Plan Review Stops For Permit 06080468 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-03-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-03-07 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-03-07 |
Time |
15:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-02-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-02-28 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-02-28 |
Time |
16:12 |
Sent To |
|
|
Notes |
2007-02-28 17:43:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)PLEASE PROVIDE ZONE 4 AND ZONE 5 AREAS FOR EACH | | FLOOR. | | | | AS DISCUSSED, NO RESUBMITTAL FEE DUE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-01-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-01-23 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-01-23 |
Time |
16:20 |
Sent To |
|
|
Notes |
2007-01-23 16:30:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)PLEASE SEE PREVIOUS LISTS IN REGARDS TO USING WALL | | PRESSURES FOR THE SOFFIT.ALSO NOTE, FROM EMAIL FROM | | ROBERT BROWN ABO TO JASON HANCHUK, PE, THE FOLLOWING: | | | | I HAVE REVIEWED THE EXAMPLE THAT YOU SENT.AS | | PREVIOUSLY STATED, I AGREE THAT ONE LOAD CASE IS 'WIND | | PERPENDICULAR TO WALL' AND THAT YOUR METHODOLOGY | | ADDRESSES THAT LOADCASE.THE WIND LOAD ON THE SOFFIT | | UNDER THAT LOAD CASE IS A POSITIVE PRESSURE. | | | | HOWEVER, WHEN WE SPOKE YESTERDAY AND AGAIN TODAY, AND | | WHEN I SPOKE TO MR KELAHER, I POINTED OUT THAT THERE IS | | A CASE AT THE EAST-WEST GRADE LEVEL WALKWAY FROM OLIVE | | AVENUE TO DIXIE HWY WHERE THERE IS NO WALL (SEE SHEET | | A-1 OF LOUIS C. KALLINOSIS, AIA PLANS).AS I STATED, | | IN THAT LOCATION, THE WIND WILL ACCELERATE ACROSS THAT | | SOFFIT IN THE SAME MANNER THAT IT DOES ACROSS A FLAT | | ROOF.THAT ACCELERATION WILL RESULT IN NEGATIVE | | PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE | | PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN | | LOAD CALCULATIONS.I DO NOT SEE THATYOU OR MR | | KELAHER HAVE ADDRESSED THAT LOAD CASE. | | | | I DISAGREE WITH THE SECOND PARAGRAPH OF YOUR LETTER | | DATED 1/8/06 (SHOULD BE 2007?) ADDRESSED TO ALLEN | | PADILLA.IT STATES THAT ZONE 2 AND 3 LOADS ARE | | OVERHANG LOADS.I WOULD CONTEND THAT FOR A FLAT ROOF | | THERE IS NO OVERHANG.IF YOU REFER TO FIGURE 6-3 IN | | ASCE7-02 YOU WILL SEE THAT FOR A FLAT ROOF THERE IS NO | | OVERHANG FOR ZONE 2 AND 3.ALSO FIGURE 6-11B IN | | ASCE7-02 WHICH GIVES EXTERNAL PRESSURE COEFFICIENTS FOR | | GABLE ROOFS WITH SLOPE RANGING FROM 0O (I.E. FLAT) TO | | 7O, GIVES PRESSURE COEFFICIENTS FOR ZONE 2 AND 3 ON THE | | ROOF AND THEN GIVES SEPARATE COEFFICIENTS FOR ZONE 2 | | AND 3 AT THE OVERHANGS.THIS WOULD NOT BE THE CASE IF | | ZONE 2 AND 3 WERE FOR OVERHANGS ONLY. | | | | WE ALSO NEED TO CONSIDER THE CASE OF 'WIND PARALLEL TO | | THE WALL'.THIS LOADCASE WILL RESULT IN A NEGATIVE | | PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE | | PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN | | LOAD CALCULATIONS. | | | | I DO NOT FOR ONE MOMENT CONSIDER DESIGN FOR WIND LOAD | | TO BE AN EXACT SCIENCE BUT I BELIEVE THE PROPOSED | | DESIGN TO BE NON-CONSERVATIVE AS THE WORST CASE | | NEGATIVE PRESSURE LOADCASE DOES NOT APPEAR TO HAVE BEEN | | FULLY INVESTIGATED.THE FACT THAT THESE REPAIRS ARE | | EVEN NECESSARY WOULD IMPLY THAT THE SOFFIT ON THIS | | BUILDING WAS SUBJECTED TO SIGNIFICANT NEGATIVE WIND | | PRESSURE EVEN DURING THE 'LESS-THAN-DESIGN' WIND | | EVENT(S) THAT CAUSED THE FAILURE.EITHER PROVIDE | | JUSTIFICATION FOR THE USE OF ZONE 4 WALL PRESSURES FOR | | THE CASE AT THE SOFFIT ABOVE THE EAST-WEST WALKWAY AND | | FOR THE 'WIND PARALLEL TO THE WALL' CASE, OR AMEND THE | | NEGATIVE PRESSURES IN THE WIND DESIGN LOAD | | CALCULATIONS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-01-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-01-02 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-01-02 |
Time |
10:39 |
Sent To |
|
|
Notes |
2007-01-02 10:49:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)COMMENT FROM PREVIOUS LIST, CEILINGS AND SOFFITS | | ARE NOT WIND ZONE 4.THE STATEMENT THAT THESE ARE | | SOFFITS, NOT OVERHANGS, IS ACKNOWLEDGED.THIS HAS BEEN | | CONFIRMED BY BUILDING OFFICIAL AND ASSISTANT BUILDING | | OFFICIAL.PLEASE CONTACT ME TO DISCUSS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-09-01 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-09-01 |
Time |
13:29 |
Sent To |
|
|
Notes |
2006-09-01 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)THE CALCULATIONS STATE THAT | | CEILINGS AND SOFFITS ARE IN ZONE 4.SEE | | ASCE7-02 FIGURE 6-11B, CEILINGS AND | | SOFFITS ARE ZONES 1, 2 AND 3 DEPENDING | | ON LOCATION. | | | | 2.)PROVIDE A CODE SUMMARY; DECLARE | | GOVERNING CODE (INCLUDING FBC EXISTING | | BUILDING CODE), BUILDING HEIGHT, | | BUILDING TYPE FBC6. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-26 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-26 |
