Plan Review Details - Permit 06071722
Plan Review Stops For Permit 06071722
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-03-17 Cont ID  
Sent By jwitmer Date 2008-03-17 Time 14:33 Rev Time 2.22
Received By jwitmer Date 2008-03-17 Time 14:33 Sent To PC
Notes
2008-03-17 14:37:07BUILDING PLAN REVIEW
 PERMIT: 06071722
 ADD: 2823 N AUSTRALIAN AVE
 CONT: HEDRICK BROTHERS
 TEL: (561) 718-9166
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW REVISIONREVISION 1 & 3
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THIS IS NEW WORK TO THE SCOPE OF THIS PERMIT OR
 REVISION PLEASE UPDATE VALUES IN THE JOB, ADDITIONAL
 PERMIT FEES MAY OCCUR.
 CITY OF WPB CODE OF ORDINANCES 3333-00.
 REVISION# 1 NEW COVERED PATIO
 REVISION# 3 NEW ROOF HATCH, LATTER AND GUARD RAIL
  
 3) REVISION # 1 COMPLIED.
  
 4)REVISION# 1,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 1) BUTLER ROOF SYSTEM RULE 9B-72.010 (31)(D)
 1609.7.1 ROOF DECK.
 THE ROOF DECK SHALL BE DESIGNED TO WITHSTAND THE WIND
 PRESSURES DETERMINED UNDER EITHER THE PROVISIONS OF
 SECTION 1609.6 FOR BUILDINGS WITH A MEAN ROOF HEIGHT
 NOT EXCEEDING 60 FEET (18 288 MM) OR SECTION 1609.1.1
 FOR BUILDINGS OF ANY HEIGHT.
  
 5)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 NOTE: THIS ADDITION WILL STILL BY DEFINITION BE
 CONSIDERED A "ENCLOSED WALKWAY" LESS THAN 30 FEET WIDE
 CONNECTING TWO BUILDINGS.
  
 REVISON# 3:
 7) THE NEW ROOF HATCH, LATTER AND GAURDRAIL SYSTEM. THE
 GUARDRAIL SYSTEM IS DESIGNED TO ASCE 7-98 WHICH WAS THE
 2001 FBC NOT THE CURRENT 2004 FBC. PLEASE CORRECT TO
 THE CURRENT STANDARD ASCE 7-02.
  
 8) PLEASE HAVE THE ENGINEER OF RECORD JOEL MIDDLEBROOKS
 REVIEW THE GUARDRAIL CALCULATIONS FOR CODE COMPLIANCE,
 BEFORE RESUBMITTAL.
  
 9) REVISION# 3,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 1) ROOF HATCH RULE 9B-72 .010(31)(A)
  
 10)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 11)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-02-26 Cont ID  
Sent By jwitmer Date 2008-02-26 Time 08:50 Rev Time 1.22
Received By jwitmer Date 2008-02-26 Time 08:50 Sent To  
Notes
2008-02-26 08:51:13REV DATED 2-19-08 SIDEWALKS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 07:17 Rev Time 2.22
Received By jwitmer Date 2008-01-31 Time 07:17 Sent To Z
Notes
2008-01-31 08:05:00BUILDING PLAN REVIEW
 PERMIT: 06071722
 ADD: 2823 N AUSTRALIAN AVE
 CONT: HEDRICK BROTHERS
 TEL: (561) 718-9166
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THIS IS NEW WORK TO THE SCOPE OF THIS PERMIT OR
 REVISION PLEASE UPDATE VALUES IN THE JOB, ADDITIONAL
 PERMIT FEES MAY OCCUR.
 CITY OF WPB CODE OF ORDINANCES 3333-00.
  
 3) THE REVISION OR ADDITION TO THIS PERMIT DOES NOT
 INDICATE TO WHATWIND DESIGN THIS ADDITION WAS
 DESIGNED TO.1609.6.2 WIND DESIGN PROCEDURES
 1)THE BASIC WIND SPEED, V, SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3. THE WIND
 SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE
 DETERMINED IN ACCORDANCE WTIH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT,
 * SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5) DETERMINE IF ADDITION IS TO BE DESIGNED AS
 PARTIALLY OPEN OR ENCLOSED. 1609.1.4.1./ 1609.2
 DEFINITIONS.
  
 4)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 1) BUTLER ROOF SYSTEM
 1609.7.1 ROOF DECK.
 THE ROOF DECK SHALL BE DESIGNED TO WITHSTAND THE WIND
 PRESSURES DETERMINED UNDER EITHER THE PROVISIONS OF
 SECTION 1609.6 FOR BUILDINGS WITH A MEAN ROOF HEIGHT
 NOT EXCEEDING 60 FEET (18 288 MM) OR SECTION 1609.1.1
 FOR BUILDINGS OF ANY HEIGHT.
  
 5)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 NOTE: THIS ADDITION WILL STILL BY DEFINITION BE
 CONSIDERED A "ENCLOSED WALKWAY" LESS THAN 30 FEET WIDE
 CONNECTING TWO BUILDINGS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-01-09 Cont ID  
Sent By jwitmer Date 2008-01-09 Time 14:39 Rev Time 2.22
Received By jwitmer Date 2008-01-09 Time 14:36 Sent To  
Notes
2008-01-09 14:40:24REVISION# 3 SHEETS A0, 01,1.01, 2.01, 2.02, & 2.03

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-10-26 Cont ID  
Sent By jwitmer Date 2007-10-26 Time 15:42 Rev Time 0.77
Received By jwitmer Date 2007-10-26 Time 15:42 Sent To PC
Notes
2007-10-26 15:43:01REV # 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-22 Cont ID  
Sent By jwitmer Date 2007-08-22 Time 16:21 Rev Time 1.33
Received By jwitmer Date 2007-08-22 Time 16:21 Sent To PC
Notes
2007-08-23 07:37:39 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 06071722
 ADDRESS: 2823 N AUSTRALIAN AVE
 CONT: HEDRICK BROTHERS
 TELL # (561)718-9166
  
 THE ATTACHED COMMENTS ARE PART OF THE PERMIT AND PLAN
 REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF PLANS.106.1.1
 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISOS:
  
 1)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER.THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE
 DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE
 THE POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING IN A DECREASE
 IN EXCESS OF 800SQ FT OF PERMEABLE LAND AREA ON ANY
 PARCELL SHALL AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
 2) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 3) BEFORE A CERTIFICATE OF OCCUPANCY WILL BE ISSUED A
 PRODUCT APPROVAL FOR THE USE OF ROOF HATCHES SHALLBE
 REVIEWED AND STAMPED BY THE CITY BEFORE
 A COF O WILL BE ISSUED . IF THE MANUFACTURER OF ROOF
 HATCH HAS NOTRECEIVED EITHER STATE APPROVAL OR A
 MIAMI-DADE NOA THE CONTRACTOR SHALL SECURE A LOCAL
 PRODUCT APPROVAL WITHIN THIS JURISDICTION. RULE 9B-72.
  
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-16 Cont ID  
Sent By jwitmer Date 2007-08-16 Time 13:08 Rev Time 2.22
Received By jwitmer Date 2007-08-16 Time 13:08 Sent To P
Notes
2007-08-16 13:11:43BUILDING PLAN REVIEW
 PERMIT: 06071722
 ADD: 2823 N. AUSTRALIAN AV
 CONT: HEDRICK BROTHERS
 TEL: (561)718-9166
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 NOTE-- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1ST REQUEST) PER ARTICLE 13 OF THE UNIFIED LAND
 DEVELOPMENT
 CODE, IMPACT FEES ARE PAYABLE ON THE CHANGE OF USE
 (OCCUPANCY).
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ONCE PLANS ARE STAMPED WWITH THE COUNTY IMPACT FEE
 STAMP INDICATING A COUNTY IMPACT FEE REVIEW BUILDING
 WILL BE ABLE TO "PASS" THE PLANS IN THE COMPUTER.
 NOTE , THERE WAS NO ROOFING PRODUCT APPROVAL SUBMITTED
 WILL REQUIRE A SEPERATE PERMIT ASSOCIATED FEES AND
 REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 17:35 Rev Time 2.20
Received By jwitmer Date 2007-06-18 Time 17:35 Sent To  
Notes
2007-06-18 17:37:26BUILDING PLAN REVIEW
 PERMIT: 06071722
 ADD: 2823 N. AUSTRALIAN AV
 CONT: HEDRICK BROTHERS
 TEL: (561)718-9166
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 NOTE-- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1ST REQUEST) PER ARTICLE 13 OF THE UNIFIED LAND
 DEVELOPMENT
 CODE, IMPACT FEES ARE PAYABLE ON THE CHANGE OF USE
 (OCCUPANCY).
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2-6 ) COMPLIED.
  
 7) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 B) WINDOWS- HORIZONTAL SLIDERS SEE COMMENT ON NOAC)
 WINDOWS- CASEMENT SEE COMMEENT ON NOA
 D) EXTERIOR HOLLOW METAL DOORS WITH VIEW PANELSLARGE
 MISSLE IMPACT TESTING , SEE NOA
 E) GLAZED DOORS ALUMINIUM/ GLAZED PANELS/ W SIDE LITES
 SEE NOA
 G)ROOF ACCESS HATCH- PROVISO: REPORT TO BE ISSUED
 BEFORE C.O SUBMIT REPORT.
 H) ROOF ASSEMBLIES.- NOT SUBMITTED
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) 2ND REQUEST,
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9-21 COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-28 Cont ID  
Sent By jwitmer Date 2007-02-28 Time 14:15 Rev Time 7.77
Received By jwitmer Date 2007-02-28 Time 14:15 Sent To  
Notes
2007-02-28 14:40:07 
 BUILDING PLAN REVIEW
 PERMIT: 06071
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 NOTE-- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1ST REQUEST) PER ARTICLE 13 OF THE UNIFIED LAND
 DEVELOPMENT
 CODE, IMPACT FEES ARE PAYABLE ON THE CHANGE OF USE
 (OCCUPANCY).
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2-5 ) COMPLIED.
  
