Plan Review Details - Permit 06080421
Plan Review Stops For Permit 06080421
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-08-21 Cont ID  
Sent By lursu Date 2006-08-21 Time 13:27 Rev Time 0.00
Received By amorse Date 2006-08-21 Time 16:02 Sent To  
Notes
2006-08-21 00:00:00SHOES FOR CREWS, OCCUPIES ENTIRE 3RD &
 4TH FLOOR, HOWEVER THE INTERIOR
 RENOVATIONS FOR THIS 403 UNIT IS WHERE
 THE JOB IS LOCATED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By lursu Date 2006-08-21 Time 10:32 Rev Time 0.00
Received By lursu Date 2006-08-21 Time 10:32 Sent To  
Notes
2006-08-16 00:00:00NEEDS, AS SPACE IS NOT ALL OF 4TH FLR
 AND SUITE IS NEEDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-03 Cont ID  
Sent By amorse Date 2006-10-03 Time 07:10 Rev Time 0.00
Received By amorse Date 2006-10-03 Time 07:10 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By amorse Date 2006-09-12 Time 16:03 Rev Time 0.00
Received By amorse Date 2006-09-12 Time 16:03 Sent To  
Notes
2006-09-12 00:00:00 
  
 DENIED
  
 PER COMMENT #2 ON 1ST REVIEW FURTHER
 COMMENTS ARE REQUIRED BY COMPLETE FLOOR
 AREA UNDER ONE TENANT.
  
 1) PROVIDE THE OCCUPANT LOAD FOR
 COMPLETE FLOOR AREA
  
 2) ASSUMING AN OCCUPANT LOAD OVER 50 NEW
 EGRESS DOORS FROM OPEN OFFICE 100 ARE
 REQUIRED TO SWING IN DIRECTION OF EGRESS
 TRAVEL PER 1008.1.2 FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By amorse Date 2006-08-17 Time 11:26 Rev Time 0.00
Received By amorse Date 2006-08-17 Time 11:26 Sent To  
Notes
2006-08-17 00:00:00 
  
 DENIED
  
 1) PROVIDE CONSTRUCTION TYPE, OCCUPANCY,
 AND ALTERATION LEVEL USED FROM EXISTING
 BLDG CODE 2004
  
 2) PROVIDE INFORMATION THAT ENTIRE FLOOR
 IS ONE TENANT SPACE IF NOT FUTHER REVIEW
 COMMENTS MAY BE NECESSARY
  
 3) AREA OF WORK SHALL INCLUDE OFFICE 108
 AND AJACENT STORAGE IF MECHANICAL AND
 ELECTRICAL CHANGES ARE MADE
  
 4) REFERENCE HALL 10 ON DRAWING WHERE
 FLOORING IS CHANGED
  
 5) TRAVEL DISTANCE PER 1015.1 FBC SHALL
 BE FROM THE MOST REMOTE POINT (OFFICE
 #103) TO EXIT ALONG A NATURAL
 UNOBSRTUCTED PATH. PLEASE NOTE ON 1-A1
 TRAVEL RUNS THROUGH NEWLY CONSTRUCTED
 WALL
  
 6) ADDITIONAL PERMITS WILL BE REQUIRED
 FOR MECH AND ELECTRIC
  
 7) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 19:22 Sent To  
Notes
2006-09-08 00:00:00OLD VOIDED SHEETS WERE NOT REMOVED AND
 NEW SHEETS WERE NOT INSERTED INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING AS
 PREVIOUSLY NOTED AND REQUESTED.
 SUITE # WAS NOT PLACED ON PLANS ALSO AS
 PREVIOUSLY REQUESTED.
  
  
 AS SCOPE OF WORK HAS BEEN NOTED ON NEW
 ARCHITECTURAL SHEETS, OLD SHEETS NEED TO
 BE PLACED IN NEW SETS AND SUITE NUMBER
 NEEDS TO BE PLACED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 19:15 Sent To  
Notes
2006-08-16 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE COVER SHEETS
 REFERENCES A "204" LS CODE / NFPA-101.
 THIS SEEMS TO BE A MISPRINT. PLEASE SEE
 THAT PLANS FOR ELECTRICAL AND "A" SHEETS
 RELFECT THE FOLLOWING CODES AT A MIN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101
  
 2) NOTE: PLEASE SEE IT IS UNCLEAR IF
 THIS WORK IS PART OF A LARGER TENANT
 SPACE WHICH IS STILL PART OF THE SAME
 TENANT OCCUPANCY. PLEASE SEE SPACE AS
 SHOWN SEEMS TO BE PART OF OTHER AREAS
 BUT UNCLEAR ATTHIS TIME. THERE SEEMS
 TO BE RECEPTS AND LTS WHICH MAY BE PART
 OF ANOTHER TENANT, YET SHOWS BEING FED
 FROM THIS TENANT.
 PLEASE CLARIFY.
  
 3) NOTE: PLEASE KNOW IF THIS IS A NEW
 BUILD OUT FOR A NEW TENANT, PLEASE SEE
 FBC CHAPTER 13, 13-415.1.ABC.1.2, .1.2
 AND .1.3 FOR CONTROL OF LIGHTING.
  
 4) NOTE: PLEASE KNOW PLANS MENTIONS 4TH
 FLR, YET THERE SHOULD BE SOME SORT OF
 SUITE/UNIT NUMBER FOR TENANT.
 PLEASE KNOW PLANS WILL BE REVIEWED BY
 THE ADDRESSING REVIEWER AND ONCE A SUITE
 # IS VERIFIED, PLEASE PLACE THAT NUMBER
 ON SAID PLANS.
 FAC 61G1-16.004
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 10:14 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 10:14 Sent To  
Notes
2006-09-13 00:00:00***PROVISO***
  
 1) PLEASE SEE BUILDING COMMENT (2)
 REGARDING DOOR SWING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By mwennerg Date 2006-08-25 Time 12:41 Rev Time 0.00
Received By mwennerg Date 2006-08-25 Time 12:41 Sent To  
Notes
2006-08-25 00:00:00***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) PERMIT APPLICATION AND PLANS INDICATE
 4TH FLOOR, HOWEVER IT IS UNCLEAR IF SAME
 TENANT OCCUPIES ENTIRE FLOOR OR JUST A
 SPACE. PLEASE ADVISE.
  
 3) PLEASE SEE BUILDING REVIEW COMMENT
 (5) REGARDING TRAVEL DISTANCE.
  
 4) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE ALARM REMODEL IN
 ADDITION TO FIRE SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:38 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:38 Sent To B
Notes
2006-10-02 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 17:11 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 17:11 Sent To  
Notes
2006-09-08 00:00:00TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-25 Cont ID  
Sent By mwennerg Date 2006-08-25 Time 13:09 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 16:36 Sent To  
Notes
2006-08-16 00:00:00TO "BOB"#3
2006-08-08 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 14:45 Rev Time 0.20
Received By tgordon Date 2006-08-17 Time 14:45 Sent To  
Notes
***NONE***