Plan Review Details - Permit 06071495
Plan Review Stops For Permit 06071495
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-31 Cont ID  
Sent By lursu Date 2006-07-31 Time 16:15 Rev Time 0.00
Received By lursu Date 2006-07-31 Time 16:15 Sent To  
Notes
2006-07-31 00:00:00UPDATE OWNER INFO USING PAPA

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-25 Cont ID  
Sent By lmartine Date 2007-04-25 Time 18:35 Rev Time 0.00
Received By lmartine Date 2007-04-25 Time 18:35 Sent To  
Notes
2007-04-25 18:43:52 
 TRUSS ENGINEERING TO BE APPROVED BEFORE INSTALLATION
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-13 Cont ID  
Sent By lmartine Date 2007-03-13 Time 17:42 Rev Time 0.00
Received By lmartine Date 2007-03-13 Time 17:41 Sent To  
Notes
2007-03-13 17:51:30 
 BUILDING REVIEW COMMENTS
  
  
  
 TRUSS ENGINEEERING AND LAYOUT ARE REQUIRED TO BE
 APPROVED BY JACK HAWK, ARCHITECT OF RECORD AND SIGNED
 AND SEALED BY TRUSS CO. ENGINEER.
  
 ENERGY CALC'S SUBMITTED REQUIRES SIGNATURE AND DATE
 FROM THE OWNER OR AN AGENT.
  
 N.O.C. HAS EXPIRED , PLEASE RE-CERTIFY ,AFTER ,THE
 NEXT REVIEW CYCLE IS COMPLETED.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By amorse Date 2006-10-23 Time 10:25 Rev Time 0.00
Received By amorse Date 2006-10-23 Time 10:25 Sent To PC
Notes
2006-10-23 10:44:56 
  
 DENIED
  
 2ND REVIEW
  
 1) OK
 2) OK
 3) OK
  
 4) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 5) OK
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
  
 11) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
 **********PLEASE SEE MECH REVIEW NOTES***********
  
 NEW REVIEW NOTES:
  
 1) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 2) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 PLEASE SUBMIT FL# 539-R1 FOR JELD-WEN DOORS, FL# 183-R1
 FOR GAF SHINGLES AND FL#7149 FOR THE DAB GARAGE DOOR
  
 3) PRODUCT APPROVALS FOR THE KINCO WINDOWS STATE THEY
 ARE NON IMPACT AS A RESULT IMPACT PROTECTION IS
 REQUIRED. ALSO PLEASE STATE THE TYPE OF GLASS THAT WILL
 BE USED AS SOME TYPES DO NOT MEET THE REQUIRED DESIGN
 PRESSURES
  
 4) REMOVE INCORRECT INFORMATION ON THE WINDOW SCHEDULE
 PAGE A/3 ( WRONG NOA#, IMPACT GLAZING, DESIGN
 PRESSURES,ETC)
  
 5) SHUTTERS REQUIRE A KEY PLAN, SHUTTER SCHEDULE AND
 THE DRAWINGS THAT ARE PART OF THE PRODUCT APPROVALS
 CLEARLY MARKED WITH THE INFORMATION SPECIFIC TO THE
 SITE (TYPE OF CONSTRUCTION, MOUNTING METHOD, ANCHOR
 TYPE, ETC.) PLEASE SEE THE ATTACHED MEMO AND SCHEDULE
  
 6) NO PRODUCT APPROVAL WAS RESUBMITTED FOR THE SLIDING
 GLASS DOOR
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By mperson Date 2006-08-04 Time 09:23 Rev Time 0.00
Received By amorse Date 2006-08-08 Time 06:55 Sent To PC
Notes
2006-08-08 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) A TITLE BLOCK WITH THE INFORMATION
 SPECIFIED PER 61G1-16.004 FAC SHALL BE
 PRESENT ON DRAWINGS ISSUED BY THE
 RESPONSIBLE ARCHITECT AND MUST,AT A
 MINIMUM CONTAIN
 1)FIRM NAME,ADDRESS, AND TELEPHONE #
 2)FIRM LICENCE #
 3)NAME OF PROJECT
 4)DATE PREPARED
 5)A SPACE FOR SIGNATURE & DATED SEAL
 6)A SPACE FOR PRINTED NAME AND LICENCE#
 OF PERSON SEALING THE DOCUMENT
  
 4) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 5) PROVIDE A SITE PLAN THAT SHOWS
 DRAINAGE IN COMPLIANCE WITH THE
 REQUIREMENTS OF R403.1
  
 6) MINIMUM DESIGN LOADS ON DRAWINGS
 REFERENCED TO ASCE 7-98, PLEASE SEE
 REFFERENCE ADOPTED BY THE 2004 FBC IS
 ASCE 7-02. DRAWINGS TO REFLECT THIS SEE
 A/3, A/4 AND A/6
  
 7) GENERAL NOTES A/6 STATE R30
 INSULATION IN CEILING ABOVE CONDITIONED
 SPACE BUT WALL SECTION SHOWS R19 PLEASE
 CLARIFY
  
 8) PROVIDE SILL DETAIL
  
 9) DRAWINGS SHOW TOP OF BEAM AT 8'-2"
 BUT GARAGE DOOR IS A 7'-0" AND THE
 LINTEL PC-1 IS 24" DEEP PLEASE CLARIFY.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 11) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. PLEASE SUBMIT ON FORM
 600A-2004 AND BE SURE CEILING INSULATION
 VALUE MATCHES DRAWINGS
  
 12) THE FOLLOWING PRODUCT APPROVALS
 REQUIRE CORRECTIONS
 A) THURMA-TRU DOES NOT HAVE STATE
 APPROVAL FOR THIS PRODUCT (WILL GIVE
 MIAMI-DADE NOA A LOCAL PROD. APPROVAL)
 B) GARAGE DOOR DESIGN PRESSURE DOES NOT
 MEET THE DESIGN PRESSURE IN THE DOOR
 SCHEDULE
 C) TIMBERLINE SELECT 40 SHINGLE NOA HAS
 BEEN REVISED (04-0305.04)
 D) KINCO NOA FOR SGD HAS EXPIRED SEE
 STATE APPROVAL CLICK ON PDF FILE AND
 PRINT INSTALLATION FOR 1X BUCK AND 2X
 BUCK BOTH ARE GOOD TO -70 PSF (FLORIDA
 SHEET OK)
 E) STATE PRODUCT APPROVAL DOES NOT COVER
 M40 XHP ONLY HP PLEASE SUBMIT REVISED
 MIAMI-DADE NOA (06-0413.06) FOR LOCAL
 PROD APPROVAL
  
 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 (PLEASE CHECK CORRECTED COPIES)
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-11 Cont ID  
Sent By dpalmer Date 2007-01-11 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2007-01-11 Time 15:10 Sent To M
Notes
2007-01-11 15:26:29*** REDLINED PLANS***
  
  
 1) RISER STILL SHOWS OCP FOR AHU AT 35A, WHERE 424.4B
 REQUIRES 125% MIN. PLEASE SEE PANEL SCHEDULE SHOWS 50A
 BREAKER.
 2) PLEASE ALSO SEE CODE REQUIRES SMOKE ALARMS.NFPA-72
 11.5.1.1, 11.8.3

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 19:57 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 19:01 Sent To M
Notes
2006-10-13 19:57:17******** UNSAT2ANDREVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTES DUE TO
 CHANGES MADE TO PLANS FROM PREVIOUS REVIEW.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW WITH NEW ADDED TO BOTTOM OFREVIEW.
  
 1) NOTE:OK.
  
 2) NOTE:NO, PLEASE SEE ALL SEALS ON ALL SHEETS ON
 BOTH SETS SHALL BE CLEAR AND VISIBLE AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE AND FLORIDA STATUES AS
 PREVIOUSLY NOTED. THIS IS REQUIRED AS THE SEALS ARE NOT
 CLEAR. PLEASE OBTAIN NEW SEAL IF NEEDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TITLE BLOCKS
 CONTAIN ALL INFORMATION AS REQUIRED BY
 FAC 61G1-16.004. PLEASE SEE MISSING THE
 PRINTED NAME AND LICENSE NUMBER OF SAID
 ARCHITECT.
 PLEASE ALSO BE SURE ALL SEALS ARE
 RAISED, CLEAR AND VISABLE WITH ALL
 INFORMATION ON SAID SEALS. PLEASE SEE
 THAT MANY OF THE SEALS ARE NOT CLEAR.
 FS 481.221
  
 3)NOTE: NO, NOTHING SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9. FBC 106.1.2
  
 4) NOTE: NO, PLEASE SEE AS NOTED ON PREVIOUS REVIEW,
 424.3B. MIN OCP REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE AND COMPLETE
 INFORMATION FOR AHU KW RATING. PLEASE
 SEE LOAD CALCS INDICATE 100% = 6500VA ,
 YET THE OCP AND CONDUCTOR SIZES LEND TO
 THIS AS A 10KW HEAT STRIP? PLEASE
 CORRELATE AS THE MECH SHEETS SHOW
 ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE
 KW RATING IS SET.
 424.3B.,220,310.16,240.4 ETC
  
 5) NOTE:NO, PLEASE SEE NOTE STILL MENTIONS TO WIRE
 INTO KITCHEN LIGHTING CIRCUIT ALTHOUGH NEW NOTE WAS
 ADDED.
 THIS COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING
 BACK FOR CORRECTIONS AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE IDICATE ALL CIRCUITS ON
 PANELS WHICH ARE REQUIRED TO CONTAIN ARC
 FAULT PROTECTION. PLEASE SEE NOTES FOR
 ARC FAULT MENTIONS ONLY RECEPTS, LTS AND
 FANS. (NO FANS SHOWN ) ALTHOUGH
 PROTECTION OF SD'S IS ALSO REQUIRED.
 PELASE SEE NOTE ABOVE MENTIONS AND PLANS
 SHOWS SD'S CIRCUITED TO KITCHEN AND BATH
 RM LIGHTING, WHICH IS OK, HOWEVER THIS
 CIRCUIT WOULD ALSO REQUIRED ARC FAULT
 PROTECTION.
 210.12B, 408.4
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK, HOWEVER SEE NEW NOTE.
  
 ** PREVIOUS NEWNOTE **
 PLEASE SEE MISSING GFI RECEPT
 FOR CU. 210.63,210.8A2
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 ** NEW NOTES **
  
 12) NOTE: PLEASE SEE NOTE" ** IMPORTANT** "NOTE BELOW
 WHICH WAS AT THE END OF THE PREVIOUS REVIEW NOTES WHICH
 ASKED FOR ALL OLD SHEETS TO BE REMOVED. PLEASE SEE THIS
 WAS NOT DONE. PLEASE DO SO BEFORE RESUBMITTING PLANS
 FOR NEXT REVIEW AS THIS WILL HELP IN NOT DELAYING
 PROJECT.
 ** NOTED PREVIOUS REVIEW**
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE, PLANS WILL BE
 PICKED UP FOR CORRECTIONS. PLEASE KNOW,
 BEFORE RESUBMITTING PLANS, ALL
 OLD/VOIDED SHEETS MUST BE COMPLETELY
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS SHOULD BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONLY ONE
 COPY OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED SEAPARATELY FOR REFERENCE.
  
 13) NOTE: PLEASE SEE THE NEW GFI RECEPT REQUIRED FOR
 THE OUTSIDE CU WHICH WAS ADDED TO THESE PLANS IS BEING
 SHOWN CIRCUITED TO THE #1, WHICH ALSO FEEDS THE AHU.
 MAY NOT BE TAPPED FROM THIS 220VA CIRCUIT .
 310.16,240.4., 240.21 ETC
  
 14) NOTE: PLEASE SEE THE RECORDED NOTICE OF COMMENCMENT
 SUBMITTED IS NO LONGER VALID AS IS HAS EXCEEDING THE
 90DAYS SINCE BEING RECORD AND WORK HAS NOT COMMENCED.
 PLEASE SEE FS 713.13(2). PLEASE KNOW, THE RECORDED NOC
 IS ONLY REQUIRED AFTER PERMIT IS ISSUED AND BEFORE
 PICKING UP PERMIT.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL SHEETS FROM EACH
 SUBMITTED SET IS BEING RETAINED BY THIS OFFICE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 18:46 Sent To M
Notes
2006-07-27 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES ARE REFELCTED ON ELECTRICAL PLANS
 AT A MINIMUM. NFPA-70 2002 (NEC) AND
 NFPA-72 2002.
 PLEASE SEE PLANS MENTIONS , "LATEST
 EDITIONS", HOWEVER THE LATEST EDITIONS
 ARE NOT YET ADOPTED BY THE STATE OF
 FLORIDA.
  
 2) NOTE: PLEASE BE SURE TITLE BLOCKS
 CONTAIN ALL INFORMATION AS REQUIRED BY
 FAC 61G1-16.004. PLEASE SEE MISSING THE
 PRINTED NAME AND LICENSE NUMEBR OF SAID
 ARCHIECT.
 PLEASE ALSO BE SURE ALL SEALS ARE
 RAISED, CLEAR AND VISSABLE WITH ALL
 INFORMATION ON SAID SEALS. PLEASE SEE
 THAT MANY OF THE SEALS ARE NOT CELAR.
 FS 481.221
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9. FBC 106.1.2
  
 4) NOTE: PLEASE CORRELATE AND COMPLETE
 INFORMATION FOR AHU KW RATING. PLEASE
 SEE LOAD CALCS INDICATE 100% = 6500VA ,
 YET THE OCP AND CONDUCTOR SIZES LEND TO
 THIS AS A 10KW HEAT STRIP? PLEASE
 CORRELATE AS THE MECH SHEETS SHOW
 ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE
 KW RATING IS SET.
 424.3B.,220,310.16,240.4 ETC
  
 5) NOTE: PLEASE IDICATE ALL CIRCUITS ON
 PANELS WHICH ARE REQUIRED TO CONTAIN ARC
 FAULT PROTECTION. PLEASE SEE NOTES FOR
 ARC FAULT MENTIONS ONLY RECEPTS, LTS AND
 FANS. (NO FANS SHOWN ) ALTHOUGH
 PROTECTION OF SD'S IS ALSO REQUIRED.
 PELASE SEE NOTE ABOVE MENTIONS AND PLANS
 SHOWS SD'S CIRCUITED TO KITCHEN AND BATH
 RM LIGHTING, WHICH IS OK, HOWEVER THIS
 CIRCUIT WOULD ALSO REQUIRED ARC FAULT
 PROTECTION.
 210.12B, 408.4
  
 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 SPECIFIC TO ALL AREAS. IE LIVING RM
 RECEPTS, BATH LTS, BEDRM #3, ETC.
 408.4
 IT IS KNOW TO THIS OFFICE THESE WILL
 MOST LIKELY BE REVISED DURING
 CONSTRUCTION.
  
 7) NOTE: PLEASE SEE A CIRCUIT #17 SEEM
 TO BE IN THE CLOSET IN BEDRM #2 WHICH
 DOES NOT SEEM TO FEED ANYTHING?
 PLEASE CLARIFY.
 106.1.2
  
 8) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR CU. 210.63,210.8A2
  
 9) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR KITCHEN COUNTER SPACE. 210.52C1,
 210.8A6
  
 10) NOTE: PLEASE SEE MISSING RECEPTS FOR
 MORE THAN 2' OF WALL SPACE.
 210.52
 *REDLINED**
  
 11) NOTE: PLEASE CLARIFY SERVICE. IS
 THIS A SEPARATE METER OR A METERMAIN
 COMBO?
 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE, PLANS WILL BE
 PICKED UP FOR CORRECTIONS. PLEASE KNOW,
 BEFORE RESUBMITTING PLANS, ALL
 OLD/VOIDED SHEETS MUST BE COMPLETELY
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS SHOULD BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONLY ONE
 COPY OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED SEAPARATELY FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:25 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:25 Sent To M
Notes
2007-04-04 17:25:54TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:53 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:53 Sent To Z
Notes
2007-04-02 17:53:18TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 17:01 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 17:01 Sent To E
Notes
2007-01-09 17:02:15TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 15:39 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 15:39 Sent To Z
Notes
2006-12-27 15:40:02TO "Z" BOX/RESUB--PLANS TO INCOMING TODAY, PLEASE SEE
 FRONT SCREEN NOTES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 09:55 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 09:55 Sent To E
Notes
2006-10-12 09:55:40TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 13:13 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 13:13 Sent To Z
Notes
2006-10-05 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-08 Time   Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 13:26 Sent To  
Notes
2006-07-27 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-05 Cont ID  
Sent By tgordon Date 2007-04-05 Time 08:29 Rev Time 0.25
Received By tgordon Date 2007-04-05 Time 08:29 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-01-12 Cont ID  
Sent By tgordon Date 2007-01-12 Time 12:00 Rev Time 0.45
Received By tgordon Date 2007-01-12 Time 12:00 Sent To P
Notes
2007-01-12 12:03:12*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 08:59 Rev Time 0.30
Received By tgordon Date 2006-10-16 Time 08:59 Sent To P
Notes
2006-10-16 09:19:55*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) 10" RETURN AIR TRANSFER DUCT TO
 MASTER SUITE IS TO SMALL, SEE NOTE #3
 PLEASE CORRECT.
  
