Plan Review Details - Permit 06080468
Plan Review Stops For Permit 06080468
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-08 Cont ID  
Sent By shill Date 2007-03-07 Time 15:13 Rev Time 0.00
Received By shill Date 2007-03-07 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-28 Cont ID  
Sent By shill Date 2007-02-28 Time 17:42 Rev Time 0.00
Received By shill Date 2007-02-28 Time 16:12 Sent To  
Notes
2007-02-28 17:43:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PLEASE PROVIDE ZONE 4 AND ZONE 5 AREAS FOR EACH
 FLOOR.
  
 AS DISCUSSED, NO RESUBMITTAL FEE DUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 16:20 Rev Time 0.00
Received By shill Date 2007-01-23 Time 16:20 Sent To  
Notes
2007-01-23 16:30:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PLEASE SEE PREVIOUS LISTS IN REGARDS TO USING WALL
 PRESSURES FOR THE SOFFIT.ALSO NOTE, FROM EMAIL FROM
 ROBERT BROWN ABO TO JASON HANCHUK, PE, THE FOLLOWING:
  
 I HAVE REVIEWED THE EXAMPLE THAT YOU SENT.AS
 PREVIOUSLY STATED, I AGREE THAT ONE LOAD CASE IS 'WIND
 PERPENDICULAR TO WALL' AND THAT YOUR METHODOLOGY
 ADDRESSES THAT LOADCASE.THE WIND LOAD ON THE SOFFIT
 UNDER THAT LOAD CASE IS A POSITIVE PRESSURE.
  
 HOWEVER, WHEN WE SPOKE YESTERDAY AND AGAIN TODAY, AND
 WHEN I SPOKE TO MR KELAHER, I POINTED OUT THAT THERE IS
 A CASE AT THE EAST-WEST GRADE LEVEL WALKWAY FROM OLIVE
 AVENUE TO DIXIE HWY WHERE THERE IS NO WALL (SEE SHEET
 A-1 OF LOUIS C. KALLINOSIS, AIA PLANS).AS I STATED,
 IN THAT LOCATION, THE WIND WILL ACCELERATE ACROSS THAT
 SOFFIT IN THE SAME MANNER THAT IT DOES ACROSS A FLAT
 ROOF.THAT ACCELERATION WILL RESULT IN NEGATIVE
 PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE
 PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN
 LOAD CALCULATIONS.I DO NOT SEE THATYOU OR MR
 KELAHER HAVE ADDRESSED THAT LOAD CASE.
  
 I DISAGREE WITH THE SECOND PARAGRAPH OF YOUR LETTER
 DATED 1/8/06 (SHOULD BE 2007?) ADDRESSED TO ALLEN
 PADILLA.IT STATES THAT ZONE 2 AND 3 LOADS ARE
 OVERHANG LOADS.I WOULD CONTEND THAT FOR A FLAT ROOF
 THERE IS NO OVERHANG.IF YOU REFER TO FIGURE 6-3 IN
 ASCE7-02 YOU WILL SEE THAT FOR A FLAT ROOF THERE IS NO
 OVERHANG FOR ZONE 2 AND 3.ALSO FIGURE 6-11B IN
 ASCE7-02 WHICH GIVES EXTERNAL PRESSURE COEFFICIENTS FOR
 GABLE ROOFS WITH SLOPE RANGING FROM 0O (I.E. FLAT) TO
 7O, GIVES PRESSURE COEFFICIENTS FOR ZONE 2 AND 3 ON THE
 ROOF AND THEN GIVES SEPARATE COEFFICIENTS FOR ZONE 2
 AND 3 AT THE OVERHANGS.THIS WOULD NOT BE THE CASE IF
 ZONE 2 AND 3 WERE FOR OVERHANGS ONLY.
  
 WE ALSO NEED TO CONSIDER THE CASE OF 'WIND PARALLEL TO
 THE WALL'.THIS LOADCASE WILL RESULT IN A NEGATIVE
 PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE
 PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN
 LOAD CALCULATIONS.
  
 I DO NOT FOR ONE MOMENT CONSIDER DESIGN FOR WIND LOAD
 TO BE AN EXACT SCIENCE BUT I BELIEVE THE PROPOSED
 DESIGN TO BE NON-CONSERVATIVE AS THE WORST CASE
 NEGATIVE PRESSURE LOADCASE DOES NOT APPEAR TO HAVE BEEN
 FULLY INVESTIGATED.THE FACT THAT THESE REPAIRS ARE
 EVEN NECESSARY WOULD IMPLY THAT THE SOFFIT ON THIS
 BUILDING WAS SUBJECTED TO SIGNIFICANT NEGATIVE WIND
 PRESSURE EVEN DURING THE 'LESS-THAN-DESIGN' WIND
 EVENT(S) THAT CAUSED THE FAILURE.EITHER PROVIDE
 JUSTIFICATION FOR THE USE OF ZONE 4 WALL PRESSURES FOR
 THE CASE AT THE SOFFIT ABOVE THE EAST-WEST WALKWAY AND
 FOR THE 'WIND PARALLEL TO THE WALL' CASE, OR AMEND THE
 NEGATIVE PRESSURES IN THE WIND DESIGN LOAD
 CALCULATIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-02 Cont ID  
Sent By shill Date 2007-01-02 Time 10:39 Rev Time 0.00
Received By shill Date 2007-01-02 Time 10:39 Sent To  
Notes
2007-01-02 10:49:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)COMMENT FROM PREVIOUS LIST, CEILINGS AND SOFFITS
 ARE NOT WIND ZONE 4.THE STATEMENT THAT THESE ARE
 SOFFITS, NOT OVERHANGS, IS ACKNOWLEDGED.THIS HAS BEEN
 CONFIRMED BY BUILDING OFFICIAL AND ASSISTANT BUILDING
 OFFICIAL.PLEASE CONTACT ME TO DISCUSS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By shill Date 2006-09-01 Time 13:29 Rev Time 0.00
Received By shill Date 2006-09-01 Time 13:29 Sent To  
Notes
2006-09-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE CALCULATIONS STATE THAT
 CEILINGS AND SOFFITS ARE IN ZONE 4.SEE
 ASCE7-02 FIGURE 6-11B, CEILINGS AND
 SOFFITS ARE ZONES 1, 2 AND 3 DEPENDING
 ON LOCATION.
  
