Plan Review Details - Permit 06080439
Plan Review Stops For Permit 06080439
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By jwitmer Date 2006-09-05 Time 07:07 Rev Time 4.44
Received By jwitmer Date 2006-09-05 Time 07:07 Sent To  
Notes
2006-09-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06080439
 ADD: 2825 AUSTRALIAN AV
 CONT: TURSO CONTRACTING CO
 TEL: (561)358-4246
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.2004 EXISTING
 BUILDING CODE INDICATE THE LEVEL OF
 ALTERATIONS?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) OCCUPANT LOAD
 H) FLOOD ZONE
 I) FLOOD ELEVATION
  
 3) SHEET A1.2 NOTE# 9 INDICATES GLAZING
 TO MEET THE REQUIREMENTS OF FBC 2001
 PLEASE CORRECT TO THE CURRENT CODE FBC
 2004.
  
 4) SHEET A1.1 PLEASE PROVIDE ELEVATIONS
 FOR THE SITE PLAN.11-4.3.7 SLOPE.
 AN ACCESSIBLE ROUTE WITH A RUNNING SLOPE
 GREATER THAN 1:20 IS A RAMP AND SHALL
 COMPLY WITH SECTION 11-4.8 . NOWHERE
 SHALL THE CROSS SLOPE OF AN ACCESSIBLE
 ROUTE EXCEED 1:50.
  
 5) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 6) SHEET A8.1 INDICATES 2 SECTIONS
 1-2/S1 THERE ARE NO STRUCTURAL SHEETS,
 ONLY "A" SHEETS.
  
 7) SHEET A8.2 SAME ISSUE PLAN DETAILS
 INDICATE STRUCTURAL SHEETS.
  
 8) A8.3 DETAILS OF STEEL COLUMN AND
 8"X30" STEEL EMBED PLATE DOESN'T
 INDICATE THE TYPE OF WELDNOR SIZE OF
 WELD. 106.1.2* ADDITIONAL INFO REQUIRED.
  
 9) SHEET A8.3 DETAIL# 2&4 INDICATES A
 STEEL PARAPET BUT NO ATTACHMENT METHOD
 IS PROVIDED?106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
  
 10) A8.3 STEEL STUD PARAPET DETAILS ARE
 MISSING DETAILS SUCH AS :
 10A) WEATHER RESISTANT BARRIER 2510.6
 10B) TYPE OF WIRE LATH, WEIGHT OF WIRE
 LATH, AND ATTACHMENT, ASTM C1063.
  
 11) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 1) TAMKO BUR ROOF SYSTEMS
 ONLY THE FIRST 4 SHEETS OF THIS REPORT
 WERE SUBMITTED. NO SUBSYSTEM WAS
 SUBMITTED OR HIGHLIGHTED. NOTE SYSTEMS
 LIMITATION# 7. FOR THIS PROJECT THERE
 WILL NEED TO HAVE 3 SEPERATE SUBSYSTEMS
 ONE FOR CONCRETE TWIN TEES WITH
 INSULATED DECK, ONE FOR SSTEEL DECK WITH
 INSULATION AND A STEEL DECK NO
 INSULATION.
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .
  
 __X_ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 13:47 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 13:47 Sent To  
Notes
2006-08-27 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE SEE THE SOIL BEARING
 REPORTS , FIELD REPORTS ARE IN FACT
 SEALED WITH A RAISED SEAL OVER
 SIGNATURES WHICH ARE PHOTO-COPIES OF
 ORIGINAL SIGNATURES. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUES 471.025, AS BOTHE OF
 THESE REQUIRE ALL SIGNATURES TO BE
 ORIGINAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE NOC WAS RECORDED ON
 6/21/06 WHICH WAS RECORDED WITHOUT THE
 PCN/TAX FOLIO NUMBER ON SAID DOCUMNET.
 PLEASE ALSO KNOW FOR INFORMATION
 PRUPOSES, THE NOC WILL BECOME VOID IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING SUCH NOC. PLEASE KNOW THE NOC
 IS ONLY REQUIRED BEFORE PICKING UP
 PERMIT.
 FS 713.13(2).
  
 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE
 FLORIDA ENERGY CODE CALCULATIONS WAS
 SUBMITTED.
 2004 FBC CHAPTER 13
  
 4) NOTE: PLEASE INDICATE AND SHOW ALL
 ROOM AND AREA DESIGNATIONS ON PLANS.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS
 AND PLEASE CORRELATE ALL CIRCUTING ON
 PLANS WITH THE PANEL SCHEDULE(S)
 SUBMITTED. PLEASE KNOW, CIRCUITS SHALL
 BE SPECIFIC TO AREAS/ROOMS ARE SHOWN ON
 PLANS. *GEN LTS AND GEN RECEPTS NEEDS TO
 BE MORE SPECIFIC*
 408.4, 310.16, 240.4
  
