Plan Review Details - Permit 06071812
Plan Review Stops For Permit 06071812
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-31 Cont ID  
Sent By rmcdouga Date 2006-08-31 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2006-08-31 Time 09:38 Sent To  
Notes
2006-08-31 00:00:00REVISION DENIED BY BUILDING
  
 1) THE STATE COVER SHEET SUBMITTED DOES
 NOT CORRESPOND TO THE NOA FOR THE
 POLYGLASS MODIFIED BITUMEN ROOFING
 SYSTEM. THE CORRECT COVER SHEET IS
 FL985-R1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-09 Cont ID  
Sent By rmcdouga Date 2006-08-09 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2006-08-09 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By rmcdouga Date 2006-08-01 Time 13:59 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 13:59 Sent To  
Notes
2006-08-01 00:00:00DENIED
  
 1) THE ENGINEERING THAT WAS SUBMITTED IS
 BASED ON PAGE 11 OF NOA 03-0501.05WITH
 -45 PSF DESIGN PRESSURE. THE NOA
 SUBMITTED SPECIFIES A -52.5 PSF DESIGN
 PRESSURE LOCATED ON PAGE 18 OF THE SAME
 NOA. THE ENGINEERING MUST CORRESPOND TO
 THE SPECIFIED SYSTEM IN THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714