 6) 2ND REQUEST, PROVIDE DETAILS FOR ALL STRUCTURAL
 MODIFICATIONS TO THE
 EXTERIOR WALLS, (INFILL OF ELEVATOR EXTERIOR DOORS, AND
 MODIFICATIONS TO
 ACCEPT NEW DOORS & WINDOWS, ETC).
  
 6A)STRUCTURAL SHEETS S-0.1-S.2ARE NOT SIGNED NOR
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6B) STRUCTURAL SHEET S0.1 DESIGN LOADS INDICATE ASCE
 7-98 CORRECT TO THE
 ASCE 7-02.
  
 6C) S.01 HAS A NOTE INDICATING THIS TO BE A THRESHOLD
 BUILDING. PLEASE TAKE NOTE OF 553.71(7) "THRESHOLD
 BUILDING" MEANS ANY BUILDING WHICH IS GREATER THAN 3
 STORIES OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY CLASSIFICATION AS DEFINED IN THE FLORIDA
 BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN
 OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
 THIS BUILDING DOES NOT QUALIFY AS A THRESHOLD
 BUILDING.
  
 6D) STRUCTURAL PLANS ALSO INDICATE A SHELL PERMIT DATED
 12-19-06 SEE ATTACHMENT NO SUCH PERMIT APPLICATION.
  
 7) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS STOREFRONT
 B) WINDOWS- HORIZONTAL SLIDERS
 C) WINDOWS- CASEMENT
 D) EXTERIOR HOLLOW METAL DOORS WITH VIEW PANELSLARGE
 MISSLE IMPACT TESTING
 E) GLAZED DOORS ALUMINIUM/ GLAZED PANELS/ W SIDE
 LITES
 F)OVERHEAD DOOR
 G)ROOF ACCESS HATCH
 H) ROOF ASSEMBLIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) 2ND REQUEST,
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9-12) COMPLIED.
  
 13) GENERATOR TO BE UNDER A SEPERATE PERMIT.
  
 14& 15 ) COMPLIED.
  
 16) DOORS STILL NOT IN COMPLIANCE WITH :11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
 DOORS: 206A, 208A & 217C.
  
 17) COMPLIED.
  
 18) 2ND REQUEST,FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN
 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING
 OF THE NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE
 BEFORE THE FIRST INSPECTION.
  
 NEW COMMENTS:
 19)SHEET A2.01 & A2.02 BOTH INDICATE THE REQUIREMENT
 FOR SMOKE RATED CORRIDORS SINCE THIS IS A FIRE
 SPRINKLERD
 BUILDING. THESE SHEETS INDICATE A "P1" WALL WHERE AS
 THE SMOKE RESISTANT WALLS ARE TO BE A "P2".TABLE
 1016.
  
 20) SHEET A2.01 ROOM 110 IS LABELED A "CHILL ZONE"
 AREAS WHERE NORMALLY SUBJECT
 TO STUDENT OCCUPANCY SHALL ALSO REQUIRE EMERGENCY
 ESCAPE AND RESCUE WINDOWS, SEE 1025.4.1.
  
 21) FLAT ROOF THE REPORT SUBMITTED, THIS ROOF IS
 MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 __X_ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By amorse Date 2006-09-01 Time 09:34 Rev Time 0.00
Received By amorse Date 2006-08-25 Time 14:54 Sent To  
Notes
2006-08-25 00:00:00 
  
 DENIED
  
 1) PER ARTICLE 13 OF THE UNIFIED LAND
 DEVELOPMENT CODE, IMPACT FEES ARE
 PAYABLE ON CHANGE OF USE. BEFORE A
 PERMIT TO CONSTRUCT, IS ISSUED IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SETS OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.PLEASE CALL (561) 233-5025
 FOR MORE INFORMATION
  
 2) PROVIDE DETAILS ON THE OCCUPANCY OF
 BUILDING #1 AS IT EXITS INTO THE SAME
 ENCLOSED CORRIDOR BETWEEN THE TWO
 BUILDINGS. VERIFY THAT THE EXITS WILL
 MEET THE REQUIRED EXIT DISCHARGE
 CAPACITY FOR BOTH BUILDINGS
  
 3) PROVIDE EXISTING FLOOR PLAN AND DEMO
 PLAN WITH THE CONSTRUCTION SET TO BETTER
 UNDERSTAND THE MODIFICATIONS, ALSO
 PROVIDE THE PREVIOUS OCCUPANCY TYPE
  
 4) THE EXIT PASSAGEWAY BETWEEN BUILDINGS
 1 AND 2 HAS 2 EXITS DOES THE WEST EXIT
 ENTER INTO AN EGRESS COURT THAT PROVIDE
 ACCESS TO THE PUBLIC WAY AS DEFINED IN
 CHAPTER 10, OR IS IT A FENCED AREA,
 PLEASE CLARIFY
  
 5) PROVIDE DETAILS OF WALKWAY TO
 EXISTING BUILDING 3 IS IT ALSO ENCLOSED
 OR OPEN
  
 6) PROVIDE DETAILS FOR ALL STRUCTURAL
 MODIFICATIONS TO THE EXTERIOR WALLS
 (INFILL OF ELEVATORS EXTERIOR DOOR,
 MODIFICATIONS TO ACCEPT NEW DOORS OR
 WINDOWS, ETC.)
  
 7) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
 (WILL BE REQUIRED FOR ROOFING, A/C OR
 OTHER EQUIPMENT STANDS AND ALL EXTERIOR
 DOORS, WINDOWS, STOREFRONTS, ROLL UP
 DOORS, ETC.)
  
 8) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9) PANIC HARDWARE SHALL COMPLY WITH
 THE REQUREMENTS OF 1027.2.1 FBC
  
 10) DOOR 106C SHALL MEET THE
 REQUIREMENTS OF 1027.3 AND 1005.2 FBC
  
 11) FLOORS AND WALLS OF TOILET ROOMS
 SHALL COMPLY WITH 1210 FBC
  
 12) TOILET ROOMS, FIXTURES AND
 ACCESSORIES SHALL COMPLY WITH CHAPTER 11
 OF THE 2004 FBC (A6.01 LISTS 1997 ED.)
  
 13) PROPOSED GENERATOR WILL REQUIRE A
 SOIL REPORT,ENGINEERED EQUIPMENT BASE,
 SURVEY THAT PROPOSED BASE IS 6" ABOVE
 THE BASE FLOOD ELEVATION FOR LOCATION.
 ALSO BE AWARE THAT ALL SUBS ARE
 SIGNED ON TO GENERATOR PERMIT AT TIME OF
 APPLICATION (GAS, ELECT, PLUMBING, ETC)
  
 14) GENERAL FINISH NOTES ON A2.01 SHOWS
 GROUP AS A3, AND THE EXIT ACCESS AS
 CLASS 'C' THIS DOES NOT CORRESPOND WITH
 THE TABLE 803.5 FBC PLEASE CLARIFY
  
 15) SEE PLUMBING NOTES ON ACCESSABLE
 SINKS IN THE BREAK ROOM AND STAFF LOUNGE
  
 16) PROVIDE MIN MANUVERING DISTANCE OF
 18" AT DOORS 121A, 218A AND 225A PER
 11-4.13.6 AND FIG.25(A). ALSO IF THE MIN
 DISTANCE PROVIDED AT DOOR 202A IS 12" ON
 THE PUSH SIDE THIS DOOR SHALL BE
 PROVIDED WITH A CLOSER AND LATCH PER
 NOTE: FIG. 25(A)
  
 17) GENERAL DOOR NOTES ON A2.01 SHALL
 PROVIDE HARDWARE THAT MEETS THE
 REQUIREMENTS OF 11-4.13.8 FBC FOR
 ACCESSABLE HARDWARE
  
 18) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-12-12 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-12-12 Time 11:32 Sent To  
Notes
2007-12-12 11:32:36*** DENIEDREVISION **
  
 1) NOTE: PLEASE SEE ONLY ONE COPY OF ELECTRICAL
 REVISIONS WERE SUBMITTED IN THE TWO SETS OF PLANS
 SUBMITTED.
 PLEASE KNOW THAT IN EITHER CASE THE ELECTRICAL
 REVISIONS AS SUBMITTED WITH REVISION DATE OF 11/27/07
 HAS ALREADY BEEN SUBMITTED, REVIEWED AND STAMPED BY
 THIS ELECTRICAL REVIEWER. THESE SAME SHEETS ARE ALREADY
 ON FILE.
 IF NO NEW SHEETS ARE BEING PRESENTED WITH REVISED ITEMS
 THERE IS NO NEED TO SUBMIT THESE SHEETS BACK FOR
 REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 09:54 Sent To PC
Notes
2007-12-03 09:54:34REV 4 AND 5 FOR
 3.01,4.01, &5.01

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-07-17 Cont ID  
Sent By dpalmer Date 2007-07-17 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2007-07-17 Time 14:40 Sent To  
Notes
2007-07-17 14:42:31*** NOTE **
  