 5) NOTE: PLEASE BE SURE PLANS REFLECT
 ALL THE CURRENT RELEVANT CODES SURRENTLY
 ADOPTED BY THE STATE OF FLORIDA.
 PLEASE SEE PLANS DO SHOW THE 2001 FBC IN
 SOME LOCATIONS.
 PLEASE SEE WE ARE CURRENTLY UNDER THE
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101, 2004 FBC.
 106.1
  
 6) NOTE: PLEASE CLARIFY RISER AS SHOWN.
 PLEASE SEE AN ADDITIONAL METER CAN IS
 BEING SHOWN FOR WHAT WOULD BE A NEW
 TENANT, HOWEVER THIS IS ONLY ONE TENANT
 AND ONLY ONE METER WIL BE PERMITTED
 UNLESS PROPER TENANT SEPARATION IS
 BUILT.
 PLEASE ALSO SEE RISER SHOWS A NEW MAIN
 DISCONNECT ON THE LINE SIDE OF THE FPL
 METERS. PLEASE SEE FPL SERVICE STANDARDS
 AS THE MAINS WOULD BE REQUIRD ON THE
 LOAD SIDE.
 PLEASE SEE RISER AS SHOWN MUST BE
 RE-DESIGNED.
 90.4.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE MISSING GROUNDFING
 ELECTRODE SYSTEM PER 250.50.
 PLEASE COMPELTE, NEW FOOTER STEEL, COLD
 WATER PIPES ETC.
  
 8) NOTE: PLEASE SEE LTS IN MANY
 LOCATIONS ARE BEING SHOWN AS A "J" WHERE
 IT APPEARS TO BE A 2X4 LAYIN TYOE
 FIXTURE. PLEASE CLARIFY IF THE "J" IS
 THE FIXTURE TYPE, THEN PLEASE INCLUDE
 ON THE FIXTURE SCHEDULE. PLEASE KNOW,
 LTS ARE REQUIRED IN ALL THESE LOCATIONS
 FOR MEANS OF EGREES ETC.
 NFPA-101 7.8
  
 9) NOTE: PLEASE SEE NOTE ABOVE #8, AS
 THE SAME IS SHOWN IN AHU CLOSETS.
 PLEASE SEE 210.70
 PLEASE ALSO SEE MISSING RECEPTS FOR
 AHU'S, AND MISSING GFI FOR CU'S .
 210.63, 210.87
  
 10) NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR AHU'S , 440.11,110.26
  
 11) NOTE: PLEASE SEE MISSING SIGN
 CIRCUIT(S). 600.5, 220.3(B)(6)
  
 10) NOTE: PLEASE SUBMIT AND SHOW
 COMPLETE LOAD CALCULATTIONS FOR
 COMMERCIAL BUILDINGS. 220.3,220.10,
 220.11,220.13, ETC AND ALL CONTINUOUS
 LOADS PER 215.3, 230.42 ETC
  
 11) NOTE: PLEASE SEE LAODS ON PANELS ARE
 SHOWING BOTH THE COND UNITS AND THE
 AHU'S. PLEASE SEE 220.11
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By rchokshi Date 2006-09-21 Time 15:28 Rev Time 0.00
Received By rchokshi Date 2006-09-21 Time 15:09 Sent To  
Notes
2006-09-21 00:00:00FAILED FOR FOLLOWING REASONS:
 1. PLEASE SHOW POLLUTION PREVENTION
 PLANS,DETAILS SILT FENCE AROUND THE SITE
 ON DRAWING
 2. PLEASE SHOW STORM WATER CAL.,RUNOFF
 CAL.,PERVIOUS,IMPERVIOUS AREA,CONTROL
 STRUCTURES IF ANY?, OR, EXFILTRATION
 TRNCHES, IF ANY? WATER QUALITY ETC.,
 3. PLEASE SHOW ON DRAWINGS DETAILS FOR
 CITY OF WPB STANDARDS FOR
 SIDEWALK,DRIVEWAY, APPROACH,HANDICAP
 PARKING, ADA, DUMPSTER ENCLOSURE,
 4. PLEASE SHOW ALL CATCH BASINS IN THE
 SURROUNDING SITE SO THE NEIGHBOURS DO
 NOT GET FLOODED.
 5. PLEASE SHOW ON DRAWING, FIRST FLOOR
 ELEVATION, CENTERLINE OF THE ROAD
 ELEVATION, SIDEWALK ELE., SO THEY ALL
 MEET MINIMUM BUILDING CODES.
 6. MUST BE APPROVED FROM UTILITY FROM
 45TH STREET, ENGINEERING BEFORE WE
 APPROVE.
  
 PLEASE RESPOND EACH ITEM OF THE
 PARAGRAPH TO EXPEDITE THE PROCESS.
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By mwennerg Date 2006-09-19 Time 15:55 Rev Time 0.00
Received By mwennerg Date 2006-09-19 Time 15:55 Sent To  
Notes
2006-09-19 00:00:00***DENIED***
  
 1) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. PLEASE SEE SHEET A1.2, NOTE
 #05.
  
