Plan Review Details - Permit 06071919
Plan Review Stops For Permit 06071919
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-10-11 Cont ID  
Sent By rmcdouga Date 2007-10-11 Time 09:14 Rev Time 0.00
Received By rmcdouga Date 2007-10-11 Time 09:14 Sent To  
Notes
2007-10-11 09:33:50REVISIONS TO SHEETS A1 AND A4 HAVE BEEN REVIEWED FOR
 CODE COMPLIANCE. ALSO STRUCTURAL DRAWINGS SK3, SK4 AND
 SK5 REVIEWED FOR COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-20 Cont ID  
Sent By rmcdouga Date 2007-09-20 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2007-09-20 Time 12:36 Sent To  
Notes
2007-09-20 13:49:37REVISONS TO WOMENS RESTROOM ON SHEET A1
  
 DENIED BY BUILDING
  
 1) SPECIFY THE SIZE OF THE DOORS TO THE RESTROOM AND
 ELECTRICAL ROOM ON THE PLANS. FBC 11-4.13.5 CLEAR WIDTH
  
  
 2) A WINDOW IS SHOWN IN THE WOMENS RESTROOM, WHICH WAS
 NOT INDICATED ON THE APPROVED SHEET A1. PLEASE CLARIFY.
 IF NEW WINDOW IS TO BE INSTALLED, SUBMIT PRODUCT
 APPROVALS AND STRUCTURAL DETAILS FOR THE OPENING.
  
 3) SUBMIT REVISED SHEET A4 THAT REFLECTS THE CHANGES
 MADE TO THE WOMENS RESTROOM.
  
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE AT FIXTURES AND
 THE REQUIRED TURNING SPACE. FBC 11-4.24.5 AND 11-4.2.3
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-14 Cont ID  
Sent By rmcdouga Date 2007-03-14 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2007-03-14 Time 18:13 Sent To  
Notes
2007-03-14 18:22:01DENIED BY BUILDING
  
 1) THE SHOP DRAWINGS AND PRODUCT APPROVALS ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 FOR THE PROJECT (HAROLD J. SMITH OF SMITH AND MOORE
 ARCHITECTS).
  
 2) SHEET A1 OF THE PLANS WHICH SPECIFIES THE LOCATIONS
 OF THE PIN PILES IS REQUIRED TO BE REVISED TO SHOW THE
 NEW LOCATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-08 Cont ID  
Sent By rmcdouga Date 2006-12-08 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2006-12-08 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By rmcdouga Date 2006-08-17 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2006-08-17 Time 07:59 Sent To  
Notes
2006-08-17 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE TYPE OF CONSTRUCTION,
 SPRINKLERED OR NOT, OCCUPANCY AND
 OCCUPANT LOAD.
  
 3) SCOPE OF WORK FALLS UNDER THE 2004
 FLORIDA EXISTING BUILDING CODE. SPECIFY
 THE LEVEL OF ALTERATION. SEE EXISTING
 BUILDING CODE CHAPTER 3.
  
 4) SPECIFY THE WIND DESIGN DATA. SEE FBC
 1603.1.4.
  
 5) SUBMIT SPECS AND INSTALLATION
 INSTRUCTIONS FOR BENTONITE WATER
 PROOFING.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
 SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING MATERIAL, SIMPSON CONNECTORS AND
 LINTELS.
  
 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/4" EXPANSION ANCHORS.
  
 8) PROVIDE DETAILS FOR THE EXISTING
 FLOOR/CEILING AND ROOF ATTACHMENTS TO
 THE NEW ELEVATOR SHAFT WALLS.
  
 9) PROVIDE LINTEL SAFE LOADING, LENGTH
 AND REQUIRED END BEARING.
  
 10) SPECIFY THE FIRE-RESISTANCE RATING
 OF THE ELEVATOR SHAFT ENCLOSURE. FBC
 707.4
  
 11) SPECIFY THE SLAB THICKNESS AT THE
 EXTERIOR ENTRANCE TO THE ELEVATOR.
  
 12) SPECIFY THE ROOF SHEATHING FASTENER
 TYPE AND SPACING. SEE TABLE 2304.9.1.
  
 13) PROVIDE DETAILS FOR THE CEILING
 ABOVE THE ENTRY TO ELEVATOR, THE ROOF
 FRAMING, ROOF COVERING MATERIAL,
 SCUPPERS, EXTERIOR CLADDING, ETC. SEE
 NOTES SHEET A3 OF PLAN FOR MISSING
 INFORMATION.
  