  
 1) 2ND SET OF SUBMITTALS BROUGHT IN BY CATHERINE FROM
 HEDRICK BROTHERS. OK, STAMPED.
 2) STAMPED ELECTRICAL PLANS OK. REDLINED OCP FOR
 ELEVATOR TO BE VIF PER 240.21,240.4.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-16 Cont ID  
Sent By dpalmer Date 2007-07-16 Time 20:35 Rev Time 0.00
Received By dpalmer Date 2007-07-16 Time 19:18 Sent To I
Notes
2007-07-16 20:35:242007-07-16 20:35:24
 ** TEMPORARY FAILED STATUS**
  
  
 1) NOTE: ONLY ONE SET OF EACH THE GENERATOR AND ATS
 SUBMITTALS WERE SUBMITTED WITH PLANS.NEED ONE SET FOR
 100KW, 150KW AND SPECS FOR THE 300 SERIES TRANSFER
 SWITCHES.
 PLACED A CALL TO CATHERINE FROM HEDRICK BROTHERS AT
 APPROX 8:15PM FOR SECOND SET OF THE ABOVE TO BE BROUGHT
 IN.
 OK TO COME IN W/ NO FEES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-16 19:18:572007-07-16 19:18:57
 PLANS REMOVED FROM INCOMING AND IN ELEC FOR REVIEW.
 PLANS WILL RETURN TO INCOMING WAITING FOR COMM BOARD
 ONCE ELECTRICLA REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-04 Cont ID  
Sent By dpalmer Date 2007-06-04 Time 21:09 Rev Time 0.00
Received By dpalmer Date 2007-06-04 Time 18:54 Sent To  
Notes
2007-06-04 21:09:29** UNSAT 3RD REVIEW **
  
 *** PLEASE SEE THERE ARE SOME EXISTING COMMENTS WHICH
 ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED PLANS SUBMITTED AND SOME
 ITEMS BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW.
  
 1) NOTE:PLEASE CLARIFY WHY THE CODES ON E1.01 WERE
 UPDATE TO THE 2005 NEC AND 2004 FBC W/ 2006 REVISIONS?
 THE TITLE BLOCK MENTIONS THIS WAS DONE PER BLDG
 DEPARTMENT COMMENTS; HOWEVER THERE WERE COMMENTS FROM
 THIS REVIEWER ON EITHER OF THE TWO PREVIOUS REVIEWS
 WHICH REQUESTED THE CODES TO BE CHANGED. PLEASE SEE ANY
 NOTES FROM PREVIOUS REVIEW WHICH REFERENCE CODE YEARS,
 REFERENCED THE 2002 NEC.
 PLEASE KNOW THAT ALL PERMITS APPLIED FOR BEFORE
 DECEMBER 8TH, 2006 PLACES PROJECTS UNDER THE 2004 FBC
 W/2005 REVISIONS AND THE 2002 NFPA-70 (NEC).
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 ENERGY CALCULATIONS WHICH REQUESTED THE SIGNATURE OF
 THE OWNER AGENT( CONTRACTOR) AS STATED ON ENERGY
 CALCULATIONS. THESE WERE SUBMITTED WITHOUT SIGNATURES.
  
 ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT
 FROM THE CORRECT VERSION ADOPTED BY THE FBC FOR THIS
 PERMIT. THE ENERGY CALCULATIONS EVEN STATE THEY ARE
 ONLY EFFECTIVE AFTER DECEMBER 8TH, 2006.
 PLEASE SEE THAT ALL PERMITS ONCE AGAIN APPLIED BEFORE
 THIS DATE PLACES VERSIONS UNDER THE 2004 FBC W/2005
 REVISIONS. ( VERSION FOR ENERGY CALCULATIONS 2.1?)
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED NEED TO
 CORRELATE WITH THE ELECTRICAL LIGHTING ON PLANS. PLEASE
 SEE THE PLANS DO INDICATE EXTERIOR LIGHTING, HOWEVER
 THE ENERGY CALCULATIONSDO NOT INCLUDE ANY EXTERIOR
 LIGHTING ENTERED IN THE SUMMARY/LIGHTINGPERFORMANCE
 OR INPUT DATA REPORT.
 PLEASE REVISE AND ADJUST ALL ENERGY CALCULATIONSPER
 13-103.1.1.1, 13-415.1.AB.1.1, 13-415.2
  
 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 PHOTO-METRICS TO VERIFY CODE COMPLIANCE FOR EXIT PATHS
 AND STAIRS. PLEASE SEE THE PLANS WERE REVISED TO
 INCREASE LIGHTING FIXTURES, HOWEVER THE RESPONSE LETTER
 MENTIONS TO SEE THE PHOTO-METRICS ATTACHED, YET NONE
 COULD BE LOCATED AS PART OF THE DESIGNERS SUBMITTED
 PLANS OR ATTACHED SHEETS.
 PLEASE SEE LS 101 2003, 7.8.1.3, 7.9.2.2.
 AS NONE WERE SUBMITTED, REVIEW CAN NOT BE
 ACCOMPLISHED.
  
 4) NOTE: PLEASE SEE THIS IS THE FIRST REVIEW WHERE
 SPECS/CUT SHEETS FOR ATS/ GENERATOR WAS SUBMITTED FOR
 REVIEW. PLEASE CLARIFY THEATS DEVICES IF THEY ARE
 3-POLE OR 4-POLE. AS THE SHEETS ONLY INDICATE ORDERING
 METHOD FOR TYPE AND THE PLANS ONLY INDICATE 3-PHASE AND
 4-WIRE.
 IF SD SYSTEMS, RISER WOULD NEED TO COMPLY WITH 250.20,
 250.50 ETC.
  
 5) NOTE: PLEASE SEE PLANS SEEM TO MENTIONS THE
 GENERATOR BUILDING AS INDEED A SEPARATE *BUILDING*?
 PLEASE SEE 225.31, AND 250.32 FOR THIS IS A SEPARATE
 BUILDING/STRUCTURE, THEN GROUNDING AT THIS BUILDING
 WOULD BE SHOWN AND A DISCONNECTING MEANS IN PANEL GR.
 PLEASE SEE THE FOLLOWING NOTE FOR MORE CLARIFY FOR THE
 GR PANEL.
  
 6) NOTE: PLEASE SEE PREVIOUS COMMENTS SPOKE OF CIRCUITS
 FOR COMMON AREAS.(MAIN ELECTRICAL ROOM, GENERATOR ROOM,
 OUTSIDE LIGHTING, ROOFTOP RECEPTS)ETC. BRANCH CIRCUITS
 WHICHARE SHOWN COMING FROM TENANT SERVICES WHICH IS
 NOT PERMITTED.
 (EXAMPLE, ROOFTOP BRANCH CIRCUIT FOR WP RECEPTACLES
 TRIPS, HOWEVER THE ONLY ACCESS TO THE OCP/BREAKER IS TO
 THE SECOND FLOOR TENANT WHICH IS NOT ACCESSIBLE TO
 ANYONE)
 PLEASE SEE THE RISER SHOWS CIRCUITS IN THE MAIN
 ELECTRICAL ROOM TO THE PANEL P1 WHICH IN THE PANEL
 SCHEDULE THESE SAME CIRCUITS ARE BLANK?
 PLEASE SEE THERE IS NO PANEL SCHEDULE FOR PANEL GR AND
 YET THE CIRCUITS WHICH ARE SHOWN ON PANEL P1 ACTUALLY
 ARE LABELED TO FEED THE CIRCUITS IN THE GENERATOR ROOM
 WHICH INDICATE CIRCUITS TO A GR PANEL? THIS IS
 CONFUSING AND NOT CLEAR WHAT IS BEING PROPOSED.
 PLEASE ALSO SEE THE LIGHTING ON THE EXTERIOR OF
 BUILDING AND STAIRS INDICATES CIRCUITS TO A PANEL GP
 WHICH IS NOT ON RISER AND NO PANEL WAS SCHEDULE
 SUBMITTED ETC?? PLEASE CLARIFY WHERE THESE ARE BEING
 FED FROM?
 240.24, 210.25 FBC 106.1.2, 106.3.5.1.2, 215.5, FBC
 106.1.2, 106.3.5.1.2, 106.4
  
 7) NOTE: PLEASE SEE THE RISER SHOWS THE NEW PANEL GR
 BEING *TAPPED* FROM A DISCONNECT YET THE EQUIPMENT
 COORDINATION SCHEDULE SHOWS THIS BEING *TAPPED* FROM
 THE ATS-1?
 PLEASE ALSO SEE 240.21 FOR THE TAPPED CONDUCTOR
 LIMITS.
 PLEASE SEE THAT BESIDE THE LENGTH NOT PERMITTED ANY
 TAPPED CONDUCTORS MUST TERMINATE IN OVER CURRENT
 PROTECTION AND AS NO PANEL GR SCHEDULE WAS SUBMITTED NO
 VERIFICATION FOR MCB AND OCP CAN BE VERIFIED.
 PLEASE KNOW THERE ARE SEVERAL QUESTIONS ON NOTES 5, 6
 AND 7.
  
 8) NOTE: PLEASE SEE THE RISER SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS* FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS NOT PERMITTED. 250.6, 250.24
 (THIS WOULD HAVE BEEN REDLINED IF PLANS WERE NOT COMING
 BACK FOR OTHER COMMENTS.
  
 9) NOTE: PLEASE SEE 620.22 AND CLARIFY THE SEPARATE
 BRANCH CIRCUITS FOR ELEVATOR CAB LIGHTS. IF TAPPED,
 PLEASE INDICATE THE CONDUCTORS AND OCP AT TERMINATION.
 (RISER AND EQUIPMENT SCHEDULE INDICATE 3-POLE FOR
 LIGHTING??
 240.4, 240.21, 310.16.
  
