Plan Review Details - Permit 06071369
Plan Review Stops For Permit 06071369 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-09-17 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-09-17 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-09-17 |
Time |
09:48 |
Sent To |
PC |
|
Notes |
2006-09-17 00:00:00 | | | | | DENIED | | | | 1) PLEASE PROVIDE A KEY PLAN WITH ALL | | OPENINGS THAT WILL BE SHUTTERED AND | | NUMBER ACCORDING TO THE INSTALLATION | | SCHEDULE, ALSO SO THE EMERGENCY MEANS OF | | EGRSS | | | | 2) SHUTTER PERMIT APPLICATIONS REQUIRE A | | KEY PLAN, SHUTTER SCHEDULE AND THE | | DRAWINGS THAT ARE PART OF THE PRODUCT | | APPROVALS CLEARLY MARKED WITH THE | | INFORMATION SPECIFIC TO THE SITE (TYPE | | OF CONSTRUCTION, MOUNTING METHOD, ANCHOR | | TYPE, ETC.) PLEASE SEE THE ATTACHED MEMO | | AND SCHEDULE | | | | 3) NO PERMIT WILL BE ISSUED UNTILL THE | | ALARM FEES ARE PAID TO THE CITY FINANCE | | DEPT | | | | ADRIAN MORSE | | BLDG PLAN REVIEW | | 561-805-6716 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-01 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-08-01 |
Time |
06:47 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-08-01 |
Time |
06:47 |
Sent To |
PC |
|
Notes |
2006-08-01 00:00:00 | | | | | DENIED | | | | 1) PLEASE MARK MIAMI-DADE NOA DRAWING | | WITH THE MOUNTING METHOD, ANCHOR TYPE, | | CONST TYPE (WOOD, CONCRETE, ETC) | | | | 2) PROVIDE THE MEAN ROOF HEIGHT ALONG | | WITH THE SHUTTER SPANS IN ORDER TO | | DETERMINE THE PRESSURES ON THE PROVIDED | | ENGINEERING | | | | 3) MIAMI-DADE NOA 02-0404.01 HAS BEEN | | REVISED NEW NOA 05-1220.12 SHOULD BE | | SUBMITTED | | | | 4) THE PRESSURE THAT WAS INDICATED ON | | THE DRAWING FOR ANCHOR SPACING CANNOT BE | | USED FOR SHUTTER BECAUSE THAT WOULD | | LIMIT THE SPAN TO 6'-0" OR LESS. PLEASE | | USE THE DESIGN PRESSURE THAT IS REQUIRED | | BY THE SUBMITTED ENGINEERING | | | | 5) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-15 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-15 |
Time |
10:09 |
Sent To |
B |
|
Notes |
2006-09-15 00:00:00 | TO "AMORSE" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-08-01 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-27 |
Time |
11:52 |
Sent To |
|
|
Notes |
2006-07-27 00:00:00 | TO "MISC" BOX#1 |
|
|
|
Account Summary | Usage Policy | Privacy Policy