 14) SHEET A4 UNDER TOILET ROOM
 ACCESSORIES THERE ARE TWO GB-2 LISTED.
 ONE OF THEM SHOULD BE GB-1.
  
 15) SHOW THE REQUIRED CLEAR FLOOR SPACES
 AT BATHROOM FIXTURES. SEE FBC 11-4.
  
 16) THE ELEVATOR CAR IS REQUIRED TO
 COMPLY WITH FBC 11-4.10.9.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-31 Cont ID  
Sent By dpalmer Date 2008-03-31 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2008-03-31 Time 16:38 Sent To PC
Notes
2008-03-31 16:55:00REV TO ADD LIGHT OUTSIDE ELEVATOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By dpalmer Date 2007-09-21 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2007-09-21 Time 13:07 Sent To B
Notes
2007-09-21 13:08:56REV ROUTED PER LUIS MARTINEZ.
 PLANS ROUTED BACK TO LM'S OFFICE, NEEDS FIRE REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-15 Cont ID  
Sent By dpalmer Date 2006-11-15 Time 08:16 Rev Time 0.00
Received By dpalmer Date 2006-11-15 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 07:07 Sent To  
Notes
2006-08-14 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE NO INFORMATION FOR
 ELEVATOR PUMP/MOTOR SIZE(S) WERE SHOWN
 ON MDP. PLEASE SEE NO FEEDERS ARE
 INDICATED. PLEASE ALSO COMPLETE
 INFORMATION FOR THE DICONNECT AND SIZE
 IN ELEVATOR EQUIPMENT ROOM.
 PLEASE CLARIFY IF THE ELEVATOR CONTROLS
 ARE GOING TO BE FED TO ANY FA SYSTEMS,
 WITH SHUNT CONTROLS.620.51B
  
 2) NOTE: PLEASE SEE PLANS MENTIONS
 EXISTING PANELS AND THESE ARE LABLED.
 PLEASE LABEL PANELS IN NEW MDP AS NEEDED
 FOR PANELS KNOWN. PLEASE SEE NOTE ABOVE
 AS THE ELEVATOR IS NOT INDICATED.
 PLEASE SEE CIRCUITING ON THE MDP, AS THE
 MDP SEEMS TO REPEAT #8,AND #9 ON THE
 NUMERICAL IDENTIFICATION.
 PANELS WHICH ARE NOT KNOWN , WILL BE
 REQUIRED TO BE REVISED AT A LATER DATE
 408.4
  
 3) NOTE: PLEASE SEE THAT SOME SORT OF EM
 BATTERY BACK UP FIXTURE WILL BE REQUIRED
 IN THE NEW BATHRMS, ELEVATOR EQUIPMENT
 RM AND THE MAIN ELECTRICAL ROOM.
 IF EXISTING, PLEASE SHOW.
 NFPA-101 2003 7.8, 7.9, NFPA-70 700.16,
 700.12E.
  
 4) NOTE: PLEASE CLARIFY PLANS WHICH SEEM
 TO ALSO LABEL THE "MAIN ELECTRICAL ROOM"
 AS THE "ELEVATOR EQUIPMENT ROOM'? PLEASE
 KNOW PER STATE ELEVATOR CODE, ONLY
 ELECTRICAL EQUIPMENT PERTINENT TO THE
 ELEVATOR EQUIPMENT IS PERMITTED IN THIS
 RM.
 PLEASE ALSO CLARIFY THE DOOR OR ACCESS
 TO THE MAIN ELECTRICAL EQUIPMENT ROOM,
 AS ELECTRICAL PLANS DO NOT APPEAR TO
 SHOW ANY OPENING?
 110.26, 230.70
  
 5) NOTE: PLEASE VERIFY THE NEW OR
 EXISTING SEC'S FOR THE NEW 800A MCB MDP.
 IT IS UNCLEAR OF THE SIZE OF THE
 EXISTING.
 240.4, 310.16.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 16:43 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 16:42 Sent To  
Notes
2007-09-25 16:43:34*****APPROVED*****
  
  
 REVISED PLAN SHEET E-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-19 Cont ID  
Sent By mawillia Date 2006-12-19 Time 17:38 Rev Time 0.00
Received By mawillia Date 2006-12-19 Time 17:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 14:38 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 14:38 Sent To  
Notes
2006-09-13 00:00:00***DENIED***
  
  
 1) WORK REF: TO ELEVATOR SHALL COMPLY
 WITH NFPA 101, 2003 EDITION SECTION 9.4
 AND ASME A17.1.
  