 10) NOTE: PLEASE CLARIFY THE 225AMP BREAKER IN PANEL M2
 IS FEEDING THE 200AMP RATED DISCONNECT FOR THE
 ELEVATOR. THE RESPONSE MENTIONS THIS IS TO AVOID *FALSE
 TRIPPING*? THIS IS NOT CLEAR WHEN THE DISCONNECT IS
 200AMPS AND THE TAPS FOR WHAT APPEARS TO BE THE
 ELEVATOR CAB LIGHTS IS IN QUESTION PER NOTE #9.
  
 11) NOTE: PLEASE SEE PREVIOUS REVIEW REQUESTED FOR ANY
 OLD/VOIDED SHEETS TO BE SUBMITTED BACK FOR REFERENCE
 YET NONE WERE SUBMITTED?
 PLEASE SEE THAT THE SAME NOTE WILL APPLY FOR THE
 FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-04 Cont ID  
Sent By dpalmer Date 2007-02-04 Time 17:54 Rev Time 0.00
Received By dpalmer Date 2007-02-04 Time 14:56 Sent To  
Notes
2007-02-04 17:54:34******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
 1) NOTE: NO, PLEASE SEE NO INFORMATION SPEC ETC WAS
 SUBMITTED FOR ANY EQUIPMENT.
 110.3, 90.7, FBC 106.1.2 ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS ON THE
 GEN, ATS AND DEPENDING ON PRIME MOVER WHETHER OR NOT A
 SUB BASE TANK IS BEING USED ETC.
 THIS INFORMATION REQUIRED FOR BOTH.
 FBC106.1.2 , NEC110.3,90.8 ETC
  
 2) NOTE: NO/OK PLEASE SEE SOMEINFORMATION WAS
 SUBMITTED FOR LOCATION HOWEVER AS SPECS ETC WAS NOT
 SUBMITTED, REVIEW FOR LOCATION CAN NOT BE CONFIRMED FOR
 CODE COMPLIANCE. PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT THIS.
 PLEASE PROVIDE FLOOD ELEVATION, AND PLEASE KNOW THAT
 BEFORE ANY FINAL, A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED ALSO.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 COULD NOT LOCATE A NEW SITE PLAN/SURVEY PLEASE INDICATE
 THE GEN LOCATION ON PLANS.IF IN A FLOOD ZONE PLEASE
 SEE BUILDING REVIEW COMMENTS AS ELEVATION IS REQUIRED A
 6" MIN ABOVE
 BFE.
 PLEASE ALSO KNOW A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL.
  
 3) NOTE: NO/OK, PLEASE PROVIDE CONDUIT AND CONDUCTORS
 FROM FPL TRANSFORMER TO GUTTER. PLEASE CORRELATE
 EQUIPMENT SCHEDULE WITH RISER. PLEASE SEE NEW COMMENTS
 FOR ACCESS AND GROUNDING ELECTRODE CONDUCTOR.
 ** SEEMS TO MATCH UP WITH FIGURE 230.9 IN 230.2 OF THE
 2002 NEC HANDBOOK.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 230.2 AS MORE THAN ONE SERVICE IS BEING
 SHOWN FOR THE ONE BUILDING, HOWEVER COULD NOT LOCATE ON
 PLANS HOW THE SECOND SERVICE BEING PROPOSED CAN BE
 GRANTED UNDER SPECIAL PERMISSION AT THIS TIME.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE KNOW THAT AT THIS TIME BASED ON NO
 INFORMATION SUBMITTED FOR THE GENERATOR AND THE SERVICE
 ENTRANCE CONDUCTORS FROM THE FPL TRANSFORMER TO THE
 GUTTER, THE GROUNDING ELECTRODE CONDUCTOR SIZE CAN NOT
 BE VERIFIED, PLEASE ALSO SEE 250.66.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASECOMPLETE GROUNDING ELECTRODE SYSTEM AS REQUIRED
 PER 250.50.
  
 6) NOTE: NO, PLEASE KNOW AT THIS TIME THE CIRCUITING
 FOR SOME AREAS (STAIRS) WHICH WILL BE UNDER COMMENT #7
 CAN NOT BE VERIFIED.
 PLEASE ALSO SEE NEW COMMENTS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SHOW ALL CIRCUITING PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES AND PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 7) NOTE: NO, PLEASE SEE THE STAIR AREAS ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE SOME ARE SHOWN WITH
 CONTROLS BY A PHOTO-CELL WHICH IS NOT PERMITTED. PLEASE
 SEE OTHER STAIRS WHICH ARE MISSING FROM PLANS ON NORTH
 SIDE OF BUILDING. PLEASE SEE THE CENTER STAIRS FROM
 SECOND FLOOR TO THE FIRST FLOOR SPECIFICALLY CONTAINS A
 NOTE WHICH MENTIONS THIS IS NOT AN EXIT.
 PLEASE KNOW THAT DURING AN EMERGENCY CONDITION OR THE
 PANIC THAT MAY OCCUR DURING A FIRE ETC, THE NORMAL
 BUILDING OCCUPANTS/EMPLOYEES OF THIS SECOND FLOOR WHO
 KNOW THIS IS A STAIR WHICH LEADS TO THE FIRST FLOOR
 WILL UTILIZE THIS AS AN EXIT. UNLESS THIS DOOR IS
 SEALED FROM THE OCCUPANTS SO THAT ACCESS IS NOT
 GRANTED, THEN IF ACCESS IS AVAILABLE THEN THIS STAIR
 WILL BE REQUIRED TO MEET 7.8.1.3 AND 7.9.2.
 PLEASE SEE THE BUILDING REVIEW NOTES WITH RESPECT TO
 THE STAIRS PLACING OCCUPANTS BACK INTO A BUILDING OR IN
 THIS CASE ANOTHER TENANT SPACE.
 PLEASE SEE NO PHOTO-METRICS WERE SUBMITTED FOR MINIMUM
 LEVELS FOR EGRESS PATHS ON FIRST FLOOR OR SECOND FLOOR.
 PLEASE SUBMIT AND BE AWARE OF ANY CHANGES FROM OTHER
 TRADES. CONSULTATION WILL BE FORTH COMING WITH THE FIRE
 MARSHAL FOR THE EXITS AND HOW THEY ARE LABELED.
 PLEASE ALSO KNOW THAT THE FAILURE OF ANY SINGLE OVER
 CURRENT PROTECTION DEVICE OR SWITCHING DEVICE CAN NOT
 LEAVE ANY EGRESS PATH IN TOTAL DARKNESS. PLEASE SEE AS
 STAIRS AS SHOWN WITH CONTROLS BY TIMERS/PHOTO-CELLS
 ETC, THESE DEVICES WOULD CREATE SUCH A LIFE SAFETY
 HAZARD. PLEASE SEE THE FAILURE OF THE DEVICE WOULD NOT
 TRIGGER THE EMERGENCY LIGHT TO COME ON AS THE CIRCUIT
 MAY STILL BE ENERGIZED.
 PLEASE SEE THE SELECTION OF THE TYPE OF OVER RIDE
 DEVICE SHOULD BE CHOSEN CAREFULLY AND WILL BE REQUIRED
 TO CONTAIN A SECOND MEANS OF BACK UP FOR CONTROL.
 PLEASE SEE EXIT FROM SOUTH STAIRS STILL DOES NOT
 PROVIDE DIRECTIONAL FOR EXIT WHEN EGRESS FROM STAIR
 DOOR.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE CLARIFY WHERE THE LIGHTING IS FOR ALL STAIRS.
 PLANS APPEAR TO SHOW SOME LIGHTING IN CENTER STAIRWAY,
 HOWEVER NOT FOR OTHERS. PLEASE ALSO SEE STAIRS ARE
 BEING SHOWN ON TIMED SCHEDULE HOWEVER CONTROLS FOR
 LIGHTING OUTSIDE TIME SCHEDULING SHALL BE PROVIDED BY A
 MIN OF TWO METHODS,(OCCUPANCY SENSORS ON LTS, OCCUPANCY
 SENSORS IN STAIRS , TIMED DOOR CONTACTS ETC.) PLEASE
 KNOW, ENTERING INTO THE EXIT STAIR WAY AND HAVING THE
 LIGHTING SHUT OFF AND LEAVE IN TOTAL DARKNESS IS A LIFE
 SAFETY ISSUE.
 PLEASE ALSO PROVIDE BATTERY BACK UP FIXTURES.
 PLEASE ALSO SEE A MINIMUM OF 10 FT CANDLES IS REQUIRED
 UNDER NORMAL AND CAN BE RATED DOWN TO 1FT UNDER EM
 CONDITIONS. PLEASE PROVIDE PHOTO-METRICS. (CAN BE
 TYPICAL)
 PLEASE SEE EXITING FROM STAIRS ON SOUTH SIDE OF
 BUILDING SHOWS EGRESS INTO A HALL WAY WITH NO EXIT
 DIRECTIONAL.
 PLEASE SEE NFPA-101
 7.8,7.8.1.3,7.9,7.9.2.2 ETC.
 PLEASE SEE FIREREVIEW COMMENTS.
 FBC CHAPTER 13
  
 8) NOTE: OK/NO, PLEASE SEE THE ELEVATOR MACHINE ROOM IS
 NOW SHOWN; HOWEVER PLEASE SEE 620.23 AND 24 FOR
 REQUIRED DEDICATED CIRCUITS. PLEASE SEE THESE ARE ON
 THE SAME CIRCUIT.
 PLEASE ALSO SEE NEW NOTES FOR ELEVATOR DISCONNECT.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 COULD NOT LOCATE THE ELEVATOR MACHINE RM.? PLEASE SEE
 620.23, 620.24,
 700.16. ETC
 COULD NOT LOCATE THE MIN CIRCUITING FOR LTS, RECEPTS ,
 CAB ETC.
 PLEASE ALSO KNOW, A BATTERY BACK UP FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE ELEVATOR EQUIPMENT RM.
 7.8,7.9, 700.16
  
 9) NOTE: OK.
  
