEN. THEREFORE, SPECIFY
 SIZE OF CEILING FANS ON ALL ROOMS AS REQUIRED BY TABLE
 13-607.1.A.1 2004 FBC. ALL CEILINGS FANS MUST BE
 INSTALLED FOR INSPECTION.
  
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS. NEED CURRENT NOA FOR 8" LINTELS.
 ONE SUBMITTED IS FOR 4", 6" AND 12" LINTELS NOT FOR 8".
 SEE PLANS FOR LINTEL SIZE SPECIFIED.
  
 B) SLIDING GLASS DOORS. SEE PLANS FOR SIZE.
  
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON TRUSS
 CONNECTOR SCHEDULE AND IN ALL DETAILS AND NOTES. SEE
 PLANS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING EACH CONNECTOR ONLY. NO NEED TO SUBMIT THE
 WHOLE LONG REPORT.
  
 D) ENTRY DOOR.
  
 E) SINGLE HUNG WINDOWS. NOA 05-0112.01 SUBMITTED
 EXPIRED ON 10/08/06. NEED CURRENT ONE.
  
 F) GARAGE SIDE AND REAR DOOR. NOA 02-0805.03
 SUBMITTED IS FOR DOUBLE DOORS ONLY. NEED PRODUCT
 APPROVAL FOR SINGLE DOORS AS SHOWN ON PLANS.
  
 G) 12' WIDE X 7' HIGH GARAGE DOOR. NOA 03-0430.04
 SUBMITTED IS FOR 9' WIDE DOORS ONLY.
  
 10- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR GARAGE
 SIDE AND REAR DOOR. IF PRODUCT APPROVAL REQUIRES 2X
 STRUCTURAL BUCK, THEN PROVIDE SUCH DETAIL. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 11- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- SPECIFY GARAGE OPENING PROTECTION AS REQUIRED BY
 SEC. R309 2004 FLORIDA RESIDENTIAL CODE.
  
 13- SHEET 5 OF 6:
 A) SPECIFY UPLIFT LOADS AND CONNECTORS AT THE ENDS
 OF GIRDER TRUSS ABOVE INTERIOR BEARING WALL.AND,
 SPECIFY STUDS TO RECEIVE GIRDER TRUSS BY BEDROOM #3.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) SPECIFY TRUSS CONNECTORS FOR TRUSSES RESTING ON
 EXISTING MASONRY WALL.HETA CONNECTORS NEED TO BE
 EMBEDED IN CONCRETE. NEED RETROFIT CONNECTOR. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) SEE CURRENT SIMPSON CATALOGUE AND REVISE ALL
 SPECIFIED CONNECTORS IF NUMBER AND TYPE OF FASTENERS
 DON'T MATCH THE ONES TESTED AND PUBLISHED BY THE
 MANUFACTURER'S. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR FASTENERS THAT DIFFER FROM THOSE ALREADY
 PUBLISHED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 SEE ALL CONNECTORS SPECIFIED THROUGHOUT THIS PAGE AND
 REVISE AS REQUIRED.CONNECTORS ARE TAKEN FROM SIMPSON
 2004 CATALOGUE AND USP 2003 CATALOGUE. UPDATE AS
 REQUIRED. SEE COMMENTS ON PLANS.
  
 D) REVISE CONNECTOR B. IT CALLS FOR (2) HETA20 AT
 EACH END OF TRUSS. THIS CONNECTOR CAN'T BE INSTALLED ON
 WOOD TO WOOD CONNECTION. ALSO, IT CAN'T BE INSTALLED ON
 EXISTING WALL. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- DRAWINGS SHOWREVISED SQUARE FOOTAGE AREAS.
 PERMIT VALUATION WAS UPDATED ACCORDINGLY. THEREFORE,
 OWES $542.74 FOR PERMIT VALUATION AND RADON FEES.
  
 15- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED.SEC. 713.13 FLORIDA STATUTES.
 NEED RE-RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By jgomez Date 2006-09-19 Time 16:56 Rev Time 5.00
Received By jgomez Date 2006-09-19 Time 16:56 Sent To  
Notes
2006-09-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- A) ARCHITECT NEEDS TO PROVIDE ALL HIS
 INFORMATION IN THE TITLE BLOCK AS REQ'D
 BY FLORIDA ADMINISTRATIVE CODE SECTION
 61G1-16.004. SEE ATTACHED COPY.
 B) ARCHITECT NEEDS TO WRITE DOWN DATE
 WHEN SIGNING AND SEALING PLANS AS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE.
  
