Plan Review Details - Permit 06071885
Plan Review Stops For Permit 06071885
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-09 Cont ID  
Sent By mawillia Date 2006-08-09 Time 15:52 Rev Time 0.00
Received By mawillia Date 2006-08-09 Time 15:52 Sent To  
Notes
2006-08-09 00:00:00**APPROVED**
  
  
  
 1.) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL ALARM.
  
 2.) FIRE ALARM SYSTEM IN CONJUNCTION
 WITH FIRE SPRINKLER SYSTEM TO BE
 MONITORED.
  
 3.) WATERFLOW TO ACTIVATE GENERAL FIRE
 ALARM WITHIN 45 TO 60 SECONDS.
  
 4.) TAMPER/SUPERVISORY SWITCH SHALL BE
 OPERATIONAL.
  
 5.) UL CERTIFICATE FOR CENTRAL STATION
 SERVICE TO BE AT THE FACP AND A COPY
 SUBMITTED TO WPBFR BY FINAL FIRE ALARM
 INSPECTION.
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-09 Cont ID  
Sent By mawillia Date 2006-08-09 Time 15:52 Rev Time 0.00
Received By mawillia Date 2006-08-01 Time 16:06 Sent To  
Notes
2006-08-01 00:00:00TO "F" BOX