 2) IS THIS PROJECT PROTECTED BY
 AUTOMATIC FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS? PLEASE ADVISE AND INDICATE HOW
 THIS WORK WILL BE IMPACTED BY REFERENCED
 SYSTEMS.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 10:32 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 10:32 Sent To B
Notes
2007-03-14 10:32:42TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 16:19 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 16:19 Sent To E
Notes
2008-03-25 16:21:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 12:06 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 12:06 Sent To M
Notes
2008-03-07 12:07:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 10:50 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 10:50 Sent To  
Notes
2007-10-05 10:50:35WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 15:36 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 15:36 Sent To  
Notes
2007-08-27 15:36:33WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 16:43 Sent To P
Notes
2007-04-11 16:44:14TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 11:44 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 11:44 Sent To  
Notes
2006-11-08 13:24:35TO "COMM" BD#12
2006-11-08 11:44:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2006-08-01 Time 15:10 Sent To  
Notes
2006-08-11 00:00:00TO "COMM" BD#21
2006-08-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-03-10 Cont ID  
Sent By tgordon Date 2008-03-10 Time 10:45 Rev Time 0.35
Received By tgordon Date 2008-03-10 Time 10:45 Sent To  
Notes
2008-03-10 10:46:42REVISION TO PART OF MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By tgordon Date 2007-09-20 Time 16:12 Rev Time 0.20
Received By tgordon Date 2007-09-20 Time 16:12 Sent To E
Notes
2007-09-20 16:13:21REVISION TO MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-08 Cont ID  
Sent By tgordon Date 2006-11-08 Time 16:19 Rev Time 0.30
Received By tgordon Date 2006-11-08 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By tgordon Date 2006-09-13 Time 11:17 Rev Time 0.30
Received By tgordon Date 2006-09-13 Time 11:17 Sent To  
Notes
2006-09-13 00:00:00*** DENIED ***
 1) NEED TO SHOW THE CFM'S FOR EF-2 IN
 MEN'S RESTROOM.
  
 2) RETURN AIR TRANSFER DUCT TO ELEVATOR
 EQUIPMENT ROOM DOES NOT RETURN TO AN
 AREA THAT RETURNS AIR TO THE AIR
 HANDLER, PLEASE CORRECT.
  
 3) RETURN AIR TRANSFER DUCT TO THE
 ELEVATOR RQUIPMENT ROOM IS UNDER SIZED,
 SEE NOTE #4 (A).
  
 4) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-20 Cont ID  
Sent By kstevens Date 2007-09-20 Time 11:37 Rev Time 0.00
Received By kstevens Date 2007-09-20 Time 11:36 Sent To B
Notes
2007-09-20 11:37:34REVISION OK--SHTS P-1 & P-2

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-08 Cont ID  
Sent By kstevens Date 2007-06-08 Time 16:46 Rev Time 0.00
Received By kstevens Date 2007-06-08 Time 16:46 Sent To  
Notes
2007-06-08 16:47:16REVISION OK - STS P-1 & P-2

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-08 Cont ID  
Sent By kstevens Date 2007-01-08 Time 09:57 Rev Time 0.00
Received By kstevens Date 2007-01-08 Time 09:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By kstevens Date 2006-08-24 Time 16:45 Rev Time 0.00
Received By kstevens Date 2006-08-23 Time 11:29 Sent To  
Notes
2006-08-24 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 WOMENS AND MENS RESTROOMS
 INDICATE ADA COMPLIANT STALLS. THESE ARE
 NOT COMPLIANT WITH FBC-2004 CHAPTER 11
 SECTION 11-4.17.3 EXCEPTION (1). SEE
 FIGURE 30E FOR CORRECT LAYOUT OF
 REQUIRED STALL.
  
 2. SHT A-4 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE RESTROOMS:
 FOR THE W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR THE UNINAL
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 FOR THE LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 3. SHT A-4 PER SECTION 1210.2
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
 PLEASE INDICATE HOW MR GYPSUM WALL BOARD
 COMPLIES WITH THESE REQUIREMENTS.
  
 4. SHT P-2 WATER ISOMETRIC. A WATER
 HAMMER ARESTOR IS REQUIRED AT THE DISH
 WASHER. 604.9.
  
 5. SHT P-2 SANT. ISOMETRIC. SHOW ALL
 PIPE SIZES TO THE W/C'S. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]