Plan Review Details - Permit 06080061
Plan Review Stops For Permit 06080061
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-22 Cont ID  
Sent By rmcdouga Date 2007-03-22 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2007-03-22 Time 07:09 Sent To  
Notes
2007-03-22 07:57:58REVISED SHEETS A1, A6, A7 AND NEW DRAWINGS SK1 AND SK4
 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-23 Cont ID  
Sent By rmcdouga Date 2007-01-23 Time 06:48 Rev Time 0.00
Received By rmcdouga Date 2007-01-22 Time 18:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-13 Cont ID  
Sent By rmcdouga Date 2006-11-13 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2006-11-09 Time 16:19 Sent To  
Notes
2006-11-09 16:57:29DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. PRODUCT APPROVALS HAVE NOT
 BEEN APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3)SUBMIT ENERGY CALCULATIONS AND FORMS AS REQUIRED BY
 FBC 13-101.1.3 FOR RENOVATED COMMERCIAL BUILDINGS.
 ADDITIONAL CONDITIONED SPACE IS BEING ADDED THAT WAS
 PREVIOUSLY UNCONDITIONED. (2 COPIES)
  
 4) ALL DOORS REQUIRED TO BE ACCESSIBLE BY FBC 11-4.1.6
 ARE REQUIRED TO HAVE HARDWARE WHICH COMPLIES WITH
 11-4.13.9. THE NOTES ON THE DOOR SCHEDULE DO NOT
 ADDRESS ALL OF THE DOORS THAT ARE REQUIRED TO BE
 ACCESSIBLE.
  
 5) THE STOREFRONT SHOP DRAWINGS FROM THE ENGINEER
 (THOMAS J. TWOMEY) ARE REQUIRED TO BE SIGNED AND
 SEALED. SEE FAC 61G15-23.002 AND CHAPTER 471, F.S.
  
 6) THE CODE SECTION FOR THE REQUIRED ACCESSIBLE COUNTER
 IS INCORRECTLY LISTED AS 11-4.33. THE CORRECT SECTION
 IS FBC 11-7.2(2). ALSO AN AUXILIARY COUNTER NOT TABLE
 IS REQUIRED AS ONE OPTION. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By rmcdouga Date 2006-08-16 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2006-08-16 Time 07:08 Sent To  
Notes
2006-08-16 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE 2004 EXISTING BUILDING CODE ALSO
 APPLIES AND IS NOT NOTED ON D-1.
  
 3) SPECIFY THE LEVEL OF ALTERATION FROM
 THE EXISTING BUILDING CODE.
  
 4) THE CONSTRUCT TYPE SPECIFIED ON D-1
 IS TYPE IV-B. UNDER THE 2004 FBC THIS IS
 HEAVY TIMBER CONSTRUCTION. SEE FBC
 CHAPTER 6.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS, STOREFRONTS,
 OVERHEAD DOORS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 6) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) SUBMIT ENERGY CALCULATIONS AS
 REQUIRED BY FBC 13-101.
  
 8) PROVIDE A BUCK DETAIL FOR THE NEW
 OVERHEAD GARAGE DOOR.
  
 9) THE EXIT LIGHT AT THE LOUNGE DOOR
 SHOWN ON THE A6 LIGHTING PLAN IS NOT
 SHOWN ON THE A2.
  
 10) NEW ENTRANCE MUST BE ACCESSIBLE.
 SHOW COMPLIANCE. SEE FBC 11-4.1.6 (1),
 (2) & (3) AND 114.14.
  
 11) RENTAL SERVICE COUNTER MUST COMPLY
 WITH FBC 11-7.2.
  
 12) THE HEIGHT OF THE BASE CABINETS
 SHALL COMPLY WITH FBC 11-4.33.
  
 13) DOOR HARDWARE SHALL COMPLY WITH FBC
 11-4.13.9.
  
 14) THE INTERIOR DOOR TO THE LOUNGE MUST
 COMPLY WITH FBC 11-4.13.6. 18" CLEAR ON
 THE PULL SIDE OF DOOR AT LATCH.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-03-28 Cont ID  
Sent By dpalmer Date 2007-03-28 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2007-03-28 Time 13:01 Sent To PC
Notes
2007-03-28 13:02:52SUBMITTAL LETTER TO ALLOW THE USE OF MC CABLE OK,
 STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 09:01 Sent To  
Notes
2007-03-18 09:09:22REV #4, STAMPED

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 18:35 Sent To  
Notes
2007-03-02 18:43:32STAMPED ELEC SHEETS, SUBMITTAL FOR TRANSFER PANEL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-07 Cont ID  
Sent By dpalmer Date 2007-01-07 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2007-01-06 Time 20:09 Sent To  
Notes
2007-01-07 10:54:32** UNSAT 3RD REVIEW **
  
  
 1) NOTE: PLEASE PROVIDE CALCULATIONS AS REQUESTED ON
 THE TWO PREVIOUS REVIEWS. RESPONSE LETTER MENTIONS TO
 SEE SHEET A-7, HOWEVER SHEET A-7 ONLY SHOWS THE PANEL
 SCHEDULE AND SOME CONNECTED LOADS. PLEASE SEE 220.3,
 220.10, 220.11 220.13 ETC
 ALL CONTINUOUS LOADS PER 215.3, 230.42
  
 2) NOTE:PLEASE SEE 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS FOR SHOW
 WINDOWS. PLEASE SEE HOW LOADS SHALL BE FIGURED FOR
 BRACNH CIRCUITS AND FOR FEEDERS. PLEASE SEE THERE IS NO
 BREAK DOWN OR INFORMATION REGARDING LOADS ON WINDOWS
 AND HOW THESE LOADS WERE DERIVED.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS THE 2ND SET OF
 PLANS WHICH CAME IN CONTAIN A COMPLETELY NEW RISER
 THERE WERE NEW COMMENTS. PLEASE SEE THAT IS WAS
 REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS
 FOR THE EMERGENCY PANEL/MTS WHICH WAS BEING INSTALLED.
 PLEASE SEE THERE ARE SPEC SHEETS IN THE PACKAGE HOWEVER
 THEY ARE FOR COUNTLESS PANELS AND EQUIPMENT. PLEASE
 ONLY SUBMIT THAT WHICH CORRELATES TO PLANS AND THAT
 WHICH IS RELEVANT TO THIS INSTALLATION. PANELS AND
 SPECS FOR ALL THE OTHERS AS SUBMITTED WILL HAVE NO
 BEARING ON THIS JOB.
 110.3, 90.7.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW FOR REQUIRED
 DISCONNECTING MEANS FOR THE FEED FROM THE GEN.IF IN
 AN EMERGENCY THE GENERATOR IS RUNNING AND CAN NOT BE
 SHUT OFF, WHEN MAINS AND DISCONNECTING MEANS ARE NOT
 GROUPED, UNPLUGGING THE GENERATOR WHILE UNDER LOAD IS
 NOT PERMITTED AND IS A SAFETY ISSUE FOR ANY PERSONNEL.
 PLEASE SEE NOTE#7 ON A-6 STILL MENTIONS ALL ELECTRICAL
 PANELS AND SERVICEEQUIPMENT IS EXISTING, YET PLANS
 SHOW MANY OF THESE ITEMS AS NEW?
 PLEASE CORRELATE NOTES, PLANS, RISER, PANELS ETC.
 225.31-225.39, 230.72
  
 5) NOTE: PLEASE KNOW IT HAS BEEN DISCOVERED SINCE THE
 LAST REVIEW THIS IS A BUILD OUT OF WHAT USED TO BE AN
 OLD SERVICE GARAGE AND WOULD BE A CHANGE IN OCCUPANCY.
  
 PLEASE SUBMIT ENERGY CALCULATIONS PER 2004 FBC.
 13-415.1.AB.1
 THIS WAS NOT PREVIOUSLY REQUESTED AS THIS WAS APPLIED
 AS EXISTING CAR SALES OFFICE AND EXISTING TENANT FOR
 SAME USE.
  
 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE. PLEASE SEE A FEE OF $2100.00 HAS NOW
 BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS REQUIRED
 PER THE FLORIDA STATUTES AS GIVEN. THIS FEE IS BEING
 ADDED TO THEEXISTING 4X FEE FOR STARTING WORK WITHOUT
 PERMITS WHICH WAS ALREADY ADDED TO THIS JOB. PLEASE SEE
 THIS FEE IS REQUIRED TO BE PAID BEFORE RESUBMITTING OF
 PLANS FOR THE NEXT REVIEW. PLEASE ALSO KNOW ONE SET OF
 EACH OF THE PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-06 20:09:502007-01-06 20:09:50
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 17:16 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 16:47 Sent To  
Notes
2006-10-28 17:16:06***UNSAT 2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO COMPLETE CHNAGE IN THE SERVICE AS NOW
 SUBMITTED.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH NEW NOTES ADDED TO THE BOTTOM.
  
 1) NOTE:NO, SAME NOTE.
 RESPONSE MENTIONS TO SEE 6 AND 7, HOWEVER NOT COMPLETE
 FOR NEW PANEL EM AS THE LOADS ARE NOT EVEN SHOWN AND
 COULD NOT LOCATE ANY LOAD CALCULATIONS FOR SERVICE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE CALCULATIONS FOR
 EXISTING SERVICE PER 220.3,220.10,220.11
 220.13 ETC
 ALL CONTINUOUS LOADS PER 215.3,230.42
  
 2) NOTE: NO/OK, RECEPTS ADDED, HOWEVER LOADS AND LOADS
 IN CALCULATIONS NOT SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.62, FOR MISSING
 SHOW WINDOWS OUTLETS REQUIRED ABOVE
 WINDOWS.
 "TO DISCOURAGE FLOOR RECEPTACLES AND
 UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS."
  
 3) NOTE:OK.
  
 4) NOTE: OK.
  
 *** NEW NOTE DUE TO COMPLETLY NEW RISER SUBMITTED. **
  
 5) NOTE: PLEASE SEE A NEW MTS PANEL IS BEING SHOWN,
 HOWEVER PLEASE SUBMIT MANUFACTURES SPACES/CUT SHEETS
 FOR THIS PANEL/ MTS.
 PLEASE SEE THIS UNIT ON RISER DOES NOT CORRELATE WITH
 THE EM AS SHOWN ON SHEET 7.
 110.3,90.7, 225.31-225.39 ETC
  
 6) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR
 POWER FROM GEN, OR-THE MTS IS TO BE LOCATED OUTSIDE, OR
 THERE ARE NUMEROUS OTHER SCENARIOS WHICH CAN BE DONE .
 PLEASE SEE NOTE ABOVE.
  
 7) NOTE: PLEASE SEE NOW A RISER IS BEING SUBMITTED,
 HOWEVER PLEASE LABEL AND CORRELATE ALL EQUIPMENT AND
 SIZES FROM PANELS TO RISER. PLEASE COMPLETE RISER
 DIAGRAM WITH ALL CONDUCTORS AND THE CORRECT AMOUNT.
 PLEASE SEE RISER SHOWS SEC'S, HOWEVER THE # OF
 CONDUCTORS DO NOT ADD UP???
 PLEASE SEE THE FEEDERS FOR THE PANEL "A" ARE NOT SHOWN
 ON RISER , HOWEVER NOTED ON PANEL "A" AS EXISTING 150A
 RATED?PLEASE EXPLAIN THIS AS THE RISER NOW INDICATES
 NEW 200A FUSES FEEDING THE EXISTING 150A FEEDERS.
 PLEASE COMPLETE RISER. 240.4,310.16, 215.5 ETC
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE MISPRINT FOR THE EQUIPMENT
 GROUNDING CONDUCTOR ON PANEL "EM", SHOWS #60 FOR #6.
  
 9) NOTE: PLEASE SEE COLOR CODING SHALL BE BLACK,
 ORANGE, RED. IF INDEED AS NOTED. PLEASE SEE LABELING OF
 277/480 CAN NOT BE "ORANGE" ON "B" PHASE, IF CODE
 REQUIRES ORANGE FOR A "HIGH-LEG" 277/480V SYSTEMS ARE
 NOT "HIGH-LEGS".
 PLEASE ADJUST.
 300.
  
 10) NOTE; PLEASE SHOW LOCATION OF RECEPT AND NEMA
 RATING. PLEASE SUBMIT SPEC ON RECEPT FOR WP LOCATION.
 110.3,90.7.
 FBC 106.1.2 ADMIN SECT.
  
 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED
 TO NOTED WITH RESPECT TO REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN ATTHIS TIME.
  
  
 ** PLEASE KNOW, AS RISER HAS MANY COMMENTS, PLEASE
 ADDRESS ALL.
 PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED THERE MAY BE COMMENTS ON NEXT REVIEW.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 20:56 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 20:42 Sent To  
Notes
2006-08-11 00:00:00***UNSAT **
  
 1) NOTE: PLEASE PROVIDE CACULATIONS FOR
 EXISTING SERVICE PER 220.3,220.10,220.11
 220.13 ETC
 ALL CONTINUOUS LOADS PER 215.3,230.42
  
 2) NOTE: PLEASE SEE 210.62, FOR MISSING
 SHOW WINDOWS OUTLETS REQUIRED ABOVE
 WINDOWS.
 "TO DISCOURAGE FLOOR RECEPTACLES AND
 UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS."
  
 3) NOTE: PLEASE SEE ALL RECEPTS IN CAR
 PREPARATION AREA SHALL BE GFI PROTECTED.
 210.8B
  
 4) NOTE: PLEASE SEE THE 2002 NEC IS THE
 CURRENT EDITION ADOPTED BY THE STATE.
 PLEASE LIST.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 10:38 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 10:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 16:07 Rev Time 0.00
Received By mawillia Date 2007-01-25 Time 16:07 Sent To  
Notes
2007-01-25 16:11:17*****APPROVED*****
  
  
  
 PLAN SHEET A-2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 13:39 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 13:39 Sent To  
Notes
2006-12-05 13:55:16*****APPROVED*****W/ PROVISO
  
  
  
  
 1.AS PER THE REFERENCED LIFE SAFETY CODE - NFPA 101-
 7.6.1, SHOW THE TRAVEL DISTANCE TO AN EXIT MEASURED ON
 THE FLOOR OR OTHER WALKING SURFACE.IN AN
 UNSPRINKLERED BUILDING , THE TRAVEL DISTANCE SHALL NOT
 EXCEED 200 FEET.
  
  
 ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 OF 10/06/2006 HAVE BEEN ADDRESSED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By mawillia Date 2006-10-06 Time 14:47 Rev Time 0.00
Received By mawillia Date 2006-10-06 Time 14:15 Sent To  
Notes
2006-10-06 00:00:00*****DENIED*****
  
  
  
  
 1.) NFPA 101,2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE,2004 SHALL BE
 REFERENCED.
  
 2.) CONSTRUTION, ALTERATION, AND
 DEMOLITION OPERATIONS TO COMPLY WITH
 NFPA 241.
  
 3.) ON SHEET A-1, SHOW HOW THE NUMERICAL
 ADDRESS WILL BE DISPLAYED. AS PER WEST
 PALM BEACH CODE, NUMERICAL ADDRESS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH VISIBLE FROM SOUTH DIXIE HIGHWAY.
  
 3.) INTERIOR FINISH, WALLS, AND CEILING
 (IN A NON-SPRINKLERED BUILDING) SHALL BE
 CLASS "A" OR CLASS "B".
  
 4.) IF THE SCOPE OF THE INTERIOR WORK
 INCLUDES THE ADDITION OR MODIFICATION OF
 THE FIRE PROTECTION SYSTEM, SEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS ARE
 REQUIRED.
  
 5.) ON SHEET D-1, TWO EXITS ARE STATED.
 ONLY ONE EXIT IS SHOWN ON THE PLANS,
 WHERE IS THE SECOND EXIT?
  
  
  
 CAPTAIN MICHAEL A. WILLIAMS
 FIRE PREVENTION REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 18:36 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 18:36 Sent To E
Notes
2007-03-27 18:36:24TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 11:56 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 11:56 Sent To  
Notes
2007-03-12 11:57:51TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 16:22 Sent To  
Notes
2007-02-27 09:37:27TO "COMM" BD#21
2007-02-22 16:22:42WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 15:12 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 15:12 Sent To  
Notes
2006-12-15 15:12:55WAITAING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 11:03 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 11:02 Sent To  
Notes
2006-10-26 08:47:47TO "COMM" BD#22
2006-10-24 11:03:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-06 Cont ID  
Sent By mawillia Date 2006-10-06 Time 14:14 Rev Time 0.00
Received By mawillia Date 2006-08-02 Time 11:23 Sent To  
Notes
2006-08-11 00:00:00TO "COMM" BD#52
2006-08-02 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-19 Cont ID  
Sent By rregueir Date 2007-01-19 Time 15:35 Rev Time 0.00
Received By rregueir Date 2007-01-19 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By rregueir Date 2006-11-02 Time 18:40 Rev Time 0.00
Received By rregueir Date 2006-11-02 Time 18:40 Sent To  
Notes
2006-11-02 18:49:37--------------------DENIED-----------------
  
 FBC 2004
 FBC,EB 2004
 FBC,M 2004
  
 1. PER FBC,EB SEC.609.1, PLEASE SHOW COMPLIANCE WITH
 VENTILATION REQUIREMENTS OF FBC,M SEC.402 OR 403.
  
 2. PER FBC,EB SEC.509.1 ANY COMPONENT OF THE EXISTING
 A/C SYSTEM SHOWN TO BE DEFECTIVE SHALL BE REPAIRED OR
 REPLACED - FBC,M 301.11
  
 3. CAR RENTAL AREA SHOWS NEW R/A GRILL IN CEILING WITH
 NO DUCT ATTACHED. PLAN NOTE SAYS ALL RETURNS TO BE
 DUCTED. THIS R/A GRILL MAY BE DELETED DUE TO FREE FLOW
 RETURN BACK TO THE 48X36 CENTRALIZED RETURN IN THE
 VESTIBULE.
  
 4. THE TWO 12" ROUND R/A JUMPERS DO NOT MEET THE
 BALANCED RETURN EXCEPTIONS OF FBC,M 601.4.UNLESS THE
 DUCTS ARE DESIGNED TO MEET THE EXCEPTIONS, A FIELD TEST
 WILL BE REQUIRED AT FINAL INSPECTION TO SHOW COMPLIANCE
 WITH THE MAXIMUM ALLOWABLE PRESSURE DIFFERENTIAL OF
 THIS SECTION (0.01" WC).
  
 5. PG A1 DETAIL #5 - ROOF INSULATION SHALL NOT BE
 INSTALLED ON A SUSPENDED CEILING WITH REMOVABLE CEILING
 PANELS PER FBC SEC. 13-404.1.ABC.1.SEE SEC. 13-B-1.3
 FOR INSULATION INSTALLATION REQUIREMENTS.
  
 REVIEWED BY:
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-26 Cont ID  
Sent By rregueir Date 2006-09-26 Time 16:57 Rev Time 0.00
Received By rregueir Date 2006-09-26 Time 16:51 Sent To  
Notes
2006-09-26 00:00:00-----------------DENIED----------------
 1.PLEASE PROVIDE A PLAN SHOWING
 SIZES,LOCATIONS AND CFM OF NEW AND
 EXISTING DUCTS.
  
 2.MECHANICAL CONTRACTOR'S INSURANCE HAS
 EXPIRED.A SEPARATE MECHANICAL PERMIT
 APPLICATION IS REQUIRED WITH ALL
 NECESSARY INFORMATION AND DOCUMENTATION
 PROVIDED.
  
 RONALD J REGUEIRO
 561.805.6734

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-04-05 Cont ID  
Sent By pschmitz Date 2007-04-05 Time 08:40 Rev Time 0.00
Received By pschmitz Date 2007-04-05 Time 08:40 Sent To  
Notes
2007-04-05 08:41:49PLUMBING REVISION, TURN AROUND.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-04-03 Cont ID  
Sent By kstevens Date 2007-04-03 Time 07:12 Rev Time 0.00
Received By kstevens Date 2007-04-02 Time 18:56 Sent To  
Notes
2007-04-03 07:13:31REVISION OK - MOVED DRINKING FOUNTAIN ALONG WITH THE
 SANITARY & WATER SUPPLY

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-10 Cont ID  
Sent By kstevens Date 2007-03-10 Time 13:08 Rev Time 0.00
Received By kstevens Date 2007-03-10 Time 13:08 Sent To  
Notes
2007-03-10 13:17:16PASSED/PROVISO--NO DEAD ENDS--FLOOR DRAIN LINE
 TO BE DELETED--CAPPED OFF LINE TO BE LEFT UNCOVERED
 UNTILL FIELD INSPECTION OF DEMO.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-01 Cont ID  
Sent By kstevens Date 2007-02-01 Time 11:17 Rev Time 0.00
Received By kstevens Date 2007-02-01 Time 11:17 Sent To  
Notes
2007-02-01 11:35:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****3RD REVIEW - FROM PREVIOUS REVIEWS:
  
 1. SHT D-1 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. INDICATE WHERE THE
 SANITARY PIPING WILL BE ABANDONED. POINT
 OF ABANDONMENT SHALL NOT BE COVERED
 PRIOR TO INSPECTIONS.
 ****RESPONSE NOTED.DETAIL 5 DOES NOT INDICATE WHERE
 THE FLOOR DRAINS HAVE BEEN DISCONNECTED FROM THE
 BUILDING DRAIN. PLEASE INDICATE WHERE THE FLOOR DRAINS
 WILL BE DISCONNECTED.DEMO INSPECTION WILL BE
 REQUIRED.
 ******RESPONSE NOTED, BUT THE NOTE INDICATING THAT THE
 FLOOR DRAINS WERE NOT CONNECTED TO THE SANITARY IS OF
 SOME CONCERN. IN A GARAGE AREA, THERE WOULD BE A
 REQUIREMENT FOR A SAND/OIL INTERCEPTOR, AND THERE IS
 ALSO A SECTION IN THE MUNICIPAL CODE THAT PROHIBITS
 CONNECTING FLOOR DRAINS IN A GARAGE TO THE STORM
 SYSTEM. VERIFICATION OF WHERE THE EXISTING FLOOR DRAINS
 ARE CONNECTED WILL BE REQUIRED. IF THE DRAINS ARE TO BE
 FILLED WITH CONCRETE, THE DRAIN PIPE SHALL BE
 DISCONNECTED AS THE DRAIN EXITS THE BUILDING, EITHER
 INSIDE OR OUTSIDE THE BUILDING. MR. RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE WILL BE CONTACTING THE
 CONTRACTOR AND OR OWNER TO VERIFY WHERE THE FLOOR
 DRAINS CONNECT. IF THERE IS AN OIL/SAND INTERCEPTOR, IT
 WILL BE ABANDONED PER CITY WEST PALM BEACH
 REQUIREMENTS.
  
 2. OK
  
 3. SHT A-5 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS PROVIDED SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS ARE
 STILL SHOWN IN THE CEILING, NOT NEAR THE FIXTURE AS
 REQUIRED.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR AT
 THE DRINKING FOUNTAIN IS STILL LOCATED IN THE CEILING.
  