 10) NOTE: NO, PLEASE SEE PLANS INDICATE GFI BEING
 PROVIDED WITH THE EQUIPMENT WHICH IS NOT COMMON. PLEASE
 PROVIDE EQUIPMENT INFORMATION SHOWING THE TAP
 CONDUCTORS, OVER CURRENT PROTECTION, MEANS OF
 DISCONNECT ETC.
 IF THIS IS NOT THE CASE, PLEASE SUBMIT AND SHOW THE
 CIRCUITING FOR ALL ROOF TOP EQUIPMENT. CAN NOT RELY ON
 THE EQUIPMENT LEGEND AND PANEL SCHEDULES.
 110.3, 90.7, 240.21, 240.4, 310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE MISSING CIRCUITING ON ROOFTOP PLANS FOR
 UNITS AND GFI RECEPTS FOR ROOFTOPQUIPMENT.
 230.63,210.8
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, PLEASE SEE THERE ARE ROOMS ON PLANS WHICH
 DO NOT INDICATE ANY DESIGNATIONS. PLEASE SEE NEW NOTES
 WITH RESPECT TO PANEL SCHEDULE(S) AND CIRCUITING ON
 PLANS.
 PLEASE SEE NEW NOTES FOR ROOMS WITH PANELS AND OTHER
 ELECTRICAL ROOMS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON PLANS.
 UNABLE TO VERIFY SOME OF THESE ROOMS AT THIS TIME.
  
 14) NOTE:NO? PLEASE SEE AS SOME OF THE ROOM
 DESIGNATIONS ARE MISSING IT IS NOT CLEAR IF THERE IS AN
 IT ROOM.IT DOES NOT APPEAR THERE WILL BE TRUE IT
 ROOM, HOWEVER PLEASE COMPLETE NOTE #13 ABOVE AND THIS
 SHOULD ALLEAVIATE THIS COMMENT.
 ** PREVIOUS REVIEW NOTE REVIEW #1
 PLEASE SEE PLANS MENTIONS "IT" ROOM ON SECOND FLR.
 PLEASE SEE NFPA-75 AND NFPA-70(NEC) 645 FOR
 REQUIREMENTS.
  
 15) NOTE: OK.
  
 16) NOTE: NO, PLEASE SEE THERE ARE A FEW NOTES
 PERTAINING TO THE ENERGY CALCULATIONS AND LIGHTING
 PERFORMANCE CALCULATIONS.
 A ) PLEASE SEE THE ENERGY CALCULATIONS ARE THE ONES
 PREVIOUSLY SUBMITTED WHICH WERE SIGNED BY THE PREVIOUS
 BUILDING CONTRACTOR WHICH IS NO LONGER APART OF THIS
 PROJECT. PLEASE OBTAIN NEW SIGNATURES.
 B) PLEASE SEE THAT NO LIGHTING PERFORMANCE TABLES,
 CHARTS, LEVELS ETC WERE SUBMITTED AND METHOD *A* DOES
 NOT PROVIDE THIS INFORMATION. PLEASE ALSO CLARIFY THE
 USE OF METHOD *A*, AS THE A-SHEETS INDICATE A LEVEL 3
 ALTERATION, HOWEVER PLEASE SEE NEW NOTES FOR THIS AS
 THIS IS A CHANGE IN OCCUPANCY AND DOES APPEAR TO FALL
 UNDER A LEVEL 3 ALTERATION. PLEASE SEE FBC CHAPTER
 13-101.3
 C) PLEASE SEE SOME AREAS IN THE INPUT DATA REPORT WHICH
 INDICATES MANUAL CONTROLS, HOW IS THIS POSSIBLE IF ALL
 LIGHTING CONTAINS AUTOMATED CONTROLS?
  
 **PLEASE SEE NEW NOTES PERTAINING TO LIGHTING
 CONTROLS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1, 415.2.B.1
  
 17) NOTE: NO, PLEASE SEE RISER SHOWS THE SECOND FLOOR
 ATS AS BEING LABELED WITH THE SAME DESIGNATION AS THE
 FIRST FLOOR ATS.
 PLEASE SEE THE ELEVATOR CIRCUITS WHICH IS SHOWN AS
 225AMPS IN PANEL M-2, YET THE EQUIPMENT LEGEND SHOWS
 200AMP DISCONNECT?
 PLEAS ADJUST AND COORDINATE.
 240.4, 310.16.
 106.1.2 ADMIN SECTION.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE "EQUIPMENT CO-ORDINATION SCHEDULE", PLEASE
 SEE MAINS DISCONNECTS WHICH ARE INDEED MAINS AND PLEASE
 ALSO SEE MAINS FOR EACH FLR ALSO BEING LABELED AS
 "MAINS" 1 AND 2.
 PLEASE ADJUSTED IDENTIFICATION ACCORDINGLY.
 230.2E
  
  
 ***** NEW NOTES *****
  
 18) NOTE: PLEASE SEE ACCESS FOR THE MAIN DISCONNECT AND
 GENERATOR DISCONNECT AND EQUIPMENT FOR THE POWER FOR
 THE SECOND FLOOR TENANT APPEARS TO ONLY BE ACCESSED
 THROUGH THE FIRST FLOOR TENANT SPACE. PLEASE SEE A
 REDESIGN WILL BE REQUIRED AS ACCESS TO THIS EQUIPMENT
 IS REQUIRED FOR THIS 2ND FLOOR TENANT AT ALL TIMES.
 (OUTSIDE DOOR) ETC 240.24B ETC
  
 19) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 ROOM DESIGNATIONS, PLEASE SEE ROOM/AREA WHERE PANEL
 *S3* IS LOCATED.
 110.26, 408.7, 240.24D
  
 20) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 A) PLEASE PROVIDE THE TIME OF DAY SCHEDULING FOR LC
 PANELS.
 B) PLEASE SEE WOMEN'S BATHROOM ON FIRST FLOOR WHICH
 CONTAINS A DEVICE*S UC*WHICH IS NOT ON ANY SYMBOL
 LEGEND. ?
 C) PLEASE SEE A SWITCH WITH A DESIGNATION OF *S M*
 WHICH IS NOT ON ANY SYMBOL LEGEND.?
 D) PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER
 RIDES/OCCUPANCY SENSORS/TIMER TYPE DEVICES.
 E) PLEASE SEE OC TYPE IS 30 MINUTES MAX AND TIMER TYPES
 ARE 4HRS MAX.
 F) PLEASE SEE HALL AREAS WHICH CONTAIN OVER RIDE
 DEVICES WHICH ARE SHOWN AS *S M*, DO THESE PROVIDE
 COMPLETE COVERAGE OF THE ENTIRE HALL WAY AREA BEING
 OVER RIDDEN WHEN TIMED SCHEDULING IS OFF. AS THIS
 DEVICE APPEARS TO BE A MOTION TYPE DEVICE, PLEASE
 VERIFY AS LOCATING *NIGHT LIGHTS* ON PLANS COULD NOT BE
 FOUNDIN THE EVENT OF THESE DEVICES NOT BEING ABLE TO
 DETECT THE OCCUPANT AND LEAVING THE OCCUPANT IN TOTAL
 DARKNESS.
 PLEASE SEE LS 101 7.8 AND 7.9 FOR THIS AS NOTED ABOVE
 IN THE PREVIOUS REVIEW NOTE #7.
  
 21) NOTE: PLEASE SEE PANEL SCHEDULE SHOULD BE MORE
 DETAILED FOR ROOMS AND AREAS WHICH THEY FEED. PLEASE
 SEE THE BELOW IS TAKEN FROM THE COMMENTARY FROM THE
 HANDBOOK IN 408.4. PLEASE SEE ALL THE CIRCUITS WHICH
 ONLY INDICATE *RECEPTACLES* AND NOT TO ANY ROOMS/OFFICE
 DESIGNATIONS.
 * REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
  
 22) NOTE: PLEASE SEE THAT ANY COMMON AREA BRANCH
 CIRCUITS SHALL BE REQUIRED TO BE FED FROM A HOUSE PANEL
 OF SOME TYPE, NOT FROM A TENANT PANEL.
 *GEN ROOM*, *MAIN ELECTRICAL ROOM*.
 104.6 FBC ADMIN SECTION.
  
 23) NOTE: PLEASE SEE ATTACHED NOTICE TO FS 553.80(2)(B)
 IS GIVEN AT THIS TIME WITH RESPECT TO CODE COMMENTS.
 PLEASE KNOW THAT THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED, COMMENTS MAY NOT BE COMPLETE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 10:32 Sent To  
Notes
2006-08-14 00:00:00******** UNSAT **********
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS ON THE GEN, ATS AND
 DEPENDING ON PRIME MOVER WHETHER OR NOT
 A SUB BSAE TANK IS BEING USED ETC.
 THIS INFORMATION REQUIRED FOR BOTH.
 FBC106.1.2 , NEC110.3,90.8 ETC
  
 2) NOTE; PLEASE INDICATE THE GEN
 LOCATION ON PLANS.IF IN A FLOOD ZONE
 PLEASE SEE BUIDLING REVIEW COMMENTS AS
 ELEVATION IS REQUIRED A 6" MIN ABOVE
 BFE.
 PLEASE ALSO KNOW A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE
 FINAL.
  