 2.)PROVIDE A CODE SUMMARY; DECLARE
 GOVERNING CODE (INCLUDING FBC EXISTING
 BUILDING CODE), BUILDING HEIGHT,
 BUILDING TYPE FBC6.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 10:56 Sent To PC
Notes
2007-06-26 11:05:12REV FOR CHANGE OF LIGHT FIXTURE TYPE TO HPS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By dpalmer Date 2006-12-05 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 18:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 17:58 Sent To  
Notes
2006-08-23 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS STATE "WORK TO
 COMPLY WITH APPLICABLE CODES". PLEASE
 KNOW, PLANS SHALL STATE THE CODES AND
 DESIGN SPECIFIC IN DESIGN.
 PLANS SHOULD REFLECT CODES FOR RELEVANT
 WORK IN SCOPE.
 FBC 2004, NFPA-70 2002 . (NEC).
  
 2) NOTE: PLEASE SEE OTHER NOTE ON PLANS
 MENTIONS CIRCUITING WAS VERIFIED IN
 ORDER TO ADDED NEW FIXTURES WITH THE
 INCREASED WATTAGE, HOWEVER BASED ON THE
 NUMBE ROF FIXTURES SHOWN ON SOME
 CIRCUITS AND THE VOLTAGE OF SAID
 CIRCUITS NOT BEING SHOWN, PLEASE SEE
 CIRCUIT(S) WHICH APPEAR TO BE OVER
 LOADED.
 PLEASE SEE VOLTAGE SHOULD BE STATED FOR
 EEACH OF THE PANELS/SYSTEMS FOR EXISTING
 CIRCUITS. 120, 208, 277 ETC.
 PLEASE ALSO KNOW, ALL CONTINUOUS LOADS
 SHOULD BE VERIFIED FOR NEW LOADS.
 (3 OR MORE HRS).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 12:51 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By mawillia Date 2006-09-15 Time 10:38 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 10:33 Sent To  
Notes
2006-09-15 00:00:00*****UNSAT*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 4.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY
 (INCLUDING FIRE LANES).
  
 5.) NFPA 101, 2003 EDITION AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION SHALL
 BE REFERENCED.
  
 6.) INDICATE ON THE PLANS THE LOCATION
 OF FIRE PROTECTION SYSTEMS (I.E.
 SPRINKLER HEADS, SMOKE DETECTORS, ETC.)
 AND WHETHER THE LISTED SCOPE OF WORK
 WILL AFFECT THEIR OPERATION.
  
 7.) IF THE FIRE ALARM AND/OR SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE
 OF WORK, SEPARATE SHOP PLANS/DRAWINGS
 AND PERMIT WILL BE REQUIRED.
  
  
  
 **PLEASE SUBMIT OR ADDRESS THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.**
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 14:41 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 14:41 Sent To E
Notes
2007-06-24 14:41:27TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-07 Cont ID  
Sent By adarroug Date 2007-03-07 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-03-07 Time 11:57 Sent To B
Notes
2007-03-07 11:57:43TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 16:50 Sent To B
Notes
2007-02-26 16:53:23TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 16:59 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 16:59 Sent To B
Notes
2007-01-18 17:00:30TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-27 Cont ID  
Sent By adarroug Date 2006-11-27 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-11-27 Time 13:37 Sent To  
Notes
2006-12-05 13:42:39TO "COMM" BD#51
2006-11-27 13:37:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-15 Cont ID  
Sent By shill Date 2006-09-15 Time 11:27 Rev Time 0.00
Received By shill Date 2006-08-11 Time 08:22 Sent To  
Notes
2006-08-22 00:00:00TO "COMM" BD#3
2006-08-11 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By mflis Date 2006-12-08 Time 14:53 Rev Time 0.00
Received By mflis Date 2006-12-08 Time 14:53 Sent To  
Notes
2006-12-08 14:54:19DMP - REVIEWED AND STAMPED.
2006-12-05 18:55:46NEW SHEETS , NEEDS STAMPING IF OK.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-05 Cont ID  
Sent By mflis Date 2006-09-05 Time 09:56 Rev Time 0.00
Received By mflis Date 2006-09-05 Time 09:56 Sent To  
Notes
***NONE***