Plan Review Details - Permit 06080052
Plan Review Stops For Permit 06080052
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-12-05 Cont ID  
Sent By mperson Date 2006-12-05 Time 14:54 Rev Time 0.45
Received By mperson Date 2006-12-05 Time 14:54 Sent To PC
Notes
2006-12-05 14:55:48REFERENCE: GEN/RES PERMIT #06070748

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-28 Cont ID  
Sent By mperson Date 2006-08-28 Time 11:52 Rev Time 0.33
Received By mperson Date 2006-08-28 Time 11:52 Sent To PC
Notes
2006-08-28 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW:
  
 1. NOTE: THERE IS STILL AN ELECTRICAL
 ISSUE WITH THE GENERATOR (GEN/RES)
 PERMIT APPLICATION PRETAINING TO THE
 LOCATION OF THE GENERATOR. PLEASE SEE
 ATTACHED ELECTRICAL PLAN REVIEW AND
 COMMENTS FROM 8/27/06 FAILING GENERATOR
 (GEN/RES) PERMIT APPLICATION. NOTE: IT
 IS SUGGESTED THAT YOUR RESUBMITTAL BE
 SUBMITTED AFTER ELECTICAL GEN/RES PERMIT
 IS ISSUED. PLEASE CORRELATE WITH THE
 ELECTRICIAN THE NEW LOCATION OF THE
 GENERATOR AND ADJUST THE GAS ISOMETRIC
 ACCORDINGLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By mperson Date 2006-08-11 Time 11:42 Rev Time 0.33
Received By mperson Date 2006-08-11 Time 11:42 Sent To PC
Notes
2006-08-11 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. NOTE: THERE ARE ELECTRICAL ISSUES
 WITH THE GEN/RES PERMIT APPLICATION
 PRETAINING TO THE LOCATION OF THE
 GENERATOR DUE TO THE MINIMUM REQUIRED
 CLEARENCE, AND ZONING SETBACK, THE
 GENERATOR LOCATION MAY BE REVISED WHICH
 MEANS THE LENGTH OF THE GAS PIPE MAY
 CHANGE. PEASES SEE ATTACHED ELECTRICAL
 PERMIT PLAN REVIEW FOR REFERENCE.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (NOTE: THE SUBMITTED
 DRAWING IS NOT AN ISOMRTEIC, PLEASE
 REFERENCE THE EXAMPLE OF AN ISOMETRIC IN
 RED INK FOR RESUBMITTAL.)
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: NOT ALL PIPE MATERIAL OR SIZES
 INDICATED, PLEASE REFERENCE THE EXAMPLE
 ISOMETRIC FOR RESUBMITTAL.)
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 5. NOTE: PER THE SUBMITTED GENERATOR
 MANUFACTURER CUT SHEETS SUBMITTED THE
 BTU LOAD INDICATED ON THE SUBMITTED
 DRAWING IS INCORRECT, PLEASE REFERENCE
 THE SUBMITTED MANUFACTURER SHEETS AND
 THE CORRECTED DRAWING IN RED INK FOR
 RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:55 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:55 Sent To G
Notes
2006-11-29 18:55:33REV GAS/TO MPERSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 18:14 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 18:14 Sent To G
Notes
2006-08-17 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-11 Cont ID  
Sent By mperson Date 2006-08-11 Time 13:09 Rev Time 0.00
Received By mperson Date 2006-08-02 Time 11:43 Sent To  
Notes
2006-08-02 00:00:00TO "G" BOX