 3) NOTE: PLEASE SEE 230.2 AS MORE THAN
 ONE SERVICE IS BEING SHOWN FOR THE ONE
 BUILDING, HOWEVER COULD NOT LOCATE ON
 PLANSHOW THE SECOND SERVICE BEING
 PRPOSED CAN BE GRANTED UNDER SPECIAL
 PERMIISION AT THIS TIME.
  
 4) NOTE: PLEASE CLARIFY ON PLANS WHERE
 M1 AND M2 ARE? CAN NOT VERIFY
 240.24,110.26 ETC.
 106.1.2 FBC.
  
 5) NOTE: PLEASECOMPLETE GROUNDING
 ELECTRODE SYSTEM AS REQUIRED PER 250.50.
  
 6) NOTE: PLEASE SHOW ALL CIRCUITING
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES AND PANEL SCHEDULES TO
 BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 7) NOTE: PLEASE CLARIFY WHERE THE
 LIGHTING IS FOR ALL STAIRS . PLANS
 APPEAR TO SHOW SOME LIGHTING INCENTER
 STAIRWAY,HOWEVER NOT FOR OTHERS. PLEASE
 ALSO SEE STAIRS ARE BEING SHOWN ON TIMED
 SCHEDULE, HOWEVER CONTROLS FOR LIGHTING
 OUTSIDE TIME SCHEDULING SHALL BE
 PROVIDED BY A MIN OF TWO
 METHODS,(OCCUPANCY SENSORS ON LTS,
 OCCUPANCY SENSORS IN STAIRS , TIMED DOOR
 CONTACTS ETC.) PLEASE KNOW, ENTERING
 INTO THE EXIT STAIR WAY AND AHAVING THE
 LIGHTING SHUT OFF AND LEAVE IN TOTAL
 DARKNESS IS A LIFE SAFETY ISSUE.
 PLEASE ALSO PROVIDE BATTERY BACK UP
 FIXTURES.
 PLEASE ALSO SEE A MINIMUM OF 10 FT
 CANDLES IS REQUIRED UNDER NORMAL AND CAN
 BE RATED DOWN TO 1FT UNDER EM
 CONDITIONS. PLEASE PROVIDE
 PHOTO-METRICS. (CAN BE TYPICAL)
 PLEASE SEE EXSTING FROM STAIRS ON SOUTH
 SIDE OF BUILDING SHOWS EGRESS INTO A
 HALL WAY WITH NO EXIT DIRECTIONALS.
 PLEASE SEE NFPA-101
 7.8,7.8.1.3,7.9,7.9.2.2 ETC.
 PLEASE SEE FIREREVIEW COMMENTS.
 FBC CHAPTER 13
  
 8) NOTE: COULD NOT LCATE THE ELEVATOR
 MACHINE RM.? PLEASE SEE 620.23,620.24,
 700.16. ETC
 COULD NOT LOCATE THE MIN CIRCUTING FOR
 LTS, RECEPTS , CAB ETC.
 PLEASE ALSO KNOW, A BATTERY BACK UP
 FIXTURE OF SOME SORT WILL BE REQUIRED IN
 THE ELEVATOR EQUIPMENT RM.
 7.8,7.9, 700.16
  
 9) NOTE: PLEASE SEE EQUIPMENT LIST,
 MENTIONS PANELBOARD/CIRCUIT AS FPL,
 HOWEVER PLEASE KNOW EQUIPMENT AS SHOWN
 IS NOT BY FPL FOR MAINS, METER ETC.
 106.1.2 FBC
  
 10) NOTE: PLEASE SEE MISSING CIRCUITING
 ON ROOFTOP PLANS FOR UNITS AND GFI
 RECEPTS FOR ROOFTOP EQUIPMENT.
 230.63,210.8
  
 11) NOTE: PLEASE VERIFY WHERE LOAD
 CALCUALTIONS ARE SHOWN AND ALL
 CONTINUOUS LOADS/LARGEST MOTORS AT
 125%.220.3,220.10,220.11,220.13,215.3,
 230.42 ETC
  
 12) NOTE: PLEASE PLEASE PROVIDE PANEL
 SCHEDULES FOR LLC1, AND LLC2 AND
 CORRELATE WITH THE CIRCUITING PLANS.
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS.
 UNABLE TO VERIFY SOME OF THESE ROOMS AT
 THIS TIME.
  
 14) NOTE: PLEASE SEE PLANS MENTIONS "IT"
 ROOM ON SECOND FLR. PLEASE SEE NFPA-75
 AND NFPA-70(NEC) 645 FOR REQUIREMENTS.
  
 15) NOTE: PLEASE SEE 620.51 FOR
 DISCONNECTING OF ELEVATOR EQUIPMENT. AS
 ROOM IS NOT VERIFIED AT THIS TIME, NOT
 SURE WHERE THIS DISCONNECTING MEANS IS?
  
 16) NOTE: PELASE SEE 13-415.2.ABC.1,
 TABLES 415.2.C.1, 415.2.B.1
  
 17) NOTE: PLEASE SEE "EQUIPMENT
 CO-ORDINATION SCHEDULE", PLEASE SEE
 MAINS DISCONNECTS WHICH ARE INDEED MAINS
 AND PLEASE ALSO SEE MAINS FOR EACH FLR
 ALSO BEING LABELED AS "MAINS" 1 AND 2.
 PLEASE ADJUSTED IDENTIFICATION
 ACCORDINLGY.
 230.2E
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-02-07 Cont ID  
Sent By mawillia Date 2008-02-07 Time 12:45 Rev Time 0.00
Received By mawillia Date 2008-02-07 Time 12:21 Sent To  
Notes
2008-02-07 12:29:37*****REVISION 2, APPROVED*****
  
  
 REVISED PLAN SHEET FP-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-02-07 Cont ID  
Sent By mawillia Date 2007-12-31 Time 12:20 Rev Time 0.00
Received By mawillia Date 2007-12-31 Time 11:17 Sent To  
Notes
2007-12-31 11:19:08*****PROVISO*****
  
  
 THE APPROPIATE REVISED PLAN SHEETS TO BE FIRE-STAMPED
 WHEN THE OTHER REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-12-04 Time 13:09 Rev Time 0.00
Received By mawillia Date 2007-12-04 Time 12:56 Sent To  
Notes
2007-12-04 13:08:55*****NOT APPLICABLE*****
  
  
 THESE FIRE ALARM PLANS HAVE BEEN IMPROPERLY SUBMITTED
 UNDER THE MASTER PERMIT;PLEASE BE ADVISED THAT
 SEPARATE PLANS AND PERMIT ARE REQUIRED FOR THE
 INSTALLATION AND/OR REMODEL OF THE FIRE ALARM SYSTEM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-06-05 Cont ID  
Sent By mawillia Date 2007-06-05 Time 16:53 Rev Time 0.00
Received By mawillia Date 2007-06-05 Time 16:17 Sent To  
Notes
2007-06-05 16:52:44*****PROVISO*****
  
 ALL COMMENTS WITH THE EXCEPTION OF THE ONE BELOW HAVE
 BEEN ADEQUATELY ADDRESSED;THE APPROPIATE PLAN SHEETS
 WILL BE STAMPED WHEN ALL PLAN REVIEW COMMENTS
 (INCLUDING THOSE OF THE OTHER PLAN REVIEWERS) HAVE BEEN
 SATISFIED.
  
  
 07.NEW DAMPER INSTALLATIONS SHALL BE DROP TESTED
 PRIOR TO THE FINAL INSPECTION.PLEASE INDICATE ON THE
 PLANS
  
  
 PLEASE ACKNOWLEDGE (ON THE PLANS) THAT THE ABOVE
 COMMENT HAS BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-01 Cont ID  
Sent By mawillia Date 2007-03-01 Time 17:30 Rev Time 0.00
Received By mawillia Date 2007-03-01 Time 17:30 Sent To  
Notes
2007-03-01 18:41:51*****DENIED*****
  
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 02.PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL
 COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS.NO
 EMERGENCY LIGHTING NOTICED IN THE STAIRWAYS ON SHEET
 A1.01
  
 05.CLASSROOMS AND SIMILAR SPACES SHALL MEET THE
 REQUIREMENTS FOR RESCUE WINDOWS.PLEASE INDICATE ON
 THE PLAN SHEET A5.01
  
 07.NEW DAMPER INSTALLATIONS SHALL BE DROP TESTED
 PRIOR TO THE FINAL INSPECTION.PLEASE INDICATE ON THE
 PLANS
  
 10.THE FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR
 EMERGENCY PERSONNEL.SIGNAGE TO BE DISPLAYED ON
 ELECTRICAL ROOM DOOR INDICATING FIRE ALARM CONTROL
 PANEL (FACP) INSIDE.PLEASE INDICATE ON THE PLANS
  
 NEW COMMENTS:
  
 AA.IT IS INDICATED THAT THE BUILDING IS 100%FIRE
 SPRINKLERED.PROVIDE A LAYOUT OF THIS FIRE SPRINKLER
 SYSTEM.SEPARATE SHOP DRAWINGS AND PERMITS WILL BE
 REQUIRED FOR ANY FIRE SPRINKLER INSTALLATION OR
 REMODEL.
  
 BB.ON SHEET A2.01, IT APPEARS THAT THE EXIT ACCESS
 CORRIDOR WILL BE COMPROMISED WHEN THE DOOR(S) TO THE
 STORAGE ROOM [109] AND THE MECHANICAL ROOM [102] ARE
 OPENED AT THE SAME TIME.AS PER NFPA 101- 7.2.1.4.4* :
 DURING ITS SWING , ANY DOOR IN A MEANS OF EGRESS SHALL
 NOT LEAVE LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR, OR A PASSAGEWAY WHEN FULLY OPEN.
  
