Plan Review Details - Permit 06080399
Plan Review Stops For Permit 06080399
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-25 Cont ID  
Sent By amorse Date 2006-09-25 Time 07:07 Rev Time 0.00
Received By amorse Date 2006-09-25 Time 07:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-14 Cont ID  
Sent By amorse Date 2006-09-14 Time 09:18 Rev Time 0.00
Received By amorse Date 2006-09-14 Time 09:18 Sent To PC
Notes
2006-09-14 00:00:00 
  
 DENIED
  
 PREVIOUS PLAN REVIEW NOTES WERE NOT
 ADDRESSED
  
 ***************************************
 3) CORRECT ENGINEERING SHEETS TO COMPLY
 WITH THE 2004 FLORIDA BLDG CODE AND ASCE
 7-02 ALSO INCLUDE THE WIND DESIGN DATA
 PER 1603.1 FBC AND SIGN,SEAL AND DATE
 EACH SHEET THAT HAS THIS INFORMATION.
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
 ***************************************
  
 PLEASE NOTE THAT WE ARE NOT USING THE
 SOUTH FLORIDA BUILDING CODE BUT THE
 FLORIDA BUILDING CODE 2004
  
 NEW COMMENTS
  
 1) PROVIDE WIND DESIGN DATA ON
 ENGINEERED DRAWINGS PER 1603.1.4 FBC
  
 2) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-27 Cont ID  
Sent By amorse Date 2006-08-27 Time 14:21 Rev Time 0.00
Received By amorse Date 2006-08-27 Time 14:21 Sent To PC
Notes
2006-08-27 00:00:00 
  
 DENIED
  
  
 1) AWNINGS SHALL BE DESIGNED SO THAT
 FABRIC OR MEMBRANE COVER CAN BE QUICKLY
 AND EASILY REMOVED PER 3105.4.2.1
 TIGHTLY WRAPED OR WOVEN CORDS ARE
 ACCEPTABLE WHEN 2 COPIES OF A DETAILED
 INSTRUCTION GUIDE FOR REMOVAL ARE
 INCLUDED IN THE SUBMITTAL.
 IN ADDITION 2 COPIES OF A NOTORIZED
 LETTER OF INTENT TO REMOVE AT 75 MPH ARE
 REQUIRED
  
 3) CORRECT ENGINEERING SHEETS TO COMPLY
 WITH THE 2004 FLORIDA BLDG CODE AND ASCE
 7-02 ALSO INCLUDE THE WIND DESIGN DATA
 PER 1603.1 FBC AND SIGN,SEAL AND DATE
 EACH SHEET THAT HAS THIS INFORMATION.
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 16:37 Sent To B
Notes
2006-09-22 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 13:58 Sent To B
Notes
2006-09-13 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 09:58 Sent To B
Notes
2006-08-15 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-27 Time   Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 16:48 Sent To  
Notes
2006-08-10 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-14 Cont ID  
Sent By mmclean Date 2006-08-14 Time 16:40 Rev Time 0.00
Received By mmclean Date 2006-08-14 Time 16:40 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved