Plan Review Details - Permit 06071461
Plan Review Stops For Permit 06071461
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-20 Cont ID  
Sent By lmartine Date 2007-03-20 Time 18:50 Rev Time 0.00
Received By lmartine Date 2007-03-20 Time 18:50 Sent To  
Notes
2007-03-20 18:50:31INTERIOR WALL REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-30 Cont ID  
Sent By rnuquist Date 2006-10-30 Time 18:32 Rev Time 0.00
Received By rnuquist Date 2006-10-30 Time 18:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-20 Cont ID  
Sent By amorse Date 2006-10-20 Time 11:01 Rev Time 0.00
Received By amorse Date 2006-10-20 Time 11:01 Sent To PC
Notes
2006-10-20 11:10:41 
  
 DENIED
  
 1) ENERGY CALC'SSECTION 9A, EXTERIOR WOOD WALLS REQUIRE
 R11 INSULATION VALUE PLEASE CORRECT AND RESUBMIT. BLOCK
 STEM WALL IS NOT APPLICABLE
  
 2) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 3) IF NO FURTHER CORRECTIONS ARE TO BE MADE TO DRAWING
 PLEASE SUBMIT 2 COMPLETE CORRECTED COPIES FOR REVEIW
 AND STAMPING WITH ONE LOOSE COPY OF ANY OLD/VOIDED
 SHEETS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By amorse Date 2006-08-18 Time 14:38 Rev Time 0.00
Received By amorse Date 2006-08-18 Time 14:38 Sent To PC
Notes
2006-08-18 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) IN AREAS OF QUESTIONABLE SOILS AS
 SHOWN IN THE OFFICIAL ZONING MAP OF THE
 CITY OF WEST PALM BEACH, 2 COPIES OF A
 SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4
  
 4) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
 *****NOTE THE CALC'S THAT WERE SUBMITTED
 HAVE WRONG INFORMATION 8B IS NOT
 APPLICABLE BECAUSE FLOOR TYPE IS 8A AND
 WALL TYPE IS WOOD FRAME AND REQUIRES
 R-11, PLEASE CORRECT*****
  
 5) CONTRACTOR DID NOT SIGN APPLICATION
  
 6) PRODUCT APPROVAL FOR WINDOWS
 INCORRECT, FLORIDA COVER SHEET FOR
 TR-9100 WINDOWS NOT 240 AS MIAMI-DADE
 NOA. IF USING 240 WINDOWS THE CORRECT
 FL# IS 6738 AND THE MIAMI-DADE REPORT
 THAT ACCOMPANIES THE COVER IS 05-0930.03
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-05 Cont ID  
Sent By dpalmer Date 2007-03-05 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2007-03-05 Time 16:22 Sent To B
Notes
2007-03-05 18:06:43PLANS ROUTED TO LUIS M.
  
 RETAINED FILE COPY OF ELECTRICAL PLANS

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-12 Cont ID  
Sent By dpalmer Date 2007-02-12 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2007-02-12 Time 12:31 Sent To PC
Notes
2007-02-12 14:58:12 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THE REVISIONS SUBMTTED ARE T DATED
 10/23/06., HOWEVER THERE ARE SEVERAL REVISIONS TO THE
 EXISTING DWELLING. PLANS INDICATE THE ENITER DWELLING
 BEING REWIRED. PLEASE SEE THAT ANY REVISIONS AFTER THAT
 DATE WOULD BE REFLECTED ON TITLE BLOCKS AND THEN THE
 PLANS LABELED WITH THE SAME NUMERICAL DESIGANTION.
 PLEASE CORRELATE AND SUBMIT REVISIONS AS NEEDED.
 106.1, 106.3.5.4
  
 2) NOTE: PLEASE SEE THE PANEL SCHEDULE SUBMITED IS THE
 SAME AS THE PREVIOUS PANEL SCHEDULE ISSUED FOR PERMIT.
 PLEASE LABEL ALL NEW CIRCUITS, ARC FAULT FOR NEW WIRED
 BEDROOMS, DEDICATED FOR BATH, ETC
 210.52, 210.12, 210.11C3.
 PLEASE SEE PANEL SCHEDULE SHALL BE ROOM AND AREA
 SPECIFIC. PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM
 THE CODE COMMENTARY.
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE SEE THAT AS THE SCOPE OF WORK FROM THE
 ORIGINAL PERMITTED SET OF PLANS HAS INCREASED, PLEASE
 ADJUST THE VALUE FROM THE APPLIED SCOPE OF WORK AND PAY
 ADDITIONAL FEES.
 PLEASE SEE THAT REVISED BUILDING SHOULD ALSO BE
 SUBMITTED FOR NEW WALL AREA.
 FBC 108.3
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-29 Cont ID  
Sent By dpalmer Date 2006-10-29 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2006-10-29 Time 10:49 Sent To B
Notes
2006-10-29 11:05:08PLANS ROUTED TO LUIS MARTINEZ, AS PREVIOUS BUILDING
 REVIEW IS NO LONGER HERE.
2006-10-29 11:03:40REDLINED**
  
  
 CROSSED OUT OLD ELECTRICAL ON PREVIOUS SHEET 3OF 4,
 SHEETS FOR PLUMBING ONLY.
 NEW SHEETS 3OF 4 CROSSED OUT PLUMB, SEE PREVIOUS
 NOTE/SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 20:29 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 20:16 Sent To M
Notes
2006-10-15 20:29:44** UNSAT 2ND REVIEW ***
  
 PLEASE SEE ONE NOTE FROM PREVIOUS REVIEW AND NEW
 NOTE(S).
  
