Plan Review Details - Permit 06071830
Plan Review Stops For Permit 06071830
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 09:48 Rev Time 0.50
Received By alange Date 2006-08-18 Time 09:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-12 Cont ID  
Sent By btrobaug Date 2006-10-12 Time 11:20 Rev Time 0.50
Received By btrobaug Date 2006-10-12 Time 11:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-28 Cont ID  
Sent By btrobaug Date 2006-09-28 Time 17:49 Rev Time 0.33
Received By btrobaug Date 2006-09-28 Time 17:45 Sent To M
Notes
2006-09-28 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 SAME COMMENTS AS LAST REVIEW
  
 1} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING. SHOULD BE
 LOCATED WHERE THE JUNCTION BOX IS SHOWN.
 THIS DISCONNECT IS NOT REQUIRED TO HAVE
 OVERCURRENT PROTECTION.
  
 2} SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH 230.72
 (GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 3} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE
 GENERATOR HAS A RATED OUTPUT OF 52.5
 AMPS PER SPEC'S. THE CALCULATION
 REQUIRED IS FOR THE CIRCUITS IN THE 16
 CIRCUIT GENERATOR PANEL. 702.5 CAPACITY
 AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 4} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST PRINT AND SIGN THEIR NAME TO
 SAME.106.3.4.2 FBC, AS AMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By btrobaug Date 2006-08-10 Time 17:04 Rev Time 1.00
Received By btrobaug Date 2006-08-10 Time 15:10 Sent To P
Notes
2006-08-09 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING. SHOULD BE
 LOCATED WHERE THE JUNCTION BOX IS SHOWN.
 THIS DISCONNECT IS NOT REQUIRED TO HAVE
 OVERCURRENT PROTECTION.
  
 2} SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH 230.72
 (GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 3} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. THE
 GENERATOR HAS A RATED OUTPUT OF 52.5
 AMPS PER SPEC'S. THE CALCULATION
 REQUIRED IS FOR THE CIRCUITS IN THE 16
 CIRCUIT GENERATOR PANEL. 702.5 CAPACITY
 AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-14 Cont ID  
Sent By mperson Date 2006-08-14 Time 14:47 Rev Time 0.15
Received By mperson Date 2006-08-14 Time 14:47 Sent To B
Notes
2006-08-14 00:00:00 
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 14:08 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 14:08 Sent To E
Notes
2006-10-06 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 14:25 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 14:25 Sent To E
Notes
2006-09-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 09:40 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 09:40 Sent To Z
Notes
2006-09-19 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:39 Sent To E
Notes
2006-08-08 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 09:49 Rev Time 0.00
Received By alange Date 2006-07-31 Time 17:26 Sent To  
Notes
2006-07-31 00:00:00TO Z BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By tgordon Date 2006-09-29 Time 09:28 Rev Time 0.20
Received By tgordon Date 2006-09-29 Time 09:28 Sent To  
Notes
2006-09-29 00:00:00CLEARANCES SHOWN ON PLANS COMPLY WITH
 REQUIREMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 16:17 Rev Time 0.15
Received By tgordon Date 2006-08-11 Time 16:17 Sent To P
Notes
2006-08-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By mmclean Date 2006-09-23 Time 08:46 Rev Time 0.00
Received By mmclean Date 2006-09-23 Time 08:46 Sent To I
Notes
2006-09-23 00:00:00NOTE: AS INDICATED ON THE TWO COPY OF
 SURVEYS, THE PROPOSED GENERATOR WILL BE
 20FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By mmclean Date 2006-08-07 Time 17:40 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 17:40 Sent To I
Notes
2006-08-07 00:00:00DENIED,
 1. PLEASE PROVIDE A FULL SURVEY THAT'S
 INTACT SHOWING THE LOCATION OF THE
 PROPOSED GENERATOR (2 COPIES), ADDRESS
 ETC.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720