2006-08-31 00:00:00 | ****** UNSAT ****** |
| |
| 1) NOTE; PLEASE SUBMIT AIC RATINGS FOR |
| ALL EQUIPMENT. NOTE MENTIONS 22K FOR |
| MAIN DISCONNECT, HOWEVER INFORMATION ON |
| RISER DOES NOT SHOW A MAIN DISCONNECT. |
| PLEASE ALSO INCLUDE ALL OTHER SERVICE |
| EQUIPMENT RATINGS. |
| 110.9 |
| FBC 106.1.2 |
| |
| 2) NOTE; PLEASE CORRELATE PLANS AND |
| RISER. RISER SHOWS WHAT APPEARS TO BE A |
| 300A SERVICE, YET PLANS INDICATE 200A'S. |
| |
| 230.70 , 215.5, 230.2 ETC |
| |
| 3) NOTE: PLEASE SEE RISER DOES NOT |
| INDICATEANY SEC'S . PLEASE COMPLETE |
| RISER. |
| 310.15B6,310.16,240.4 ETC |
| |
| 4) NOTE: PLEASE SEE RISER SHOWS 1/0'S |
| FOR FEEDERS TO SUB PANEL, "A", YET THE |
| MAIN BREAKER BEING SHOWN FEEDING THIS |
| PANEL IS 200A'S. 1/0'S ARE NOT LARGE |
| ENOUGH. |
| 310.16, 240.4 |
| |
| 5) NOTE: PLEASE PROVIDE INFORMATION FOR |
| MAIN/PANEL/DISCONNECT ON RISER WHICH |
| FEEDS TWO SUB PANELS. PLEASE SEE 230.70 |
| AS THERE CAN BE NO MORE THAN 6 SPACES |
| FOR EQUIPMENT AND NO MORE THAN 6 MAINS |
| FOR SERVICE. |
| |
| 6) NOTE: PLEASE INDICATE THE SIZE OF THE |
| METER CAN BEING PROVIDED. |
| 106.1.2 FBC |
| |
| 7) NOTE: PLEASE CORRELATE RISER AND |
| PANELS, AS PANEL FOR CABANA IS BEING |
| SHOWN ONE SIZE AND RISER SHOWS ANOTHER. |
| 106.1.2 FBC |
| |
| 8) NOTE: PLEASE SEE LOADS SHOWN FOR A/C |
| INDICATES COMPRESSOR LOAD FOR THE 10KW, |
| WHERE THE AHU, IS THE LARGER OF THE TWO, |
| THE CALCULATIONS SHOULD INDICATE THE |
| AHU. |
| 220.21., 220.31 |
| |
| 9) NOTE; PLEASE SEE MISSING GROUNDING |
| ELECTRODE SYSTEM AT THE DETACHED |
| BUILDING. |
| 250.32, 250.50. |
| |
| 10) NOTE: ONCE RISER HAS BEEN CORRECTED |
| FOR THE SIZE OF PANELS ETC AT CABANA, |
| PLEASE BE SURE TO CLEARLY INDICATETHE |
| MAIN DISCONNETC AT THE DEACHED BUILDING |
| MEETING 225.31-225.39. |
| PLEASE KNOW, SINCE PLANS FOR THE CABANA |
| HAVE NOT BEEN SUBMITTED AT THIS TIME, |
| THIS CAN NOT BE VERIFIED FOR CODE |
| COMPLIANCE. |
| |
| 11) NOTE: PLEASE SUBMIT AND COMPLETE |
| PLANS FOR CABANA IF PART OF THIS PERMIT APPLICATION |
| ETC. PLEASE KNOW, NO REVIEW |
| COULD BE DONE FOR CABANA , AND THERE MAY |
| BE COMMENTS TO FOLLOW. |
| 106.1.2 FBC, 2002 NEC. |
| |
| 12) NOTE: PLEASE SEE 422.11(E)3,AS THE |
| OCP FOR THE WATER HEATER CAN NOT EXCEED |
| 150%. PLEASE SEE 60A OCP IS BEING SHOWN |
| ON A 5KW UNIT. |
| PLEASE ADJUST. |
| 106.1.2 |
| |
| 13) NOTE: PLEASE SEE CONDUCTOR SIZE |
| BEING SHOWN ON PANEL SCHEDULE FOR RANGE |
| DOES NOT CLEARLY INDICATE THE SIZE. |
| SEEMS TO CONTAIN A MISPRINT. |
| 310.16,240.4 |
| |
| 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| FOR ALL CIRCUITS TO THE ROOMS AND AREAS |
| IN WHICH THEY FEED. CIRCUITS ARE TO BE |
| SPECIFIC. IE: LIVING RM, KITCHEN LTS, |
| ETC. |
| 408.6. |
| 106.1.2 |
| ** IT IS KNOWN TO THIE OFFICE THAT THE |
| CIRCUITING WILL BE REVISED AT A LATER |
| DATE, HOWEVER THE MINIMUM IS REQUIRED AT |
| THIS TIME. |
| |
| 15) NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 FOR 2' OF WALL SPACE OR MORE. |
| |
| 16) NOTE: PLEASE SEE NOTE #7 ON PLANS |
| WHICH REFERENCES A CODE IN THE NEC, |
| PLEASE KNOW, HOWEVER THIS MUST BE FROM |
| AN OLDER NEC, AS THE CURRENT NFPA-70 IN |
| EFFECT DOES NOT CORRELATE WITH THIS |
| ARTICALE BEING REFERENCED. |
| PLEASE ADJUST. |
| |
| 17) NOTE: PLEASE SEE PLANS ARE MISSING |
| THE DISCONNECTS REQUIRED FOR THE A/C CU |
| AND THE SPRINKLER PUMP/IRRIGATION. |
| 440.11, 430.31 |
| |
| 18) NOTE: PLEASE SEE MISSING EGRESS |
| LIGHTING CONTROL AT MASTER BEDRM TO |
| AREAS WITH GRADE LEVEL ACCESS. |
| 210.70, LS 101 7.8 |
| |
| 19) NOTE: PLEASE KNOW, ALL FANS AND LT |
| KITS WILL BE REQUIRED TO BE INSTALLED |
| BEFORE FINALS, AS EGRESS LTS ARE |
| REQUIRED. SINCE THE LIGHTING IS BEING |
| SHOWN ON THE FANS, THESE WILL BE |
| REQUIRED. |
| ** PLEASE KNOW, IF USING A 1/2 SW RECEPT |
| OR OTHER LIGHTING , THIS WOULD NOT BE |
| REQUIRED. |
| ** THIS NOTE IS FOR INFORMATIONAL |
| PURPOSE ONLY. |
| |
| 20) NOTE: PLEASE SEE RISER, PLEASE |
| CLARIFY THE "9" BEING SHOWN AS THE |
| DESRIPTION OF THE CONDUIT?? |
| IT IS UNCLEAR WHAT THIS IS? |
| 106.1.2 |
| |
| 21) NOTE: PLEASE SEE PLANS INDICATE |
| SCOPE OF WORK BEING LOCATED IN "PALM |
| BEACH COUNTY" , WHEN SCOPE OF WORK AND |
| THIS JOB LOCATION IS LOCATED IN THE |
| "CITY OF WEST PALM BEACH". |
| |
| 22) NOTE: PLANS TO NOTE: SD'S TO BE |
| INSTALLED PER NFPA-72 2002, 11.5.1.1, |
| 11.8.3 |
| |
| 23) NOTE: PLEASE SEE PLANS ARE MISSIGN |
| THE PRINTED NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR SAID PLANS. |
| FBC 106.1.2 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |