Plan Review Details - Permit 06071649
Plan Review Stops For Permit 06071649
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-23 Cont ID  
Sent By lmartine Date 2007-08-23 Time 17:41 Rev Time 0.00
Received By lmartine Date 2007-08-23 Time 17:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-27 Cont ID  
Sent By lmartine Date 2007-06-27 Time 10:59 Rev Time 0.00
Received By lmartine Date 2007-06-27 Time 10:59 Sent To  
Notes
2007-06-27 11:04:37DENIED
  
 AGAIN !, PLEASE PROVIDE INFORMATION FOR THE BASE PAD
 AND THE FASTENING METHOD FOR THE GENERATOR.
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-27 Cont ID  
Sent By alange Date 2006-09-27 Time 09:00 Rev Time 0.50
Received By alange Date 2006-09-27 Time 09:00 Sent To  
Notes
2006-09-27 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 08:50 Rev Time 0.50
Received By alange Date 2006-08-18 Time 08:50 Sent To  
Notes
2006-08-18 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 15:12 Rev Time 0.00
Received By btrobaug Date 2007-07-16 Time 14:24 Sent To G
Notes
2007-07-16 14:52:23 

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-05-02 Cont ID  
Sent By btrobaug Date 2007-05-02 Time 12:46 Rev Time 0.50
Received By btrobaug Date 2007-05-02 Time 12:07 Sent To G
Notes
2007-05-02 12:46:48NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE RISER DIAGRAM IS INCOMPLETE, IT DOES NOT SHOW
 THE METER LOCATION IN THE SERVICE. PLEASE LOCATE ALL
 SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. DO THIS ON A SITE
 PLAN, NOT ON THE SURVEY, 106.1.3 FBC. SEE NOTE #2 AND
 3, PREVIOUS REVIEW. THE GENERATOR AND A DISCONNECT ARE
 ALL THAT'S SHOWN.
  
 2} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.THE LOAD CALCULATION THAT WAS SUBMITTED IS
 INCORRECT, SEE 220.31(B) IF USING OPTIONAL. THE HEAT
 LOAD IS AT 100%.
  
 3} THE GENERATOR DOES NOT MEET THE MANUFACTURERS
 RECOMENDED SETBACKS, SEE PAGE 9 OWNERS MANUAL.
  
 4} THE INFORMATION REGARDING THE TRANSFER SWITCH IS
 INSUFFICIENT. INDICATE THAT THE "PANEL SCHEDULE"
 SUBMITTED WITH 16 CIRCUITS IS IN FACT THE CIRCUITS IN
 THE TRANSFER SWITCH OR IN A GENERATOR PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-14 Cont ID  
Sent By btrobaug Date 2006-09-14 Time 15:45 Rev Time 1.00
Received By btrobaug Date 2006-09-14 Time 14:58 Sent To P
Notes
2006-09-14 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.VALUE HAS BEEN INCREASED BY
 REVIEWER, FEE MUST BE PAID PRIOR TO RE
 SUBMITTING FOR REVIEW.
  
  
 1} THE RISER DIAGRAM IS NOT LEGIBLE.
 PLEASE INCREASE THE SIZE OR REDRAW FOR
 CLARITY. 106.1.3 FBC AMMENDED. STILL NOT
 LEGIBLE ENOUGH TO RETAIN FOR RECORDS.
  
 2} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING. CAN'T READ
 RISER. UTILITY CONNECTION NOT INDICATED.
 IS THE TRANSFER SWITCH NOW THE FIRST
 MEANS OF DISCONNECT?
  
 3} PROVIDE A SITE DIAGRAM PER 106.3.5.4
 FBC AS AMMENDED, INCLUDING GENERATOR AND
 RELATED EQUIPMENT AND ALL SERVICE
 EQUIPMENT. SURVEY IS NOT A SITE PLAN.
 ALL EQUIPMENT WAS NOT LISTED ON THE
 "SURVEY" EITHER.
  
 5} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.THE SPECIFICATIONS PROVIDED
 DO NOT ALLOW FOR THE UTILITY TO BE
 DISCONNECTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By btrobaug Date 2006-08-09 Time 11:17 Rev Time 1.00
Received By btrobaug Date 2006-08-09 Time 10:26 Sent To P
Notes
2006-08-09 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
  
 1} THE RISER DIAGRAM IS NOT LEGIBLE.
 PLEASE INCREASE THE SIZE OR REDRAW FOR
 CLARITY. 106.1.3 FBC AMMENDED.
  
 2} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING.
  
 3} PROVIDE A SITE DIAGRAM PER 106.3.5.4
 FBC AS AMMENDED, INCLUDING GENERATOR AND
 RELATED EQUIPMENT AND ALL SERVICE
 EQUIPMENT.
  
 4} INDICATE WHICH MODEL GENERATOR IS
 BEING USED, THE SPEC BOOK IS GENERIC.
  
 5} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-08-01 Cont ID  
Sent By mperson Date 2007-08-01 Time 13:10 Rev Time 0.45
Received By mperson Date 2007-08-01 Time 13:09 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-05-03 Cont ID  
Sent By mperson Date 2007-05-03 Time 10:12 Rev Time 0.45
Received By mperson Date 2007-05-03 Time 10:12 Sent To M
Notes
2007-05-03 10:27:18DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS AND RESIDENTIAL
 GENERATOR PERMITAPPLICATION REQUIREMENTS.
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE GENERATOR DOES NOT MEET THE MANUFACTURER'S
 RECOMENDED SETBACKS, PLEASE REFERENCE PAGE 9 OF OWNERS
 MANUAL AND PLEASE REVISE THE SITE PLAN TO REFLECT THE
 MANUFACTURER'S RECOMENDATIONS OF THREE FEET (3') ON THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-09-15 Cont ID  
Sent By mperson Date 2006-09-15 Time 09:07 Rev Time 0.33
Received By mperson Date 2006-09-15 Time 09:07 Sent To B
Notes
2006-09-15 00:00:00******DENIED 2ND TIME*****
  
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW DUE TO THE
 FACT THAT THE PREVIOUS COMMENTS HAVE NOT
 BEEN ADDRESSED:
  
 1. MORE INFOMATION IS REQUIRED ON THE
 TYPE OF MATERIAL THAT IS BEING INDICATED
 ON THE GAS RISER DIAGRAM. WHAT IS "CTS"?
 PLEASE CLARIFY FOR THE RESUBMITTAL.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE INDICATE THE BTU LOAD LOAD
 OF THE GENERATOR ON THE ISOMETRIC RISER
 DIAGRAM FOR THE RESUBMITTAL.
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER CUT
 SHEETS OF THE 1ST AND 2ND STAGE
 REGULATORS.
 4.PLEASE INDICATE WHICH MODEL GENERATOR
 IS BEING USED IN THE MANUFACTURER
 ISTALLATION AND OWNERS MANUAL ON PAGE 6
 SO THAT THE GENERATOR BTU LOADS CAN BE
 VERIFIED.
 5. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: THERE ARE NO MEASUREMENTS
 INDICATED ON THE SURVEY COMPLYING WITH
 NFPA 58, PLEASE ADD THE MEASUREMENTS FOR
 THE RESUBMITTAL.
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By mperson Date 2006-08-10 Time 15:47 Rev Time 0.45
Received By mperson Date 2006-08-10 Time 15:47 Sent To M
Notes
2006-08-10 00:00:00REFERENCE: GAS PERMIT #06071651

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 10:10 Sent To E
Notes
2007-05-01 10:11:22TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 10:59 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 10:59 Sent To Z
Notes
2007-04-24 11:00:12TO "Z" BOX/RESUB--NEW SHEETS FOR "Z" AND "M"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 14:17 Sent To E
Notes
2006-08-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:18 Sent To E
Notes
2006-08-07 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 08:50 Rev Time 0.00
Received By alange Date 2006-07-28 Time 14:37 Sent To  
Notes
2006-07-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By tgordon Date 2007-08-02 Time 08:17 Rev Time 0.20
Received By tgordon Date 2007-08-02 Time 08:17 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 08:45 Rev Time 0.20
Received By tgordon Date 2007-05-04 Time 08:45 Sent To B
Notes
2007-05-04 08:47:04*** DENIED ***
 1) SEE GAS REVIEW NOTE #1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 16:26 Rev Time 0.15
Received By tgordon Date 2006-08-11 Time 16:26 Sent To B
Notes
2006-08-11 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 08:52 Rev Time 0.00
Received By choops Date 2007-08-02 Time 08:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By choops Date 2007-04-30 Time 14:21 Rev Time 0.00
Received By choops Date 2007-04-30 Time 14:21 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 14:28 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 14:28 Sent To I
Notes
***NONE***