 2- PROVIDE COPY OF THE IMPACT FEES PAID
 RECEIPT.
  
 3- ALL BEDROOMS WINDOWS DON'T COMPLY
 WITH EGRESS REQUIREMENTS. SEC. R310 OF
 2004 RESIDENTIAL CODE.
  
 4- SITE PLAN ON SHEET A-1 IS NOT TO
 SCALE.
  
 5- A) MISSING ONE ELEVATION. PROVIDE
 EAST ELEVATION. EAST ELEVATION SHOWN ON
 PLANS CORRESPONDS TO NORTH ELEVATION.
 REVISE AS REQUIRED.
 B) ROOF SHOWN ON ELEVATIONS DON'T MATCH
 ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 6- SPECIFY ALL SIZES & TYPES OF WINDOWS
 AND GLASS BLOCK. SOME WINDOWS ARE
 MISSING THIS INFORMATION.
  
 7- SPECIFY SAFETY GLASS FOR WINDOW ABOVE
 TUB ON EAST ELEVATION. SEC. R308.4 2004
 RESIDENTIAL CODE.
  
 8- PROVIDE COMPLETE STRUCTURAL DETAIL
 SHOWING HOW ARE SLIDING GLASS DOORS AT
 FAMILY ROOM MULLED TOGETHER. AND HOW IS
 MULLION ATTACHED TO STRUCTURE AT TOP AND
 BOTTOM. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 9- PLANS ARE NOT CLEAR. NEED TO PROVIDE
 WALL LEGEND TO IDENTIFY TYPE OF WALLS,
 WHAT'S NEW, WHAT'S EXISTING AND WHICH
 WALLS ARE TO BE REMOVED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 10- PROVIDE STRUCTURAL DETAILS/SPECS
 SHOWING STRUCTURAL SUPPORT WHEN WALLS
 ARE REMOVED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- PROVIDE COMPLETE AND CORRECT BEAM,
 LINTEL, COLUMN AND FOOTING SCHEDULE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 12- PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB. THERE ARE MANY DETAILS THAT
 DON'T APPLY TO THIS JOB.
 ALSO, THERE ARE SOME REPETITIVE DETAILS
 WITH INFORMATION THAT DOESN'T MATCH.
  
 13- PROVIDE DETAIL FOR STEP UP AT DINING
 ROOM. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 14- CLARIFY WHY ARE THERE NO DOORS TO
 ENTER BATHROOM ON EAST SIDE.SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- PROVIDE SMOKE DETECTORS IN BEDROOMS
 AS REQ'D BY SEC. R313 2004 RES. CODE.
  
 16- SPECIFY ATTIC ACCESS AS REQUIRED BY
 SEC. R807 2004 RESIDENTIAL CODE.
  
 17- ARCHITECT TO IDENTIFY LEVEL OF
 ALTERATION AS REQUIRED BY SECTION 301.5
 OF 2004FLORIDA EXISTING BUILDING CODE.
  
 18- ARCHITECT TO SPECIFY BUILDING CODE
 AND ALL DESIGN CRITERIA AS REQUIRED BY
 SEC. R301 2004 RESIDENTIAL CODE.
  
 19- PROVIDE TRUSS DRAWINGS REVIEWED AND
 APPROVED BY THE ARCHITECT PRIOR TO
 INSTALLATION AS REQUIRED BY SEC.
 R802.10.1 2004 RESIDENTIAL CODE.
  
 20- ARCHITECT TO SPECIFY CONCRETE SLAB
 JOINTS AS REQUIRED BY SECTION R506.2.4
 2004 RESIDENTIAL CODE.
  
 21- ARCHITECT TO SPECIFY CALCULATED
 DESIGN PRESSURES FOR DOORS, WINDOWS AND
 GARAGE DOOR. SEC. R301 2004 RES. CODE.
  
 22- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING KEY PLAN AND A
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE
 ON CITY IMPLEMENTATION STANDARD FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION.
  
 23- PROVIDE CORRECT ENERGY CALCULATIONS.
 NEED TO COMPLETE FORM 600A-04. FORM
 600C-04 SUBMITTED IS FOR ADDITIONS OF
 600S.F. OR LESS ONLY.
  
