Plan Review Details - Permit 06080029
Plan Review Stops For Permit 06080029
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-17 Cont ID  
Sent By mjacobs Date 2006-08-17 Time 13:34 Rev Time 0.00
Received By mjacobs Date 2006-08-17 Time 11:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-08-11 Cont ID  
Sent By btrobaug Date 2006-08-11 Time 09:24 Rev Time 0.33
Received By btrobaug Date 2006-08-11 Time 08:57 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-15 Cont ID  
Sent By mperson Date 2006-08-15 Time 11:23 Rev Time 0.00
Received By mperson Date 2006-08-15 Time 11:23 Sent To B
Notes
2006-08-15 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 08:51 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 08:51 Sent To P
Notes
2006-09-12 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-28 Cont ID  
Sent By adarroug Date 2006-08-28 Time 08:49 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 08:49 Sent To P
Notes
2006-08-28 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 15:59 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 15:59 Sent To E
Notes
2006-08-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-17 Time   Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 10:34 Sent To  
Notes
2006-08-02 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-09-14 Cont ID  
Sent By mperson Date 2006-09-14 Time 16:39 Rev Time 0.33
Received By mperson Date 2006-09-14 Time 16:39 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-01 Cont ID  
Sent By mperson Date 2006-09-01 Time 13:27 Rev Time 0.33
Received By mperson Date 2006-09-01 Time 13:27 Sent To PC
Notes
2006-09-01 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004, SEC. 424.2 OR
 FBRC-2004, SEC. 4101 SWIMMING POOLS:
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
  
 1. THE RESUBMITTED PRINTS WITH THE
 REVISED PIPING SCHEMATIC SHOWING THE GAS
 POOL HEATER NEED TO BE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD, ANGELA A
 PRYMAS, P.E.#56087. NOTE: POOL IS AN
 ENGINEERED SYSTEM ANY NEW REVISED SHEETS
 SHALL BE SIGNED AND SEALED BY SAID
 ENGINEER, ANGELA A PRYMAS, P.E.#56087.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-15 Cont ID  
Sent By mperson Date 2006-08-15 Time 11:03 Rev Time 0.33
Received By mperson Date 2006-08-15 Time 11:03 Sent To G
Notes
2006-08-15 00:00:00******DENIED******
 REFERENCE: FBC-2004, SEC. 424.2 OR
 FBRC-2004, SEC.4101 SWIMMING POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. PLEASE CORRELATE THE 400,000 GAS
 HEATER INDICATED ON SHEET 1 SPECIFICA-
 TIONS WITH THE PIPING SCHEMATIC ON SHEET
 2. THE PIPING SCHEMATIC ON SHEET 2 DOES
 NOT INDICATE THE GAS HEATER, PLEASE
 INDICATE THE GAS HEATER ON THE
 RESUMITTAL.
 2. PLEASE SUBMIT MANUFACTURER CUT SHEETS
 OF THE 400,000 BTU GAS HEATER THAT
 CONFORMS WITH THE FOLLOWING.
 (A) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 (B) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-09 Cont ID  
Sent By mmclean Date 2006-08-09 Time 14:47 Rev Time 0.00
Received By mmclean Date 2006-08-09 Time 14:47 Sent To I
Notes
***NONE***