Plan Review Details - Permit 06071403
Plan Review Stops For Permit 06071403
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 14:06 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 14:06 Sent To M
Notes
2006-08-12 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:19 Sent To M
Notes
2006-08-08 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 11:07 Rev Time 0.00
Received By tgordon Date 2006-07-26 Time 15:00 Sent To  
Notes
2006-07-26 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By tgordon Date 2006-08-16 Time 13:58 Rev Time 0.25
Received By tgordon Date 2006-08-16 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 16:13 Rev Time 0.20
Received By tgordon Date 2006-08-10 Time 16:13 Sent To  
Notes
2006-08-10 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-28-06 NOTE
 #3. TWO 10" RETURN AIR DUCTS IS NOT
 ENOUGH FOR A 3 1/2 TON SUSTEM WITH A 16"
 SUPPLY AIR DUCT, WHITE-OUT MAY NOT BE
 USED ON PLANS, SIGN AND DATE EACH
 CORRECTION ON PLANS AND "ALL" COPYS
 SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 11:00 Rev Time 0.30
Received By tgordon Date 2006-07-28 Time 11:00 Sent To  
Notes
2006-07-28 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 2) JOB ADDRESS NEEDS TO BE ON ALL PLANS
 (ALL PAGES) .
  
 3) TWO 10" RETURN AIR DUCTS IS NOT
 ENOUGH FOR A 3 1/2 TON SUSTEM WITH A 16"
 SUPPLU AIR DUCT, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.