Time |
10:56 |
Sent To |
PC |
|
Notes |
2007-06-26 11:05:12 | REV FOR CHANGE OF LIGHT FIXTURE TYPE TO HPS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-12-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-05 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-05 |
Time |
18:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-08-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-23 |
Time |
18:16 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-23 |
Time |
17:58 |
Sent To |
|
|
Notes |
2006-08-23 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE PLANS STATE "WORK TO | | COMPLY WITH APPLICABLE CODES". PLEASE | | KNOW, PLANS SHALL STATE THE CODES AND | | DESIGN SPECIFIC IN DESIGN. | | PLANS SHOULD REFLECT CODES FOR RELEVANT | | WORK IN SCOPE. | | FBC 2004, NFPA-70 2002 . (NEC). | | | | 2) NOTE: PLEASE SEE OTHER NOTE ON PLANS | | MENTIONS CIRCUITING WAS VERIFIED IN | | ORDER TO ADDED NEW FIXTURES WITH THE | | INCREASED WATTAGE, HOWEVER BASED ON THE | | NUMBE ROF FIXTURES SHOWN ON SOME | | CIRCUITS AND THE VOLTAGE OF SAID | | CIRCUITS NOT BEING SHOWN, PLEASE SEE | | CIRCUIT(S) WHICH APPEAR TO BE OVER | | LOADED. | | PLEASE SEE VOLTAGE SHOULD BE STATED FOR | | EEACH OF THE PANELS/SYSTEMS FOR EXISTING | | CIRCUITS. 120, 208, 277 ETC. | | PLEASE ALSO KNOW, ALL CONTINUOUS LOADS | | SHOULD BE VERIFIED FOR NEW LOADS. | | (3 OR MORE HRS). | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-22 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-22 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-09-15 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-09-15 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-09-15 |
Time |
10:33 |
Sent To |
|
|
Notes |
2006-09-15 00:00:00 | *****UNSAT***** | | | | | | | | | | 1.) STRUCTURES UNDERGOING CONSTRUCTION, | | ALTERATION, OR DEMOLITION OPERATIONS | | SHALL COMPLY WITH NFPA 241. | | | | 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE | | MATERIAL AND DUST DEBRIS SHALL BE | | REMOVED FROM THE STRUCTURE AND ITS | | IMMEDIATE VICINITY AT THE END OF EACH | | SHIFT OR MORE FREQUENTLY AS NECESSARY | | FOR SAFE OPERATIONS. | | | | 3.) ALL EXIT COMPONENTS SHALL BE | | MAINTAINED, CLEAR AND UNOBSTRUCTED. | | | | 4.) CONSTRUCTION AND/OR DEMOLITION | | OPERATIONS SHALL NOT INTERFERE OR HINDER | | EMERGENCY ACCESS TO THE SAID PROPERTY | | (INCLUDING FIRE LANES). | | | | 5.) NFPA 101, 2003 EDITION AND FLORIDA | | FIRE PREVENTION CODE, 2004 EDITION SHALL | | BE REFERENCED. | | | | 6.) INDICATE ON THE PLANS THE LOCATION | | OF FIRE PROTECTION SYSTEMS (I.E. | | SPRINKLER HEADS, SMOKE DETECTORS, ETC.) | | AND WHETHER THE LISTED SCOPE OF WORK | | WILL AFFECT THEIR OPERATION. | | | | 7.) IF THE FIRE ALARM AND/OR SPRINKLER | | SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE | | OF WORK, SEPARATE SHOP PLANS/DRAWINGS | | AND PERMIT WILL BE REQUIRED. | | | | | | | | **PLEASE SUBMIT OR ADDRESS THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | QUESTIONS, PLEASE DO NOT HESITATE TO | | CALL.** | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-24 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-24 |
Time |
14:41 |
Sent To |
E |
|
Notes |
2007-06-24 14:41:27 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-07 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-07 |
Time |
11:57 |
Sent To |
B |
|
Notes |
2007-03-07 11:57:43 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-26 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-26 |
Time |
16:50 |
Sent To |
B |
|
Notes |
2007-02-26 16:53:23 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-18 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-18 |
Time |
16:59 |
Sent To |
B |
|
Notes |
2007-01-18 17:00:30 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-27 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-27 |
Time |
13:37 |
Sent To |
|
|
Notes |
2006-12-05 13:42:39 | TO "COMM" BD#51 | 2006-11-27 13:37:35 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-09-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-09-15 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-08-11 |
Time |
08:22 |
Sent To |
|
|
Notes |
2006-08-22 00:00:00 | TO "COMM" BD#3 | 2006-08-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2006-12-08 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2006-12-08 |
Time |
14:53 |
Sent To |
|
|
Notes |
2006-12-08 14:54:19 | DMP - REVIEWED AND STAMPED. | 2006-12-05 18:55:46 | NEW SHEETS , NEEDS STAMPING IF OK. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2006-09-05 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2006-09-05 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2006-09-05 |
Time |
09:56 |
Sent To |
|
|
Notes |
|
|