 CC.ON SHEET A1.01, VERIFY AND /OR INSTALL A
 DIRECTIONAL EXIT SIGN LIGHT INDICATING THE EXIT ONCE
 PERSON(S) ARE IN THE CORRIDOR BETWEEN BUIDING #2 AND
 BUILDING #1.
  
 DD. THERE SEEMS TO BE A DISCREPANCY AS REFERNCE TO A AN
 EXIT DOOR LOCATED AT THE MIDDLE STAIRWAY ON THE SECOND
 FLOOR.IT IS INDICATED AS AN EXIT ON SHEET A1.01, BUT
 IS INDICATED ON SHEET E3.02 THAT IT IS NOT AN EXIT.
 PLEASE CLARIFY.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By mwennerg Date 2006-10-10 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2006-10-10 Time 15:07 Sent To  
Notes
2006-10-10 15:15:58***DENIED***
  
 1) EXIT SIGNS SHALL BE MOUNTED AT DISTANCES NOT TO
 EXCEED 100'. SHT A1.01.
  
 2) PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL
 COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE MOUNTED
 NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL.
  
 5) CLASSROOMS AND SIMILAR SPACES SHALL MEET
 REQUIREMENTS FOR RESCUE WINDOWS.
  
 6) PLEASE SHOW ADDRESS ON BUILDING THAT SHALL BE A
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING TO
 THE BACKGROUND.
  
 7) NEW FIRE DAMPER INSTALLATIONS SHALL BE DROP TESTED
 PRIOR TO FINAL INSPECTION.
  
 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 9) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 10) FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR EMERGENCY
 PERSONNEL. SIGNAGE TO BE DISPLAYED ON ELECTRICAL ROOM
 DOOR INDICATING FACP INSIDE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-16 Cont ID  
Sent By kstevens Date 2007-08-16 Time 15:01 Rev Time 0.00
Received By kstevens Date 2007-08-16 Time 15:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By kstevens Date 2007-06-11 Time 11:43 Rev Time 0.00
Received By kstevens Date 2007-06-11 Time 11:43 Sent To  
Notes
2007-06-11 11:54:47DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-5.1 INDICATES THE GAS METERS INSIDE THE
 STRUCTURE. THIS IS HIGH PRESSURE AND PER SECTION 402.6
 THE MAXIMUM DESIGN OPERATING PRESSUREFOR PIPING
 SYSTEMS LOCATED INSIDE BUILDINGS IS 5 PSI.PLEASE
 INDICATE THE SUPPLY PRESSURE TO THE METERS AND/OR MOVE
 THE METERS OUTSIDE THE BUILDING AND RECHECK THE TOTAL
 DEVELOPED LENGTH OF THE GAS PIPING TO THE FURTHEST
 GENERATOR.
  
 NOTE: THERE WAS NO INDICATION THAT A NEW PLUMBING SHEET
 AS ADDED AFTER THE FIRST REVIEW IN THE COMMENT
 RESPONSES SO SHT P-5.1 WAS OVERLOOKED IN THE SECOND
 REVIEW.THAT IS WHY THE GAS REVIEW COMMENTS WERE NOT
 INDICATED ON THE SECOND REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 17:00 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 17:00 Sent To  
Notes
2008-03-10 16:31:40TO "COMM" BD#7
2008-03-07 17:00:38WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 12:14 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 12:14 Sent To  
Notes
2008-02-22 12:17:21TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 16:10 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 16:10 Sent To B
Notes
2008-01-30 16:10:32TO "JWITME" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 11:43 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 11:43 Sent To  
Notes
2008-01-22 11:47:10TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 11:54 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 11:54 Sent To  
Notes
2007-12-06 11:54:25TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 16:41 Sent To E
Notes
2007-11-29 16:42:11TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 16:39 Sent To FIRE
Notes
2007-11-29 16:39:56TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 16:37 Sent To FIRE
Notes
2007-11-29 16:38:22TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 13:46 Sent To  
Notes
2007-10-04 10:11:04TO "COMM" BD#20
2007-09-13 13:47:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 15:41 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 15:41 Sent To B
Notes
2007-08-22 15:42:16TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 16:55 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 16:55 Sent To  
Notes
2007-07-24 09:57:27TO "COMM" BD#48
2007-07-10 16:55:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 15:58 Sent To  
Notes
2007-05-18 13:40:27TO "COMM" BD#42/PLANS ON RACK/2 ROLLS
2007-05-07 15:58:42WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-01-19 Time 13:16 Sent To  
Notes
2007-01-30 10:45:47TO "COMM" BD#56
2007-01-19 13:16:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By mwennerg Date 2006-10-10 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2006-08-01 Time 13:10 Sent To  
Notes
2006-10-11 14:44:35ROUTED FROM "COMM" BD TO "Z"--ZONING LAST REVIEWER
2006-08-11 00:00:00TO "COMM" BD#36
2006-08-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-01-24 Cont ID  
Sent By tgordon Date 2008-01-24 Time 16:02 Rev Time 0.45
Received By tgordon Date 2008-01-24 Time 16:02 Sent To  
Notes
2008-01-24 16:02:47MECHANICAL REVISION TO PLANS PAGE M-3.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 16:33 Rev Time 0.10
Received By tgordon Date 2007-12-07 Time 16:33 Sent To  
Notes
2007-12-07 16:33:52** MECHANICAL REVISION TO PAGE M-3 **
 *** DENIED ***
 1) PAGE M-3 PACKAGED ROOF TOP SCHEDULE SHOWS THE A/C
 SYSTEMS AS 12 SEER, PER 2004 FBC 13-407.1.ABC.3.2.1 THE
 MINIMUM SEER IS 13. WAS EER INTENDED. PLEASE CORRECT.
  
 2) PAGE M-3 SPLIT SYSTEM SCHEDULE SHOWS SYSTEM #4 AS
 12.75 SEER, PER 2004 FBC 13-407.1.ABC.3.2.1 THE MINIMUM
 SEER IS 13. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 16:03 Rev Time 1.20
Received By tgordon Date 2007-12-07 Time 16:03 Sent To  
Notes
2007-12-07 16:30:32MECHANICAL REVISION TO PAGES M-1, M-2.1, M-2.2, M-2.3,
 M-4, M-5, AND M-6.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-21 Cont ID  
Sent By tgordon Date 2007-05-21 Time 12:02 Rev Time 1.00
Received By tgordon Date 2007-05-21 Time 12:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-16 Cont ID  
Sent By tgordon Date 2007-02-16 Time 10:59 Rev Time 0.45
Received By tgordon Date 2007-02-16 Time 10:59 Sent To  
Notes
2007-02-16 11:03:29*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES REGARDING THE GENERATOR
 AND THE ENERGY CALCULATIONS, PLEASE ADDRESS AND
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By tgordon Date 2006-09-13 Time 14:38 Rev Time 1.30
Received By tgordon Date 2006-09-14 Time 10:34 Sent To  
Notes
2006-09-13 00:00:00*** DENIED ***
 1) MECHANICAL PLANS NEED THE ENGINEERING
 COMPANY'S CITIFICATE OF AUTHORIZATION
 NUMBER ON THEM, PER FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By kstevens Date 2008-02-07 Time 11:33 Rev Time 0.00
Received By kstevens Date 2008-02-07 Time 11:33 Sent To  
Notes
2008-02-07 11:36:43SEPARATE MED-GAS PERMIT REQUIRED. CERTIFICATIONS
 REQUIRED FOR THE QUALIFER, INSTALLER, AND BRAZER AT
 TIME OF APPLICATION WITH PICTURE I.D'S

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 10:55 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 10:55 Sent To  
Notes
2007-12-20 15:46:00REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 NFPA 99C-99
  
 1. SUBMITISOMETRIC RISER DIAGRAMS FOR THE VACUUM
 PIPING AND THE COMPRESSED AIR PIPING. SECTION
 106.3.5.1.3.
  
 2. SHT P-3.3 THE VACUUM SYSTEM SHALL COMPLY WITH
 SECTION 4-5.2 AND ALL SUBSECTIONS. SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 4-5.2.1.1 SERVICE INLETS SHALL BE EITHER A SHUT
 OFF VALVE WITH A THREADED FEMALE PIPE CONNECTOR, OR A
 QUICK-CONNECT FITTING WITH A SINGLE CHECK VALVE.
 B. 4-5.2.1.2 LIQUID/AIR SEPARATOR (EQUIPMENT SHALL BE
 OBTAINED FROM AND BE INSTALLED UNDER THE SUPERVISION OF
 A MANUF. OR SUPPLIER FAMILIAR WITH PROPER PRACTICES FOR
 ITS CONSTRUCTION AND USE). (SEE FIGS. 4-5.2.1.2 A THRU
 D.
 C. 4-5.2.1.3 LIQUIDS FROM A LEVEL VACUUM SYSTEM, PER
 4-5.2.2, SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM. (SEE FIGURES 4-5.2.1.3(A) THRU(B).
 (SEE ATTACHED SHEETS). (SHOWN AS INDIRECT CONNECTION ON
 FIGURE 2 SHT P-3.3).
 D. 4-5.2.1.5 EXHAUST SHALL BE LOCATED REMOTE FROM ANY
 DOOR, WINDOW, AIR INTAKE, OR OTHER OPENING IN THE
 BUILDING ETC.
 E. 4-5.2.1.6 EXHAUST PROTECT AGAINST ENTRY OF INSECTS
 ETC.
 F. 4-5.2.2.1 CLEANOUTS REQUIRED.
 G. 4-5.2.2.3 CLEANOUTS REQUIRED.
 H. 4-5.2.2.5 PIPING TO BE SLOPED .
  
