Plan Review Details - Permit 06080177
Plan Review Stops For Permit 06080177
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-25 Cont ID  
Sent By rnuquist Date 2006-11-25 Time 12:32 Rev Time 0.00
Received By rnuquist Date 2006-11-25 Time 12:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By amorse Date 2006-08-18 Time 06:40 Rev Time 0.00
Received By amorse Date 2006-08-18 Time 06:40 Sent To PC
Notes
2006-08-18 00:00:00 
  
 DENIED
  
  
 1) PER 1609.6.1 THE SIMPLIFIED
 CALCULATION METHOD FOR WIND LOADS SHALL
 NOT BE USED TO DETERMINE WIND PRESSURES
 FOR BUILDINGS OVER 60 FT IN HEIGHT.
 PLEASE SUBMIT ENGINEERED CALCULATIONS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 11:20 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 11:20 Sent To B
Notes
2006-11-17 11:20:42TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-18 Time   Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 08:18 Sent To  
Notes
2006-08-03 00:00:00TO "MISC' BOX#1