 24- AS REQUIRED DCA RULE 9B-72, PROVIDE
 PRODUCT APPROVAL FOR:
 A) WINDOW MULLIONS. PRODUCT APPROVAL
 SUBMITTED IS EXPIRED. NEED UPDATED NOA.
 B) PRECAST LINTELS. ONE SUBMITTED IS
 FOR 4", 6" & 12". THESE LINTELS ARE NOT
 USED. NEED CURRENT NOA FOR 8" LINTELS.
 C) SLIDING GLASS DOORS.
 D) GLASS BLOCK.
 E) ALL STRUCTURAL CONNECTORS SPECIFED
 ON TRUSS ANCHOR SCHEDULE AND DETAILS.
 F) MULLION FOR SLIDING GLASS DOORS.
  
 25- ARCHITECT TO REVIEW AND APPROVE IN
 WRITTING ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 26- ACCORDING TO WALL SECTION ON SHEET
 A-5 THE ROOF PITCH IS 3:12. NEED TO
 SPECIFY DOUBLE LAYER OF UNDERLAYMENT AS
 REQ'D BY SEC. R905.27 2004 RES. CODE.
  
 27- PLEASE RETURN REVIEWED SET TO
 EXPEDITE REVIEW PROCESS.
  
 28- SPECIFY BEAM/HEADER ABOVE GLASS
 BLOCK IN DINING ROOM AND HOW IS
 STRUCTURE SUPPORTED WHILE REMOVING WALL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 29- PLANS ARE MISSING A LOT OF
 DIMENSIONS. PROVIDE ALL DIMENSIONS
 INCLUDING DIMENSIONS BETWEEN KITCHEN AND
 FAMILY ROOM. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 30- SPECIFY GARAGE OPENING PROTECTION AS
 REQUIRED BY SEC. R309 2004 RES. CODE.
  
 31- CLARIFY IF THERE IS A STEP FROM
 GARAGE FINISH FLOOR TO INTERIOR OF HOUSE
 FINISH FLOOR. PLANS DON'T PROVIDE THIS
 INFORMATION. SECTION 106.1.2 OF CITY
 AEMNDMENTS TO FBC 2004.
  
 32. REVISE STRUCTURAL GARAGE DOOR BUCK
 DETAIL TO MATCH ACTUAL CONDITIONS. SEE
 FLOOR PLAN AND REVISE AS REQUIRED.
  
 33- SHEET A-2:
 A) THERE IS A 3'X3' CONCRETE PAD IN
 FOUNDATION PLAN. WHAT IS THIS FOR? IS
 THIS TO SUPPORT A COLUMN?. SPECIFY
 COLUMN AND CONCRETE PAD REINFORCEMENT.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 B) HOW IS BEAM AT NEW PORCH AREA
 SUPPORTED? ARE THERE ANY CONCRETE PADS
 REQUIRED TO SUPPORT CONCRETE COLUMNS?.
 PROVIDE COMPLETE INFORMATION. SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) SIZE OF FOOTING DOESN'T MATCH WALL
 SECTIONS. PROVIDE COMPLETE FOOTING SIZES
 FOR ALL FOOTING TYPES SHOWN ON PLAN.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 34- SPECIFY WHAT IS THE FINISH FLOOR AT
 NEW PORCH. CONCRETE? NO INFORMATION
 GIVEN. LOOK AT ELEVATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 35- SHEET A-4:
 A) ROOF FRAMING PLAN IS WRONG AND
 INCOMPLETE. SEE EXTERIOR ELEVATIONS.
 B) SPECIFY CALCULATED UPLIFT LOADS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 C) SPECIFY ALL BEARING WALLS. SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) PROVIDE TRUSS ANCHOR SCHEDULE.
 E) DIMENSIONS DON'T MATCH PLANS.
  