 2) THE EXIT DOOR LEADING TO THE EXISTING
 BUILDING APPEARS TO CONFLICT WITH THE
 AHU DOOR. WHAT PREVENTS THAT EXIT FROM
 BEING OBSTRUCTED IF THE AHU DOOR IS IN
 THE OPEN POSITION?
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 14:52 Sent To  
Notes
2006-08-22 00:00:00TO "COMM" BD#45
2006-08-10 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 15:39 Rev Time 0.45
Received By tgordon Date 2006-09-20 Time 15:39 Sent To  
Notes
2006-09-20 00:00:00*** DENIED ***
 1) SEE ENERGY CAL'S. PAGE 6 AND
 COMPLETE.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 3) PLEASE PROVIDE OUTDOOR AIR AND
 OUTDOOR AIR CALCULATIONS, PER 2004 FBC/M
 403.2 .
  
 4) PLEASE SHOW SIZES OF SUPPLY AIR DUCTS
 (FLEX) TO NEW ADDITION AND TO BATHROOMS
 IN EXISTING.
  
 5) PLEASE SEE HIGH LITED WALLS ON
 MECHANICAL PLAN AS THEY ARE FIRE RATED
 AND REQUIRE FIRE DAMPERS.
  
 6) PLEASE SHOW A MANUFACTURE DETAIL FOR
 FIRE DAMPERS ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By kstevens Date 2006-09-05 Time 13:51 Rev Time 0.00
Received By kstevens Date 2006-09-05 Time 13:51 Sent To  
Notes
2006-09-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. BUILDING SHALL BE DESIGNED TO THE
 FBC-2004 CODE. PLEASE INDICATE ON PLANS.
 SECTION 106.1.1
  
 2. PROVIDE AN EXISTING FLOOR PLAN TO
 DETERMINE EXTENT OF ALTERATION. SECTION
 106.1.1.
  
 3. SHT A1.2 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
  
 4. SHT A2.1 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. NO DRAINAGE OR
 WATER SUPPLY IS SHOWN TO THE DRINKING
 FOUNTAIN. PLEASE CLARIFY.
  
 5. SHT A2.1 ACCESSIBILITY REQUIREMENTS.
 SHOW THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 FOR LAV'S
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 6. SHT A2.1 SHOWS A FREE STANDING
 DRINKING FOUNTAIN, AND A WALL HUNG
 DRINKING FOUNTAIN DETAIL. PLEASE
 INDICATE WHICH TYPE WILL BE INSTALLED.
 SECTION 106.1.1. IF THE WALL HUNG TYPE
 WILL BE USED, A FORWARD APPROACH CLEAR
 FLOOR SPACE IS REQUIRED. SECTION
 11-4.15.5. ALSO SHOW PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING AS REQUIRED BY SECTION
 11-4.1.3(10)(A), IF THIS IS NOT A
 HIGH/LOW DRINKING FOUNTAIN.
  
 7. SHT A4.1 SCUPPERS SHOWN ON SHT A5.1
 ARE NOT SHOWN ON THE ELEVATIONS. PLEASE
 INDICATE THE SCUPPERS. SECTION 106.1.1.
  
 8. SHT A5.1 SUBMIT CALCULATIONS FOR THE
 ROOF DRAINS PER SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS. SIZE GUTTERS AND
 DOWNSPOUTS REQUIRED BY SECTION 1503.6
 PER TABLES 1106.3 AND 1106.6. SHOW THE
 SQUARE FOOTAGE BEING DRAINED BY EACH
 DOWNSPOUT. SHOW ENTIRE SQUARE FOOTAGE
 BEING DRAINED AS WELL AS 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, IN
 THE CALCULATIONS. INDICATE SLOPE OF THE
 GUTTER AND INDICATE THE LOCATION OF THE
 HIGH SPOTS OF THE GUTTER.
  
 9. SHT A5.1 SEPARATE PRIMARY AND
 SECONDARY ROOF DRAINS ARE REQUIRED ON
 THE LOWER ROOF. SUBMIT CALCULATIONS
 SHOWING THE SQUARE FOOTAGE OF THE ROOF
 AS WELL AS 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS. SHOW THE
 PRIMARY ROOF DRAINS. DETAIL SHOWN
 INDICATES EMERGENCY OVERFLOW SCUPPERS AS
 THE FLOW LEVEL IS 2" TO $' OFF THE ROOF.
  
 10. SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (IF REQUIRED BY SECTION 604.9
 - (W/M'S, D/W'S, OR ICE MAKERS). ALSO
 SEE SECTION 606.1(4). SECTION
 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-12 Cont ID  
Sent By mmclean Date 2006-08-12 Time 10:45 Rev Time 0.00
Received By mmclean Date 2006-08-12 Time 10:45 Sent To I
Notes
2006-08-12 00:00:00DENIED, - OC - COMMERCIAL STRUCTURE
 SEC 94-35(4)
 1. NEED TO APPLY FOR AN INFORMAL(LEVEL 1
 SITEPLAN REVIEW) WITH THE PLANNING &
 ZONING DEPT, 5TH FLOOR OF CITY HALL, OR
 CALL 822-1435 TO SPEAK WITH A PLANNER.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720