Plan Review Details - Permit 06080306
Plan Review Stops For Permit 06080306
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-04 Cont ID  
Sent By alange Date 2006-10-04 Time 14:44 Rev Time 0.00
Received By alange Date 2006-10-04 Time 14:44 Sent To  
Notes
2006-10-04 00:00:00BUILDING REVIEW OK.SEE ELECTRICAL
 REVIEW COMMENTS THAT NEED TO BE
 ADDRESSED PRIOR TO ISSUING OF THE
 PERMIT.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By alange Date 2006-08-16 Time 16:30 Rev Time 0.00
Received By alange Date 2006-08-16 Time 16:30 Sent To  
Notes
2006-08-16 00:00:00DENIED
  
 1. A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 2.DOORS OPENING INTO THE PATH OF
 EGRESS TRAVEL SHALL NOT REDUCE THE
 REQUIRED WIDTH TO LESS THAN ONE-HALF
 DURING THE COURSE OF THE SWING. WHEN
 FULLY OPEN, THE DOOR SHALL NOT PROJECT
 MORE THAN 7 INCHES INTO THE REQUIRED
 WIDTH.FBC 1005.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 17:11 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 17:04 Sent To  
Notes
2006-09-24 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE KNOW, IT HAS BEEN
 CONFIRMED WITH TEH STATE'S LEGAL COUNSEL
 TO THE BOARD OF ARCHITECTS, AS PER FS
 481.223(1)(A), 481.229(1)(C), PLANS MUST
 BE DONE BY AN ARCHITECT AT A MINIMUM.
 A "DESIGN" OR "DRAFTING" FIRM MAY NOT DO
 PLANS UNLESS DIRECTLY "EMPLOYED" BY AN
 ARCHITECT OR ENGINEER. WHICH WOULD MEAN
 EMPLOYMENT WITH W-2'A WORKER'S COMP ETC.
 THIS OFFICE HAS GIVEN NOTICE TO A&J
 TECHNOLOGIES THAT THIS IS NOT PERMITTED.
 PLEASE SEE FS 481.229 AS NOTED ABOVE,
 MAY NOT DO COMMERICAL PLANS FOR
 ARCHITECTURE NO MATTER THE VALUE.
  
 ** PLEASE ADDRESS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 20:12 Sent To  
Notes
2006-08-16 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE KNOW PLANS MUST CONTAIN
 RESPONSIBILITY TAKEN BY THE DESIGN
 PROFESSIONAL. "DRAWN BY; PRINTED NAME
 AND SIGNATURE" ETC.
 FBC 106.1.2
  
 2) NOTE: PLEASE INDICATE NEW CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 408.4, 240.4, 310.16
  
 3) NOTE: PLEASE DECLARE WHAT
 CHEMICALS/USE WILL BE IN THE "MIXING
 ROOM" AS SHOWN. WILL THIS ROOM CONTAIN
 QUANITIES OF ANY FLAMMABLE LIQUIDS FOR
 MIXING ETC?
 NFPA-30,30B
 SEE FIRE REVIEW COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-18 Cont ID  
Sent By mwennerg Date 2006-10-18 Time 09:38 Rev Time 0.00
Received By mwennerg Date 2006-10-18 Time 09:38 Sent To  
Notes
2006-10-18 09:42:11***DENIED***
  
 1) COMMENT (2) FROM LAST FIRE REVIEW REQUESTED
 ADDITIONAL INFORMATION REGARDING PROPOSED MATERIAL FOR
 MIXING ROOM. NO RESPONSE COULD BE FOUND WITH
 RESUBMITTAL.
  
 2) PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By mwennerg Date 2006-08-25 Time 15:39 Rev Time 0.00
Received By mwennerg Date 2006-08-25 Time 15:39 Sent To  
Notes
2006-08-25 00:00:00***DENIED***
  
 1) PLEASE SHOW LOCATION OF 2A-10B,C
 RATED FIRE EXTINGUISHER(S).
  
 2) PLEASE CLARIFY THE USE OF THE NEW
 MIXING ROOM. NOTE (1) ON SHT 1.1
 REFERENCES MIXING PAINT. PLEASE INDICATE
 MATERIALS AND OR CHEMICALS THAT WILL BE
 USED IN REFERENCED ROOM.
  
 3) IN ADDITION TO APPLICABE BUILDING
 CODES, LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT MAY
 BE REQUIRED FOR FIRE SPRINKLER REMODEL.
 PLEASE INDICATE HOW EXISTING FIRE
 SPRINKLER SYSTEM WILL BE IMPACTED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 15:24 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 15:24 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#13
2006-09-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-26 Cont ID  
Sent By mmiller Date 2006-08-26 Time 08:37 Rev Time 0.00
Received By jleech Date 2006-08-04 Time 13:47 Sent To  
Notes
2006-08-16 00:00:00TO "BOB"#2
2006-08-08 00:00:008/8/06-WAITING FOR "BOB"
2006-08-04 00:00:00SENT "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-10-18 Time 15:58 Rev Time 0.30
Received By tgordon Date 2006-10-18 Time 15:58 Sent To  
Notes
2006-10-18 16:03:19*** DENIED ***
 1) MECHANICAL PAGE M-3 WAS NOT WITH REVISED PLANS, IF
 YOU WANT TO SUBMIT THE PREVIOUS APPROVED STAMPED COPYS
 THEN YOU NEED TO SUBMIT BOLTH COPYS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-08-17 Time 14:14 Rev Time 0.00
Received By tgordon Date 2006-08-17 Time 14:13 Sent To  
Notes
2006-08-17 00:00:00*** PROVISO ***
 1) IF MIXING ROOM WILL HOUSE ANY NOXIOUS
 GASES, FUMES, OR ODERS THEN RETURN AIR
 MAY NOT GO BACK TO THE AIR HANDLER UNIT,
 BUT MUST BE EXHAUSTED TO THE OUTDOORS,
 PER 2004 FBC/M 502.1.3 AND 502.1.4 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 14:07 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 14:06 Sent To  
Notes
2006-10-21 14:10:18NO PAGE 3.1 IN NEW SET OF PLANS AND ONLY ONE COPY OF
 OLD SET OF PLANS PLEASE PROVIDE TWO SETS OF PAGE 3.1
 WITH NEW SET OF PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 08:37 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 08:37 Sent To  
Notes
***NONE***