 36- SHEET A-5:
 A) REVISE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS TO COMPLY WITH SECTION
 R613.6.2 2004 RESIDENTIAL CODE.
 B) SIZE OF FASTENER SPECIFIED FOR
 WINDOW ATTACHMENT DOESN'T WORK ACCORDING
 TO SIZE OF BUCK SPECIFIED. REVISE.
 C) NOTE AT BOTTOM OF TYPICAL WALL
 SECTION REGARDING WINDOW/DOOR BUCKS
 DON'T MATCH DETAILS SHOWN ON TOP OF
 PAGE. REVISE AS REQUIRED..
 D) SIZE OF TYPICAL WALL SECTION
 DOESN'T MATCH FOUNDATION PLAN. REVISE AS
 REQUIRED.
 E) DETAIL F: REVISE HUGHES CONNECTORS.
 THIS COMPANY IS OUT OF BUSINESS.
 F) LINTEL DETAILS. PROVIDE INFORMATION
 REGARDING THE ADDITIONAL REINFORCEMENT.
 G) SIMPSON H10 CONNECTOR SPECIFIED ON
 TYP. WALL SECTION IS FOR WOOD TO WOOD
 CONNECTION. NEED WOOD TO MASONRY
 CONNECTOR. SEE CURRENT CATALOGUE FOR
 PROPER CONNECTOR.
 H) TYP. WALL SECTION: WHAT LOCAL CODE
 CALLS FOR 2% CLORDANE SOLUTION? CLARIFY
 NOTE FOR CONCRETE SLAB.
  
 37- SHEET A-6:
 A) UPDATE ALL CONSTRUCTION DOCUMENT
 NOTES AND ALL GENERAL CONSTRUCTION
 NOTES. SEE 2004 FLORIDA BUILDING AND
 RESIDENTIAL CODES TO REFERENCE CORRECT
 CODE STANDARDS AND EDITIONS.
 B) PROVIDE INFORMATION FOR ADDITIONAL
 LINTEL REINFORCEMENTS. SEE LINTEL
 DETAILS. SEC. 106.1.2 CITY AMENDMENTS.
 C) WALL SECTION CALLS FOR SPANISH 'S'
 TILE. REVISE AS REQUIRED. ALS. THIS WALL
 SECTION DOESN'T MATCH OTHER WALL SECTION
 SHOWN ON SHEET A-5. REVISE AS REQUIRED.
  
 38- SHEET A-8:
 A) UPDATE ALL STRUCTURAL NOTES. SEE
 2004 FLORIDA BUILDING AND RESIDENTIAL
 CODES FOR CORRECT CODE STANDARDS AND
 EDITIONS. REVISE ALL NOTES AS REQUIRED
 INCLUDING DESIGN WIND LOADS AND ROOF
 LOADS.
 B) PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB.
  
 39- OWES $139.57 FOR UPDATED PERMIT
 VALUATION AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-07 Cont ID  
Sent By btrobaug Date 2007-03-07 Time 13:08 Rev Time 0.33
Received By btrobaug Date 2007-03-07 Time 13:08 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 12:19 Rev Time 0.33
Received By btrobaug Date 2006-12-20 Time 12:02 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By btrobaug Date 2006-08-17 Time 10:09 Rev Time 0.50
Received By btrobaug Date 2006-08-17 Time 07:36 Sent To P
Notes
2006-08-17 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE PANEL SCHEDULES AND RISERS
 ON SHEET A5 AND E2, DECIDE WHICH ONE IS
 CORRECT AND REMOVE THE OTHER.
  
 2} PLEASE COMBINE ALL DRAWINGS PERTINENT
 TO THE ELECTRICAL SCOPE ON THE SAME
 SHEET OR CONTINUOUS PROGRESSION OF
 SHEETS. 106.1.3 FBC, AS AMENDED.
  
 3} SEE 220.30 FOR REQUIRED ITEMS FOR THE
 LOAD CALCULATION, INCLUDE ALL.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. SEE SHEET
 E2.
  
 5} THE GARAGE RECEPTACLES ARE REQUIRED
 TO BE GFI PROTECTED PER 210.8(A)(2).
  
 6} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 7} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI.
  
 8} INDICATE THE REQUIRED BATH CIRCUITS
 ON THE PANEL SCHEDULE. 210.11(C)(3).
  
