Plan Review Details - Permit 06080554
Plan Review Stops For Permit 06080554
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-25 Cont ID  
Sent By lursu Date 2006-08-25 Time 10:47 Rev Time 0.00
Received By lursu Date 2006-08-23 Time 13:06 Sent To  
Notes
2006-08-25 00:00:00THE CORRECT PCN IS 74434328060060110
 WITH 806 KANUGA DR SITE ADDRESS
2006-08-09 00:00:00PCN # FROM PROPERTY APPRAISERS DOES NOT
 MATCH ADDRESS OR OWNER GENERATED BY THE
 COMPUTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-04 Cont ID  
Sent By lmartine Date 2007-04-04 Time 19:10 Rev Time 0.00
Received By lmartine Date 2007-04-04 Time 19:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By rnuquist Date 2006-12-26 Time 21:47 Rev Time 0.00
Received By rnuquist Date 2006-12-26 Time 21:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 09:13 Rev Time 3.00
Received By alange Date 2006-09-05 Time 09:13 Sent To  
Notes
2006-09-05 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 2.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $213,721.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 3.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 4.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 5.SELECT ROOF ASSEMBLY USED FOR THE
 TAMKO ROOFING.
  
 6.PRE-ENGINNERED TRUSSES, FBC 2309 IS
 THE INCORRECT CODE SECTION USED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-01 Cont ID  
Sent By dpalmer Date 2007-03-01 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 09:36 Sent To B
Notes
2007-03-01 11:01:18ELEC OK, ZONING STILL HAS COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 15:30 Rev Time 0.00
Received By dpalmer Date 2006-11-30 Time 13:55 Sent To M
Notes
2006-11-30 15:32:43****** UNSAT2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING, ALSO THERE ARE SOME NEW
 NOTES BASED ON SOME CHANGES ON PLANS.
  
 1) NOTE: OK
  
 2) NOTE: NO, PLEASE STILL CLARIFY SERVICE EQUIPMENT. IS
 THIS A 300A PANEL BOARD OF SOME KIND, A 300A METER MAIN
 COMBO WITH TWO MAINS?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE PLANS AND RISER. RISER SHOWS WHAT
 APPEARS TO BE A
 300A SERVICE, YET PLANS INDICATE 200A'S.
 230.70 , 215.5, 230.2 ETC
  
 3) NOTE:NO, PLEASE SEE THE RISER DIAGRAM DOES NOT
 INDICATE ANY SERVICE ENTRANCE CONDUCTORS? PLEASE SEE
 THE CODE SECTIONS AS PREVIOUSLY NOTED WERE ADDED TO A
 NOTE #19, HOWEVER IT IS NOT PERMITTED TO PLACE CODE
 SECTIONS ON PLANS IN LIEU OF ACTUAL DETAIL OF DESIGN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER DOES NOT INDICATE ANY SEC'S . PLEASE
 COMPLETE RISER.
 310.15B6,310.16,240.4 ETC
  
 4) NOTE: OK.
  
 5) NOTE:NO, SEE NOTE #2, FOR CLARIFICATION OF SERVICE
 MAIN EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION FOR MAIN/PANEL/DISCONNECT ON
 RISER WHICH FEEDS TWO SUB PANELS. PLEASE SEE 230.70 AS
 THERE CAN BE NO MORE THAN 6 SPACES FOR EQUIPMENT AND NO
 MORE THAN 6 MAINS FOR SERVICE.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK; HOWEVER SEE POSSIBLE NOTE UNDER 06081932
 AS THE SAME RISER SHOULD BE NOTED UNDER THAT REVIEW.
 CABANA IS UNDER A SEPARATE PERMIT..
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, PLEASE SEE CIRCUITING WHICH HAS NOW BEEN
 ADDED TO PLANS WHICH DO NOT CORRELATE WITH THE PANEL
 SCHEDULE SUBMITTED. AS PREVIOUSLY NOTED, PLEASE ONLY
 INDICATE THE AREAS WHICH ARE BEING FED FROM THE
 CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE NOW PLANS INDICATE BATH ROOM GFI"S BEING FED
 FROM THE SMALL APPLIANCE CIRCUIT(S).
 PLEASE SEE SMALL APPLIANCE CIRCUITS FEEDING BEDROOM,
 HALLWAY, LIVING ROOM ETC.
 PLEASE SEE ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN
 KITCHEN ETC.
 PLEASE KNOW IT WAS ONLY REQUESTED TO INDICATE ON THE
 PANEL SCHEDULE THESE AREAS/ROOMS.
 PLEASE SEE THE FOLLOWING SECTIONS FOR ITEMS NOT
 PERMITTED ON SMALL APPLIANCE OR BATHROOM CIRCUITS.
 210.52B1, 210.52D, 210.11C1, 210.11C3, 220.16
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE FOR ALL CIRCUITS TO THE
 ROOMS AND AREAS IN WHICH THEY FEED. CIRCUITS ARE TO BE
 SPECIFIC. IE: LIVING RM, KITCHEN LTS, ETC.
 408.6.
 106.1.2
 ** IT IS KNOWN TO THIS OFFICE THAT THE CIRCUITING WILL
 BE REVISED AT A LATER DATE, HOWEVER THE MINIMUM IS
 REQUIRED AT THIS TIME.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE:NO, PLEASE SEE THIS IS THE SAME NOTE, PLEASE
 SEE MISSING DISCONNECT AT THE CU.
 440.11, 110.26
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE MISSING THE DISCONNECTS REQUIRED
 FOR THE A/C CU AND THE SPRINKLER PUMP/IRRIGATION.
 440.11, 430.31
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE: OK.
  