 3) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 14:41 Rev Time 0.45
Received By tgordon Date 2006-07-28 Time 14:41 Sent To P
Notes
2006-07-28 00:00:00*** DENIED ***
 1) MECHANICAL PLANS NEED THE JOB ADDRESS
 ON THEM.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) SEE CONDENSER DETAIL, 18GA. STRAP IS
 NOT PERMITTED, MUST USE CLIPS, PLEASE
 CORRECT.
  
 4) MECHANICAL PLANS MUST ALSO HAVE ON
 THEM THE A/C EQUIPMENT LISTING WITH ALL
 THE PERTINENT INFORMATION.
  
 5) CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 , PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-16 Cont ID  
Sent By mperson Date 2007-01-16 Time 11:36 Rev Time 0.33
Received By mperson Date 2007-01-16 Time 11:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 13:42 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 13:42 Sent To B
Notes
2006-10-21 13:46:17SEALS ON PLANS ARE NOT CLEAR SEE ELECTRICAL PLAN REVIEW
 NOTE # 2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By mperson Date 2006-08-04 Time 08:55 Rev Time 0.33
Received By mperson Date 2006-08-04 Time 08:55 Sent To B
Notes
2006-08-04 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) PLEASE SEE ELECTRICAL COMMENT #2.
 2) PER FBC-2004 PLUMBING SECTION 708.9
 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS.
 NOTE: CLEANOUT TO WASHING MACHINE SHALL
 BE LOCATED 4' AFF. PLEASE SEE SHEET A-5
 CORRECTED ISOMETRIC PLUMBING RISER
 DIAGRAM IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 4 Status P Date 2007-04-04 Cont ID  
Sent By jroach Date 2007-04-04 Time 15:58 Rev Time 0.00
Received By jroach Date 2007-04-04 Time 15:58 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-01-07 Cont ID  
Sent By jroach Date 2007-01-07 Time 16:17 Rev Time 0.00
Received By jroach Date 2007-01-07 Time 16:17 Sent To I
Notes
2007-01-07 16:18:51***FAILED***
  
 1) REAR SETBACK SHALL BE A MINIMUM OF 9 FEET (10% OF
 THE LOT DEPTH).
  
 2) A MINIMUM OF 75 PERCENT OF THE FRONT YARD SHALL BE
 LANDSCAPED.THE SIZE OF THE PROPOSED DRIVEWAY WILL
 NEED TO BE REDUCED AS INSUFFICIENT LANDSCAPING IS BEING
 PROPOSED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-11 Cont ID  
Sent By jroach Date 2006-10-11 Time 11:36 Rev Time 0.00
Received By jroach Date 2006-10-11 Time 11:36 Sent To I
Notes
2006-10-11 11:38:32***FAILED***
  
 1) THE DIMENSIONS OF THE PROPOSED DRIVEWAY AND WALKWAY
 NEED TO BE SHOWN ON THE SURVEY.
  
 2) AT LEAST 75% FO THE FRONT YARD (FIRST 25 FEET) SHALL
 BE LANDSCAPING.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By mmclean Date 2006-07-27 Time 16:11 Rev Time 0.00
Received By mmclean Date 2006-07-27 Time 16:11 Sent To E
Notes
2006-07-27 00:00:00DENIED,
 1. THE PROPOSED STRUCTURE MUST BE 25FT
 FROM THE FRONT SETBACK.
 2. NEED TO PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY & WALKWAY (LENGTH &
 WIDTH)
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 3. THE PROPOSED CONCRETE PATIO SHOULD BE
 SHOWN ON THE FLOOR PLAN A-2
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720