 9} INDICATE THE REQUIRED ARC FUULT
 CIRCUITS ON THE PANEL SCHEDULE. 210.12.
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 15:28 Sent To M
Notes
2007-12-07 15:28:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 14:12 Sent To M
Notes
2007-11-15 14:12:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 08:42 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 08:42 Sent To M
Notes
2007-11-07 08:43:13TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 14:34 Sent To M
Notes
2007-05-04 14:34:40TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 16:57 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 16:57 Sent To Z
Notes
2007-04-25 16:58:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 08:23 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 08:23 Sent To E
Notes
2007-03-19 08:24:06TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 13:18 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 13:18 Sent To Z
Notes
2007-02-27 13:18:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 11:57 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 11:57 Sent To E
Notes
2006-12-15 11:57:36TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 11:01 Sent To Z
Notes
2006-12-06 11:01:26TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 16:39 Sent To E
Notes
2006-08-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-19 Cont ID  
Sent By jgomez Date 2006-09-19 Time 16:57 Rev Time 0.00
Received By jgomez Date 2006-08-11 Time 18:48 Sent To  
Notes
2006-08-11 00:00:00TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-07-14 Cont ID  
Sent By rkussner Date 2008-07-14 Time 10:22 Rev Time 0.00
Received By rkussner Date 2008-07-14 Time 10:22 Sent To  
Notes
2008-07-14 10:25:417/14/08RAK- SENT TO MC

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-12-10 Cont ID  
Sent By tgordon Date 2007-12-10 Time 13:39 Rev Time 0.35
Received By tgordon Date 2007-12-10 Time 13:39 Sent To  
Notes
2007-12-10 13:40:48REVISION TO MECHANICAL PLAN, ENERGY CAL'S. AND COOLING
 LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-11-29 Cont ID  
Sent By tgordon Date 2007-11-29 Time 09:11 Rev Time 0.35
Received By tgordon Date 2007-11-29 Time 09:11 Sent To  
Notes
2007-11-29 09:36:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR
 26,339 TOTAL COOLING BTU'S. FOR SYSTEM ONE, MECHANICAL
 PLANS SUBMITTED ARE SHOWING 33,600 TOTAL COOLING BTU'S.
 FOR SYSTEM ONE. THE PLANS CAN ONLY CALL FOR 15% MORE
 TOTAL BTU'S. THAN THE COOLING LOAD CAL'S.. A 2.5 TON
 SYSTEM MAY MEET THIS REQUIREMENT, SEE ATTACHED ARI
 PRINT OUT. SEE 2004 FBC 13-607.1.ABC.1.1.
  
 2)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) THE JOB ADDRESS MUST APPEAR ON ALL PLANS, SEE 2004
 WPB AMEND. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 11:27 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 11:27 Sent To  
Notes
2007-11-13 11:32:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) MECHANICAL PLAN ON FILE IS SIGNED AND SEALED BY AN
 ARCHITECT (MICHAEL CLARK) SO ONLY HE MAY MAKE REVISIONS
 TO THEM, SEE FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 15:45 Rev Time 0.20
Received By tgordon Date 2007-05-04 Time 15:45 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 16:41 Rev Time 0.30
Received By tgordon Date 2007-03-07 Time 16:41 Sent To P
Notes
2007-03-07 16:43:01*** PROVISO ***
 1) DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R 309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-20 Cont ID  
Sent By tgordon Date 2006-12-20 Time 16:01 Rev Time 0.30
Received By tgordon Date 2006-12-20 Time 16:01 Sent To P
Notes
2006-12-20 16:13:33*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW, ENTER ALL REQUIRED
 INFORMATION ON ENERGY CALCULATIONS, SEE HIGH LIGHTS ON
 ENERGY CAL'S.
  
 2) EQUIPMENT LISTING ON MECHANICAL PLANS IS DIFFICULT
 TO READ. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1.
  
 3) PLEASE SHOW ON THE MECHANICAL PLANS THE SIZE OF THE
 RETURN AIR GRILL TO THE AIR HANDLER.
  
 4) PLEASE PROVIDE FOR RETURN AIR TO BEDROOMS.BALANCED
 RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
 .

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By tgordon Date 2006-09-12 Time 10:33 Rev Time 0.30
Received By tgordon Date 2006-09-12 Time 10:33 Sent To B
Notes
2006-09-12 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS CAN NOT BE ON
 FORM 600C-04 AS THE ADDITION IS OVER 600
 SQ. FT.. WHEN SUBMITTING CORRECT FORM
 ENTER ALL REQUIRED INFORMATION AND
 SIGNATURES.
  
 2) NO MECHANICAL PLANS SUBMITTED, PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER
 2004 FBC AMEND. WPB 106.3.5.4 #10.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-05-11 Cont ID  
Sent By mperson Date 2007-05-11 Time 10:04 Rev Time 0.33
Received By mperson Date 2007-05-11 Time 10:04 Sent To B
Notes
2007-05-11 10:14:52****************PROVISO****************
 FBC-2004 PLUMBING
 A} 802.1.6 THE DOMESTIC DISHWASHER SHALL DISCHARGE
 INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE
 KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
 B} 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. NOTE: CLEANOUT FOR THE
 WASHING MACHINE TO BE LOCATED AT 4' A.F.F.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-13 Cont ID  
Sent By jleech Date 2007-03-13 Time 07:43 Rev Time 0.00
Received By jleech Date 2007-03-13 Time 07:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By jleech Date 2006-12-27 Time 09:03 Rev Time 0.00
Received By jleech Date 2006-12-27 Time 09:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By jleech Date 2006-09-12 Time 09:09 Rev Time 0.00
Received By jleech Date 2006-09-12 Time 09:09 Sent To M
Notes
2006-09-12 00:00:00DENIED;
 1.TWO SANITARY RISER DIAGRAMS DRAWN,
 NEITHER ARE CORRECT.
 A-6 1/2 BATH IS SHOWN AS A FULL BATH.
 MASTER BATH LAVATORIES WILL BE ON ONE
 VENT NOT TWO AS SHOWN.
 A-7 AUTOMATIC WASHING MACHINE TO BE 3"
 PER.406.3 MASTER BATH TUB AND SHOWER NOT
 VENTED.ETC.
 2.1/2 BATH, MUST HAVE 18" IN FRONT OF
 TOILET TO MEET CODE, LAVATORY WILL BE IN
 THE WAY.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2007-05-02 Cont ID  
Sent By adavila Date 2007-05-02 Time 14:47 Rev Time 0.00
Received By adavila Date 2007-04-30 Time 14:04 Sent To I
Notes
2007-05-02 14:48:06PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-03-15 Cont ID  
Sent By adavila Date 2007-03-15 Time 17:12 Rev Time 0.00
Received By adavila Date 2007-03-15 Time 15:34 Sent To I
Notes
2007-03-15 17:16:56PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROVIDE HEIGHT DIMENSIONS OF PROPOSED ADDITION.
  
 2.PROVIDE SETBACK DIMENSIONS FROM PROPERTY LINE TO
 A/C UNIT.
  
 3.PEDESTRIAN WALKWAY SHALL BE SHOWN ON BOTH COPIES OF
 THE SURVEY.
  
 4.PROVIDE DIMENSIONS, INCLUDING SETBACK DIMENSIONS,
 OF PEDESTRIAN WALKWAY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By mmclean Date 2006-12-13 Time 14:43 Rev Time 0.00
Received By mmclean Date 2006-12-13 Time 14:43 Sent To I
Notes
2006-12-13 14:47:02DENIED,
 1. PLEASE SHOW THE PROPOSED WORK ON THE TWO COPIES OF
 SURVEYS (LEGAL DOCUMENT).
 2. SITEPLANS DOES NOT PROVIDE THE SETBACK OF THE THE
 EXISTING AND PROPOSED FRONT SETBACK. (PLEASE SHOW THE
 PROPOSED ON SURVEYS).
 3. THE DIMESION FOR THE NEW DRIVEWAY IS NOT SHOWN ON
 THE SITEPLAN, PLEASE SHOW ON SURVEYS.
 4. SITEPLANS DOES NOT SHOW THE A/C UNIT.
 5. SITEPLANS HAS INSUFFICIENT INFORMATION, PLEASE SHOW
 ON THE TWO COPIES OF SURVEYS WITH SETBACKS AND
 DIMENSIONS (DRIVEWAY).
 6. PLEASE PROVIDE THE REAR SETBACK OF THE PROPOSED
 ADDITION.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-12 Cont ID  
Sent By mmclean Date 2006-08-12 Time 11:16 Rev Time 0.00
Received By mmclean Date 2006-08-12 Time 11:16 Sent To I
Notes
2006-08-12 00:00:00DENIED,
 1. THE PROPOSED ADDITION IS LINED UP
 WITH THE EIXISTING STRUCTURE (SETBACK
 10FT) AND THE WRITTEN SETBACK SHOWS
 (7.5FT). PLEASE SHOW CORRECTLY ON THE
 TWO COPY OF SURVEY THE SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720