 21) NOTE: OK.
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
  
 ** NEW NOTES **
  
 24) NOTE: PLEASE SEE RISER MENTIONS "RIGID" CONDUIT
 BEING INSTALLED, PLEASE VERIFY THIS AT THIS TIME, AS
 THIS TYPE OF CONDUIT FOR THIS INSTALLATION IS NOT
 USUAL. THIS DOES NOT VIOLATE ANY CODE, HOWEVER PLEASE
 KNOW IF INSTALLATION OF PVC CONDUIT IS USED INSTEAD
 WHICH IS OK, THEN AN EQUIPMENT GROUNDING CONDUCTOR
 WOULD BE REQUIRED TO CABANA AND PLANS WOULD BE REVISED
 TO INDICATE CONDUIT OTHER THAN "RIGID".
 THIS IS NOTED ONLY.
  
 25) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) GIVEN
 ONLY AS A NOTICE AT THIS TIME AS SOME COMMENTS WERE
 INDEED REPEAT COMMENTS FROM PREVIOUS REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-30 13:57:33FROM ZONING/INCOMING ON 11/29

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By dpalmer Date 2006-08-31 Time 11:30 Rev Time 0.00
Received By dpalmer Date 2006-08-31 Time 08:16 Sent To M
Notes
2006-08-31 00:00:00****** UNSAT ******
  
 1) NOTE; PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. NOTE MENTIONS 22K FOR
 MAIN DISCONNECT, HOWEVER INFORMATION ON
 RISER DOES NOT SHOW A MAIN DISCONNECT.
 PLEASE ALSO INCLUDE ALL OTHER SERVICE
 EQUIPMENT RATINGS.
 110.9
 FBC 106.1.2
  
 2) NOTE; PLEASE CORRELATE PLANS AND
 RISER. RISER SHOWS WHAT APPEARS TO BE A
 300A SERVICE, YET PLANS INDICATE 200A'S.
  
 230.70 , 215.5, 230.2 ETC
  
 3) NOTE: PLEASE SEE RISER DOES NOT
 INDICATEANY SEC'S . PLEASE COMPLETE
 RISER.
 310.15B6,310.16,240.4 ETC
  
 4) NOTE: PLEASE SEE RISER SHOWS 1/0'S
 FOR FEEDERS TO SUB PANEL, "A", YET THE
 MAIN BREAKER BEING SHOWN FEEDING THIS
 PANEL IS 200A'S. 1/0'S ARE NOT LARGE
 ENOUGH.
 310.16, 240.4
  
 5) NOTE: PLEASE PROVIDE INFORMATION FOR
 MAIN/PANEL/DISCONNECT ON RISER WHICH
 FEEDS TWO SUB PANELS. PLEASE SEE 230.70
 AS THERE CAN BE NO MORE THAN 6 SPACES
 FOR EQUIPMENT AND NO MORE THAN 6 MAINS
 FOR SERVICE.
  
 6) NOTE: PLEASE INDICATE THE SIZE OF THE
 METER CAN BEING PROVIDED.
 106.1.2 FBC
  
 7) NOTE: PLEASE CORRELATE RISER AND
 PANELS, AS PANEL FOR CABANA IS BEING
 SHOWN ONE SIZE AND RISER SHOWS ANOTHER.
 106.1.2 FBC
  
 8) NOTE: PLEASE SEE LOADS SHOWN FOR A/C
 INDICATES COMPRESSOR LOAD FOR THE 10KW,
 WHERE THE AHU, IS THE LARGER OF THE TWO,
 THE CALCULATIONS SHOULD INDICATE THE
 AHU.
 220.21., 220.31
  
 9) NOTE; PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED
 BUILDING.
 250.32, 250.50.
  