 4. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By kstevens Date 2006-12-07 Time 13:48 Rev Time 0.00
Received By kstevens Date 2006-12-07 Time 13:48 Sent To  
Notes
2006-12-07 13:54:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****2ND REVIEW - FROM PREVIOUS REVIEW:
  
 1. SHT D-1 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. INDICATE WHERE THE
 SANITARY PIPING WILL BE ABANDONED. POINT
 OF ABANDONMENT SHALL NOT BE COVERED
 PRIOR TO INSPECTIONS.
 ****RESPONSE NOTED.DETAIL 5 DOES NOT INDICATE WHERE
 THE FLOOR DRAINS HAVE BEEN DISCONNECTED FROM THE
 BUILDING DRAIN. PLEASE INDICATE WHERE THE FLOOR DRAINS
 WILL BE DISCONNECTED.DEMO INSPECTION WILL BE
 REQUIRED.
  
 2. OK
  
 3. SHT A-5 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS PROVIDED SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS ARE
 STILL SHOWN IN THE CEILING, NOT NEAR THE FIXTURE AS
 REQUIRED.
  
 4. SHT A-5 WATER RISER DIAGRAM. FULL
 OPEN VALVES SHALL BE INSTALLED ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
 ****RESPONSE NOTED, BUT THE WATER DOWN FEED PIPE TO THE
 TOILET ROOM FIXTURES DOES NOT HAVE A FULL OPEN VALVE
 INSTALLED AT THE TOP AS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By kstevens Date 2006-08-25 Time 06:40 Rev Time 0.00
Received By kstevens Date 2006-08-24 Time 18:47 Sent To  
Notes
2006-08-25 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT D-1 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. INDICATE WHERE THE
 SANITARY PIPING WILL BE ABANDONED. POINT
 OF ABANDONMENT SHALL NOT BE COVERED
 PRIOR TO INSPECTIONS.
  
 2. SHT A-1 CAR PREPARATION AREA DRAIN
 MAY BE REQUIRED TO CONNECT TO A SAND/OIL INTECEPTOR.
 PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. (561)
 822-2271, (561 822-2279(FAX), OR E-MAIL
 [email protected].
  
 3. SHT A-5 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS PROVIDED SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 4. SHT A-5 WATER RISER DIAGRAM. FULL
 OPEN VALVES SHALL BE INSTALLED ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-25 Cont ID  
Sent By jroach Date 2007-01-25 Time 08:47 Rev Time 0.00
Received By jroach Date 2007-01-25 Time 08:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-22 Cont ID  
Sent By jroach Date 2006-11-22 Time 14:53 Rev Time 0.00
Received By jroach Date 2006-11-22 Time 14:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By jroach Date 2006-09-08 Time 12:04 Rev Time 0.00
Received By jroach Date 2006-09-08 Time 12:04 Sent To  
Notes
2006-09-08 00:00:009/8/06 ***FAILED***
  
 1) EXISTING STRUCTURE/SITE IS
 NONCONFORMING.AS PROVIDED IN SECTION
 94-441 OF THE CITY OF WPB ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS),
 RENOVATIONS EXCEEDING 50% OF THE
 ASSESSED VALUE OF THE STRUCTURE SHALL
 BRING THE SITE INTO CONFORMITY WITH
 REGARD TO ARTICLE XIV (LANDSCAPING) OF
 THE ZLDRS.
  
 2) A SITE PLAN AND LANDSCAPE PLAN
 (SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT) SHALL BE PROVIDED.
  
 3) INFORMATION SHALL BE PROVIDED SHOWING
 THE LOCATION OF CAR STORAGE FOR THE
 RENTAL BUSINESS.SUCH STORAGE SHALL BE
 SCREENED ACCORDING TO SECTION 94-444(C)
 OF THE CITY'S ZLDRS.
  
 4) SITE PLAN SHALL INDICATE THE LOCATION
 OF ADDITIONAL REQUIRED PARKING (NOT TO
 INCLUDE THAT OF THE VEHICLE STORAGE) FOR
 THE BUSINESS AS REQUIRED BY SECTION
 94-486 OF THE CITY'S ZLDRS.
  
 BASED UPON THE SUBMISSION OF THE
 ADDITIONAL MATERIALS REQUESTED ABOVE,
 OTHER COMMENTS MAY BE GENERATED.
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.
  