 1) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE
 PLANS NOW SHOWS A J-BOX WHERE RISER SHOWS AND NEW MAIN
 DISCONNECT??
 FBC 106.1.2, NEC 2002
  
 2) NOTE: PLEASE PLACE PLANS INTO TWO COMPLETE SETS
 ATTACHED AND BOTH SIGNED BY THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN.
 FBC 106.1.2, 106.1.3
  
 3) NOTE: PLEASE SEE A/ C LOAD IN LOAD CALCS STILL
 MENTIONS "COMP" , HOWEVER THE HEAT IS THE LARGER OF THE
 TWO LOADS. 220.21.
 PLEASE CORRELATE.
  
 4) NOTE: PLEASE SEE ALL THREE COPIES OF SURVEY'S HAVE
 BEEN "VOIDED" AS THEY DO NOT CONTAIN AN ORIGINAL
 SIGNATURE AND SEAL AS REQUIRED UNDER FAC 61G17, FS
 472.025. PLEASE SEE STATEMENT ON SURVEY EVEN SAYS NOT
 VALID W/OUT SEAL.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 07:07 Sent To M
Notes
2006-08-09 00:00:00IN ELEC FOR REVIEW, IN PROGRESS.
 *** UNSAT ****
  
 1) NOTE: PLEASE SEE CODE REFERENCED IN
 NOTES MENTIONS THE 1996 NEC?
 PLEASE SEE THIS SHOULD READ 2002 NEC.
  
 2) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. (REDLINED)
  
 3) NOTE: PLEASE SEE RISER DOES NOT SEEM
 TO CORRELATE WITH PLANS AND PANEL NOTE.
 PLEASE SEE RISER SHOWS THIS AS A NEW
 PROPOSED SERVICE WITH A NEW MAIN LOCATED
 OUTSIDE ,PLANS DO NOT SHOW ANY MAIN AND
 PANEL NOTE MENTIONS THIS IS EXSITING.
 PLEASE EXPLAIN HOW THE SERVICE IS
 EXISTING AS SHOWN AS THE ADDITION HAS
 NOT YET BEEN BUILT?
 PLEASE CORRELATE AND REVISE AS NEEDED.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING SHOWN WITH
 THE SEC'S. PLEASE SEE 250.24B, 250.6 FOR
 OBJECTIONABLE CURRENTS AND THE
 "EQUIPMENT GROUNDING CONDUCTOR" BEING
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
 5) NOTE: PLEASE SEE MISSING A/C CU
 DISCONNECT PER 440.11.
  
 6) NOTE: PLEASE SE EMISSING GFI RECEPT
 FOR CU. 210.63,210.8A.
  
 7) NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH INDICATE THE CU AT THE LOAD LARGER
 THAN HEAT AT 8KW, YET THE AHU'S HEAT IS
 THE 8KW WHICH IS LARGER.
 PLEASE ADJUST.
 PLEASE SEE 220.21, 220.30C
  
 8) NOTE: PLEASE SEE MISSING KITCHEN
 COUNTER SPACE GFI RECEPT REQUIRED PER
 210.52C1, 210.8A6
  
 9) NOTE: PLEASE SEE WALL SPACE IN
 KITCHEN WHICH IS 2' OR MORE IS REQUIRED
 TO CONTAIN A RECEPT. PLEASE SEE
 210.52B1, 210.11C1, AS THIS IS REQUIRED
 OT BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS.
  
 10) NOTE: PLEASE SEE PLANS IDNICATE A
 NEW DISPOSAL, HOWEVER THIS COULD NOT BE
 LOCATED ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS.
  
 11) NOTE: PLEASE SE MIN OCP FOR THE AHU
 SHALL BE SIZED AT 125% PER 424.3B.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS INNEW SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 15:01 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 15:01 Sent To E
Notes
2007-03-03 15:01:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 15:27 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 15:27 Sent To E
Notes
2007-02-09 15:28:05TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 10:33 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 10:33 Sent To E
Notes
2006-10-26 10:33:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 19:58 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 19:58 Sent To E
Notes
2006-10-10 19:58:47TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 17:01 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 17:01 Sent To Z
Notes
2006-10-05 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:22 Sent To E
Notes
2006-08-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-18 Time   Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 10:29 Sent To  
Notes
2006-07-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 09:46 Rev Time 0.20
Received By tgordon Date 2006-10-16 Time 09:46 Sent To P
Notes
2006-10-16 09:48:18NO NEW MECH. PLANS SUBMITTED
 STAMPED MECH. PLANS FROM LAST
 REVIEW STILL WITH SET.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-09 Cont ID  
Sent By tgordon Date 2006-08-09 Time 09:02 Rev Time 0.30
Received By tgordon Date 2006-08-09 Time 09:02 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By jleech Date 2006-10-20 Time 07:22 Rev Time 0.00
Received By jleech Date 2006-10-20 Time 07:22 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By jleech Date 2006-08-14 Time 07:10 Rev Time 0.00
Received By jleech Date 2006-08-14 Time 07:10 Sent To B
Notes
2006-08-14 00:00:00DENIED;
 SANITARY RISER DIAGRAM;THE WASHER AND
 KITCHEN SINK CANNOT RUN THRU THE
 BATHROOM GROUP. FBC-2004 PLUMBING SCE.
 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-10 Cont ID  
Sent By jroach Date 2006-10-10 Time 09:52 Rev Time 0.00
Received By jroach Date 2006-10-10 Time 09:52 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 11:58 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 11:58 Sent To I
Notes
2006-08-05 00:00:00DENIED,
 1. THE PROPOSED ADDITION MUST BE SHOWN
 ON TWO COPY OF CURRENT SURVEY WITH
 SETBACKS FROM THE SIDE & REAR PROPERTY
 LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720