Plan Review Details - Permit 06080288
Plan Review Stops For Permit 06080288
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-20 Cont ID  
Sent By rmcdouga Date 2007-03-20 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2007-03-20 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By rmcdouga Date 2006-08-17 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2006-08-17 Time 07:05 Sent To  
Notes
2006-08-17 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ADDRESS COMMENTS FROM OTHER REVIEWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By dpalmer Date 2007-03-05 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-03-05 Time 08:45 Sent To  
Notes
2007-03-05 09:06:24STAMPED REVISED SHEETS AND SPECS FOR PUMP.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 19:50 Sent To  
Notes
2006-08-16 00:00:00* UNSAT *
  
 1) NOTE: PLEASE BE SURE THE PLANS
 REFLECT THE FOLLWOIGN CODES AT A MIN.
 NFPA-70 2002, NFPA-30A 2003.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT SHWOIGN
 THE CLASS LOCATIONS AS SPECIFIED IN NEC
 ART 514.
  
 3) NOTE: PLEASE SHOW ALL ELECTRICAL
 EQUIPMENT ON ELECTRICAL SITE PLAN AS
 SHOWN ON RISER DIAGRAM.
 FBC 106.1.2, NEC 514
  
 4) NOTE: PLEASE PROVIDE MANUFACTURES
 SPECS/CUT SHEETS ON EQUIPMENT /FUEL
 PUMPS, TANKS ETC. PLEASE SEE COMMENTS
 FROM OTHER TRADES WHICH MAY ALSO REQUIRE
 TO REVIEW SUCH ITEMS.
 PLEASE BE SURE ALL ARE LISTED BY A NRTL.
 110.3,90.7
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-08 Cont ID  
Sent By mwennerg Date 2007-03-08 Time 14:54 Rev Time 0.00
Received By mwennerg Date 2007-03-08 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By mwennerg Date 2006-09-15 Time 15:16 Rev Time 0.00
Received By mwennerg Date 2006-09-15 Time 15:16 Sent To  
Notes
2006-09-15 00:00:00***DENIED***
  
 1) PRODUCT APPROVALS WILL BE REQUIRED
 FOR THE PROPOSED FUEL TANKS. INFORMATION
 REGARDING THE CONSTRUCTION, FIRE RATING,
 DOCUMENTED LISTINGS OR APPROVALS FROM
 THIRD PARTY TESTING AGENCIES, AND ANY
 APPLICABLE BALLISTIC TESTING RESULTS.
  
 2) WHO WILL BE RESPONSIBLE FOR FUELING
 OPERATIONS?
  
 3) IN ADDITION TO NO SMOKING AND STOP
 ENGINE, APPROPRIATE WARNING SIGNS SHALL
 INDICATE THE TYPE OF PORTABLE CONTAINERS
 THAT CAN BE FILLED, AND EMERGENCY SHUT
 OFF WORDING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 09:47 Sent To  
Notes
2007-02-28 09:56:32TO "COMM" BD#18
2007-02-26 09:48:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 14:01 Rev Time 0.00
Received By tgordon Date 2006-08-03 Time 16:53 Sent To  
Notes
2006-08-16 00:00:00TO "COMM" BD#25
2006-08-08 00:00:008/8/06-WAITING FOR "COMM" BD
2006-08-03 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 10:56 Rev Time 0.20
Received By tgordon Date 2007-03-19 Time 10:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 14:01 Rev Time 0.20
Received By tgordon Date 2006-09-19 Time 14:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-08-25 Cont ID  
Sent By kstevens Date 2006-08-25 Time 07:23 Rev Time 0.00
Received By kstevens Date 2006-08-25 Time 07:23 Sent To  
Notes
2006-08-25 00:00:00GASOLINE FUEL TANKS. - NO FUEL GAS
 REVIEW REQUIRED

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-04 Cont ID  
Sent By jroach Date 2007-03-04 Time 13:52 Rev Time 0.00
Received By jroach Date 2007-03-04 Time 13:52 Sent To  
Notes
2007-03-04 13:53:00***PROVISO***
  
 1) PARKING STRIPING SHALL BE IN ACCORDANCE WITH THE
 ATTACHED PAINTING DETAIL.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By jroach Date 2006-09-05 Time 15:41 Rev Time 0.00
Received By jroach Date 2006-09-05 Time 15:41 Sent To  
Notes
2006-09-05 00:00:009/5/06 ***FAILED***
  
 1) PER SECTION 94-482(C) OF THE CITY OF
 WPB ZONING AND LAND DEVELOPMENT
 REGULATIONS, OFF-STREET PARKING SHALL
 NOT BE REDUCED TO AN AMOUNT LESS THAN
 REQUIRED FOR THE BUILDING SQUARE
 FOOTAGE.PROPOSED TANKS APPEAR TO BE
 PLACED IN EXISTING PARKING.
  
 2) A SURVEY OF THE EXISTING PROPERTY,
 DATED WITHIN THE LAST YEAR, SHALL BE
 PROVIDED.
  
 3) PER SECTION 94-444(B) OF THE CITY OF
 WPB ZONING AND LAND DEVELOPMENT
 REGULATIONS, A FOUR-SIDED ENCLOSURE
 SHALL BE PROVIDED AS SCREENING.
 SCRRENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND
 STEEL.WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO (2)
 FOOT INTERVALS.
  
 4) LANDSCAPE PLAN, SIGNED AND SEALED BY
 A LICENSED LANDSCAPE ARCHITECT, SHALL BE
 PROVIDED INDICATING THE ABOVE-REFERENCED
 LANDSCAPE REQUIREMENTS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.