 10) NOTE: ONCE RISER HAS BEEN CORRECTED
 FOR THE SIZE OF PANELS ETC AT CABANA,
 PLEASE BE SURE TO CLEARLY INDICATETHE
 MAIN DISCONNETC AT THE DEACHED BUILDING
 MEETING 225.31-225.39.
 PLEASE KNOW, SINCE PLANS FOR THE CABANA
 HAVE NOT BEEN SUBMITTED AT THIS TIME,
 THIS CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE.
  
 11) NOTE: PLEASE SUBMIT AND COMPLETE
 PLANS FOR CABANA IF PART OF THIS PERMIT APPLICATION
 ETC. PLEASE KNOW, NO REVIEW
 COULD BE DONE FOR CABANA , AND THERE MAY
 BE COMMENTS TO FOLLOW.
 106.1.2 FBC, 2002 NEC.
  
 12) NOTE: PLEASE SEE 422.11(E)3,AS THE
 OCP FOR THE WATER HEATER CAN NOT EXCEED
 150%. PLEASE SEE 60A OCP IS BEING SHOWN
 ON A 5KW UNIT.
 PLEASE ADJUST.
 106.1.2
  
 13) NOTE: PLEASE SEE CONDUCTOR SIZE
 BEING SHOWN ON PANEL SCHEDULE FOR RANGE
 DOES NOT CLEARLY INDICATE THE SIZE.
 SEEMS TO CONTAIN A MISPRINT.
 310.16,240.4
  
 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR ALL CIRCUITS TO THE ROOMS AND AREAS
 IN WHICH THEY FEED. CIRCUITS ARE TO BE
 SPECIFIC. IE: LIVING RM, KITCHEN LTS,
 ETC.
 408.6.
 106.1.2
 ** IT IS KNOWN TO THIE OFFICE THAT THE
 CIRCUITING WILL BE REVISED AT A LATER
 DATE, HOWEVER THE MINIMUM IS REQUIRED AT
 THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 FOR 2' OF WALL SPACE OR MORE.
  
 16) NOTE: PLEASE SEE NOTE #7 ON PLANS
 WHICH REFERENCES A CODE IN THE NEC,
 PLEASE KNOW, HOWEVER THIS MUST BE FROM
 AN OLDER NEC, AS THE CURRENT NFPA-70 IN
 EFFECT DOES NOT CORRELATE WITH THIS
 ARTICALE BEING REFERENCED.
 PLEASE ADJUST.
  
 17) NOTE: PLEASE SEE PLANS ARE MISSING
 THE DISCONNECTS REQUIRED FOR THE A/C CU
 AND THE SPRINKLER PUMP/IRRIGATION.
 440.11, 430.31
  
 18) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL AT MASTER BEDRM TO
 AREAS WITH GRADE LEVEL ACCESS.
 210.70, LS 101 7.8
  
 19) NOTE: PLEASE KNOW, ALL FANS AND LT
 KITS WILL BE REQUIRED TO BE INSTALLED
 BEFORE FINALS, AS EGRESS LTS ARE
 REQUIRED. SINCE THE LIGHTING IS BEING
 SHOWN ON THE FANS, THESE WILL BE
 REQUIRED.
 ** PLEASE KNOW, IF USING A 1/2 SW RECEPT
 OR OTHER LIGHTING , THIS WOULD NOT BE
 REQUIRED.
 ** THIS NOTE IS FOR INFORMATIONAL
 PURPOSE ONLY.
  
 20) NOTE: PLEASE SEE RISER, PLEASE
 CLARIFY THE "9" BEING SHOWN AS THE
 DESRIPTION OF THE CONDUIT??
 IT IS UNCLEAR WHAT THIS IS?
 106.1.2
  
 21) NOTE: PLEASE SEE PLANS INDICATE
 SCOPE OF WORK BEING LOCATED IN "PALM
 BEACH COUNTY" , WHEN SCOPE OF WORK AND
 THIS JOB LOCATION IS LOCATED IN THE
 "CITY OF WEST PALM BEACH".
  
 22) NOTE: PLANS TO NOTE: SD'S TO BE
 INSTALLED PER NFPA-72 2002, 11.5.1.1,
 11.8.3
  
 23) NOTE: PLEASE SEE PLANS ARE MISSIGN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR SAID PLANS.
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-08-23 Cont ID  
Sent By ssherman Date 2006-08-23 Time 13:06 Rev Time 0.00
Received By ssherman Date 2006-08-23 Time 13:05 Sent To  
Notes
2006-08-23 00:00:00HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 15:58 Sent To E
Notes
2007-02-26 15:58:34TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 18:57 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 18:57 Sent To Z
Notes
2007-02-20 18:58:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-29 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2006-11-29 Time 13:56 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 11:15 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 11:15 Sent To Z
Notes
2006-11-20 11:15:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 09:18 Rev Time 0.00
Received By alange Date 2006-08-26 Time 12:45 Sent To  
Notes
2006-08-26 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-30 Cont ID  
Sent By tgordon Date 2006-11-30 Time 16:17 Rev Time 0.30
Received By tgordon Date 2006-11-30 Time 16:17 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By tgordon Date 2006-09-01 Time 14:37 Rev Time 0.30
Received By tgordon Date 2006-09-01 Time 14:37 Sent To B
Notes
2006-09-01 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A
 5.6 KW HEATER, MECHANICAL PLANS ARE
 CALLING FOR A 10 KW HEATER, THE TWO MUST
 COINSIDE, PLEASE CORRECT.
  
 2) CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 .PLEASE
 CORRECT.
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE SIZE RETURN AIR GRILL TO AHU.
  
 5) PLEASE PROVIDE RETURN AIR TO
 BEDROOMS, SEE NOTE #6.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 13:18 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 13:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By jleech Date 2006-08-28 Time 15:08 Rev Time 0.00
Received By jleech Date 2006-08-28 Time 15:08 Sent To E
Notes
2006-08-28 00:00:00DENIED;
 1.THE AUTOMATIC CLOTHES WASHER MUST
 DRAIN DOWN STREAM OF THE BATHROOM GROUP.
 FBC-2004 PLUMBING SECTION 909.1.
 2.THE AUTOMATIC CLOTHES WASHER BRANCH
 DRAIN IS REQUIRED TO BE 3" SECTION
 496.3.
 3.PLUMBING PLAN SHOWS A GAS WATER HEATER
 ELECTRICAL LOAD CALCULATION TABLE PAGE
 6/8 WATER HEATERIS LISTED AS ELECTRIC.
 PLEASE CHANGE ONE OF THE PAGES. IF WATER
 HEATER IS GAS THE A/C HANDLER WILL HAVE
 TO HAVE A DUCTED RETURN OR THE A/H
 CLOSET WILL HAVE TO BE AIR TIGHT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status F Date 2007-02-23 Cont ID  
Sent By adavila Date 2007-02-23 Time 18:33 Rev Time 0.00
Received By adavila Date 2007-02-23 Time 18:33 Sent To I
Notes
2007-02-23 18:38:52PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PLEASE REMOVE THE INTERIOR SHOWER FROM THE PROPOSED
 COTTAGE.IF COTTAGE IS NOT PART OF THIS PERMIT
 APPLICATION, PLEASE INDICATE SO ON ALL PLANS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL
 PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-25 Cont ID  
Sent By mmclean Date 2006-11-25 Time 21:49 Rev Time 0.00
Received By mmclean Date 2006-11-25 Time 21:44 Sent To I
Notes
2006-11-26 21:45:31DENIED, 2ND REQUEST.
 1. PLEASE PROVIDE THE APPROVED LETTER FROM THE PLANNING
 & ZONING DEPT FOR LOT SEPARATION OF THE PROPERTY.
 2. AS INDICATED FOR THE PERMIT PULLED FOR COTTAGE, THE
 INTERIOR SHOWER MUST BE REMOVED FROM PLANS.LOT DOES
 NOT MEET THE REQUIREMENT FOR AN ACCESSORY APT.
 PERMIT # 06081932
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By mmclean Date 2006-08-28 Time 08:13 Rev Time 0.00
Received By mmclean Date 2006-08-28 Time 08:13 Sent To E
Notes
2006-08-28 00:00:00DENIED.
 1. PLEASE PROVIDE THE APPROVED LETTER
 FROM THE PLANNING & ZONING DEPT FOR LOT
 SEPARATION OF THE PROPERTY.
 2. PLEASE PROVIDE THE WIDTH OF THE
 PROPOSED DRIVEWAY.
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
 3. NEED TO INDICATE OF IF THE PROPOSED
 COTTAGE IS INCLUDED IN THE PROPOSED WORK
 OR SEPARATE PERMIT.
 4. NO PLANS (FLOOR/ELEVATION ETC) IS
 SUBMITTED.
 5. THE PROPOSED A/C UNIT SHALL BE NO
 CLOSER THAN 6FT FROM THE SIDE PROPERTY
 LINE.
 6. PLEASE PROVIDE THE DRAWINGS WITH
 DIMENSION FOR THE PROPSED AWNINGS (SEE
 2/8 SOUTH ELEVATION). SEC 94-305 -
 AWNINGS SHALL NOT PROJECT MORE THAN 4FT
 INTO ANY SETBACK OR BE SUPPORTED BY ANY
 MEANS OTHER THAN THE ATTACHEMENT TO THE
 BUILDING.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720