Plan Review Details - Permit 06071402
Plan Review Stops For Permit 06071402
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 17:38 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 17:38 Sent To M
Notes
2006-10-10 17:38:52TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 13:33 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 13:33 Sent To M
Notes
2006-08-12 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:20 Sent To M
Notes
2006-08-08 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-07-28 Time 16:19 Rev Time 0.00
Received By adarroug Date 2006-07-26 Time 15:01 Sent To  
Notes
2006-07-26 00:00:00TTO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-11 Cont ID  
Sent By tgordon Date 2006-10-11 Time 09:05 Rev Time 0.30
Received By tgordon Date 2006-10-11 Time 09:05 Sent To  
Notes
2006-10-11 09:06:08REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By tgordon Date 2006-08-16 Time 14:15 Rev Time 0.30
Received By tgordon Date 2006-08-16 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 16:41 Rev Time 0.20
Received By tgordon Date 2006-08-10 Time 16:41 Sent To  
Notes
2006-08-10 00:00:00*** DENIED ***
 1) WHITE-OUT MAY NOT BE USED ON PLANS,
 SIGN AND DATE EACH CORRECTION ON PLANS
 AND "ALL" COPYS SUBMITTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 11:09 Rev Time 0.30
Received By tgordon Date 2006-07-28 Time 11:09 Sent To  
Notes
2006-07-28 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 2) JOB ADDRESS NEEDS TO BE ON ALL PLANS
 (ALL PAGES) .
  
 3) AHU #3 SUPPLY AIR DUCT TO MIXING BOX
 NEEDS TO BE SIZED.
  
 4) AHU #2 RETURN AIR TRANSFER DUCT
 14'+10" TO MASTER SUITE IS TO SMALL, SEE
 NOTE #6 (A).
  
 5) AHU #2 10" RETURN AIR TRANSFER DUST
 TO AIH HANDLER CLOSET IS TO SMALL, SEE
 NOTE #6 (A).
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.