 3. SHT P-3.3 THE GAS-POWERED DEVICES LEVEL 3 SHALL
 COMPLY WITH SECTION 4-5.1.1 AND ALL SUBSECTIONS. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 4-5.1.1.3(A)(D)(E)(G)(H) INTAKE SHALL BE FROM THE
 OUTSIDE WHEN PRACTICAL.
 B. 4-5.1.3.3(A) THRU (I)
  
 4. SEE ATTACHED SHEETS FOR TYPICAL LEVEL 3 VACUUM AND
 AND GAS POWERED DEVICES SUPPLY SYSTEMS.
  
 5. A SEPARATE MED-GAS PERMIT IS REQUIRED.
 CERTIFICATIONS FOR THE QUALIFER, THE BRAZER, &
 INSTALLER ARE REQUIRED WHEN APPYING FOR THE PERMIT.
 PICTURE IDENTIFICATION IS REQUIRED ON THE
 CERTIFICATIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 15:48 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 15:48 Sent To  
Notes
2007-12-20 15:51:16REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P-1, P-4, P-5.1, P-5.2 NO REVISION INDICATED OR
 NOTED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-11 Cont ID  
Sent By kstevens Date 2007-06-11 Time 12:01 Rev Time 0.00
Received By kstevens Date 2007-06-11 Time 12:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-16 Cont ID  
Sent By kstevens Date 2007-02-16 Time 06:26 Rev Time 0.00
Received By kstevens Date 2007-02-15 Time 18:53 Sent To  
Notes
2007-02-16 07:02:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 NFPA 99C
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHTS A2.01 & A2.02 THE FIRST FLOOR
 FINISH SCHEDULE FOR ROOMS 103, 104, 118,
 (WOMEN, UNISEX HDCP, & MEN TOILET ROOMS)
 AS WELL AS ROOMS 202, 205, 208, & 210
 TOILET ROOMS INDICATE PAINTED MR GWB FOR
 THE WALLS. PLEASE SHOW HOW THIS COMPLIES
 WITH SECTION 1210.2 REQUIREMENTS FOR
 WALLS TO BE HARD & NON-ABSORBENT.
 ****RESPONSE NOTED, BUT THE FINISH SCHEDULE SHALL
 REFLECT THE WALL MATERIAL TO BE INSTALLED.
  
 4. SHT A2.01 THE BREAK ROOM SINK AND SHT
 A2.02 THE STAFF LOUNGE SINK SHALL BE
 ACCESSIBLE. SUBMIT DETAILS SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 (FORWARD APPROACH REQUIRED,
 AND NO CABINET DOORS ALLOWED IN CLEAR
 FLOOR SPACE).
 ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 5. OK
 6. OK
  
 7. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAINS.
 ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
  
 8. SHTS P3.1 & P3.2 AND RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE AS CLOSE
 TO THE METER AS POSSIBLE, ON PRIVATE
 PROPERTY. SECTION 608.13.2 AND MUNICIPAL
 ORDINANCE 2853-95.
 ****NO RESPONSE, NOT ADDRESSED
  
 9. SHT P3.2 FULL OPEN VALVES SHALL BE
 INSTALLED ON THE BASE OF EVERY WATER
 RISER PIPE, AND ON THE TOP OF EVERY
 WATER DOWN-FEED PIPE. SECTION 606.1(3) & 606.1(4).
 ****RESPONSE NOTED, BUT THE VALVES ARE NOT SHOWN ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE AS REQUIRED. ***CHECK
 BOAF INTERPRETATIONS AND IT INDICATED THE VALVES ARE
 FOR "UPSIDE DOWN RISERS MORE THAN ONE FLOOR"
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By kstevens Date 2006-08-22 Time 09:54 Rev Time 0.00
Received By kstevens Date 2006-08-21 Time 18:50 Sent To  
Notes
2006-08-22 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 NFPA 99C
  
 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 OF THE ARCHITECTURAL BUSINESS ON THE
 TITLE BLOCK DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE RECORDS AT DBPR. (SEE
 ATTACHED SHEET). PER FAC 61G1-16.004(1)
 THE ADDRESS MUST BE SHOWN IN THE TITLE
 BLOCK. FS 481-2055.
  
 2. ALL ARCHITECTURAL SHEETS. THE SEAL
 SHALL CONTAIN THE REGISTRATION NUMBER OF
 THE ARCHITECT. NO NUMBER HAS BEEN
 IMPRESSED ON THE SHEETS IN THE SEAL. FAC 61G1-16.002(1)
 & FS 481.2055.
  
 3. SHTS A2.01 & A2.02 THE FIRST FLOOR
 FINISH SCHEDULE FOR ROOMS 103, 104, 118,
 (WOMEN, UNISEX HDCP, & MEN TOILET ROOMS)
 AS WELL AS ROOMS 202, 205, 208, & 210
 TOILET ROOMS INDICATE PAINTED MR GWB FOR
 THE WALLS. PLEASE SHOW HOW THIS COMPLIES
 WITH SECTION 1210.2 REQUIREMENTS FOR
 WALLS TO BE HARD & NON-ABSORBENT.
  
 4. SHT A2.01 THE BREAK ROOM SINK AND SHT
 A2.02 THE STAFF LOUNGE SINK SHALL BE
 ACCESSIBLE. SUBMIT DETAILS SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 (FORWARD APPROACH REQUIRED,
 AND NO CABINET DOORS ALLOWED IN CLEAR
 FLOOR SPACE).
  
 5. SHT A6.01 UNISEX TOILET ROOM - 104
 SHOW THE CLEAR FLOOR SPACE FOR THE W/C
 AND LAV, AND SHOW THE TURNING AREA.
 SECTIONS 11-4.16.2, 11-4.16.3, AND
 11-4.22.3.
  
 6. SHT A6.01 DETAILS 1, 2, 3, & TOILET
 ACCESSORY LEGEND REFERENCE COMPLIANCE
 WITH 1997 EDITION ACCESSIBILITY. DESIGN
 REQUIRED TO BE COMPLIANT WITH FBC-2004
 CHAPTER 11. PLEASE CHANGE REFERENCE.
  
 7. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 FOR THE DRINKING FOUNTAINS.
  
 8. SHTS P3.1 & P3.2 AND RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE AS CLOSE
 TO THE METER AS POSSIBLE, ON PRIVATE
 PROPERTY. SECTION 608.13.2 AND MUNICIPAL
 ORDINANCE 2853-95.
  
 9. SHT P3.2 FULL OPEN VALVES SHALL BE
 INSTALLED ON THE BASE OF EVERY WATER
 RISER PIPE, AND ON THE TOP OF EVERY
 WATER DOWN-FEED PIPE. SECTION 606.1(3) & 606.1(4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status F Date 2008-03-13 Cont ID  
Sent By choops Date 2008-03-13 Time 10:46 Rev Time 0.00
Received By choops Date 2008-03-13 Time 10:46 Sent To  
Notes
2008-03-13 10:54:16***FAILED - REVISION - ADDING PATIO STRUCTURE WITH
 GUARDRAIL ON ROOFTOP***
  
  
 1)PROVIDE A RECORDED UNITY OF TITLE, UNIFYING PCN
 #74-43-43-05-01-023-0020 AND PCN
 #74-43-43-05-01-023-0040.
  
 2)CLARIFY SCOPE OF WORK.IS COVERED PATIO STRUCTURE
 EXISTING OR PROPOSED?IF PROPOSED, PLANS SHALL
 INDICATE HOW THE STRUCTURE COMPLIES WITH THE REAR
 SETBACK REQUIREMENT OF 15 FEET FROM THE PROPERTY LINE.
  
 3)PROVIDE A DATA TABLE SHOWING THE PROPOSED
 ADDITIONAL SQUARE FOOTAGE WITH THE EXISTING, REQUIRED
 PARKING, AND PROVIDED PARKING.
  
 4)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE PROPOSED WORK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 4 Status P Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 09:27 Rev Time 0.00
Received By choops Date 2008-02-25 Time 09:27 Sent To B
Notes
2008-02-25 09:28:16***APPROVED - REVISION - SUBMITTING SIDEWALK PLAN***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-01-31 Cont ID  
Sent By choops Date 2008-01-31 Time 08:23 Rev Time 0.00
Received By choops Date 2008-01-31 Time 08:23 Sent To  
Notes
2008-01-31 08:24:21***FAILED - REVISION - ADDING COVERED PATIO***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE PROPOSED, WITH SETBACK DIMENSIONS TO THE
 PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 2 Status N Date 2007-02-16 Cont ID  
Sent By kdfreema Date 2007-02-16 Time 13:14 Rev Time 0.00
Received By kdfreema Date 2007-02-16 Time 13:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-28 Cont ID  
Sent By mmclean Date 2006-10-28 Time 12:10 Rev Time 0.00
Received By mmclean Date 2006-10-28 Time 12:10 Sent To  
Notes
2006-10-28 12:35:39DENIED,
 1. PLEASE INDICATE IF THE GENERATOR WILL BE LOCATED IN
 AN ASSIGNED PARKING SPACE.
 2. PLEASE PROVIDE THE APPROVED PARKING COUNT FOR THE
 LOCATION AND THE AMOUNT OF PARKING THAT IS EXISTING.
 GENERATOR MUST BE SCREENED FROM THE VIEW OF THE
 PUBLIC.
 3. PLEASE INDICATE IF THERE WILL BE A CHANGE OF
 OCCUPANCY AND WHAT THAT CHANGE WILL BE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved